Installation Guide
ECL Comfort 210 / 310, application A214 / A314
MENU > Alarm > Digital S9
MENU > Alarm > Inlet pressure
MENU > Alarm > Outlet pressure
Clear alarm
1x390
Circuit
Setting range
Factory setting
All
*
*
Alarm types 2 (requiring manual reset) can be reset here.
* See Appendix “Parameter ID overview”
OFF:
No alarm present
ON:
Resetting the alarm
An alarm can be cleared (to "OFF").
If the alarm reason still exists, the "OFF" changes to "ON" after 10
seconds (alarm types without delay) or the alarm's delay time (alarm
types with delay).
MENU > Alarm > Air quality
MENU > Alarm > Inlet pressure
MENU > Alarm > Outlet pressure
Alarm high
1x614
Circuit
Setting range
Factory setting
All
*
*
When the measured value gets higher than the set value, the alarm will
be activated.
* See Appendix “Parameter ID overview”
Value:
Set the alarm value
MENU > Alarm > Air quality
MENU > Alarm > Heat recovery
MENU > Alarm > Inlet pressure
MENU > Alarm > Outlet pressure
Alarm low
1x615
Circuit
Setting range
Factory setting
All
*
*
When the measured value gets lower than the set value, the alarm will be
activated.
* See Appendix “Parameter ID overview”
Value:
Set the alarm value
166
DEN-SMT/DK
VI.GU.A2.02