Installation Guide
ECL Comfort 210 / 310, application A214 / A314
MENU > Settings > Fan / acc. control
Acc. cut-in delay (Accessory cut-in delay, relay 2, P2)
1x087
Circuit
Setting range
Factory setting
All
*
*
Set the delay for activating the damper (relay 2, P2).
* See Appendix “Parameter ID overview”
0 ... 900:
Set the delay (in seconds).
A delay in opening the damper can prevent frost damages in the heat
exchanger.
MENU > Settings > Fan / acc. control
Fan output func. (Fan output function, relay 1, F1)
1x088
Circuit
Setting range
Factory setting
All
*
*
Desired function for relay 1 (F1). F1 is typically the fan. The codes have
different meanings.
* See Appendix “Parameter ID overview”
Code:
Description (relay 1 (F1)):
Comfort mode
Saving mode
Frost alarm
0
1
2
3
The connected unit is switched OFF
The connected unit is switched ON
Example, code = 1
:
The fan is ON during Comfort mode. In case of frost alarm, the fan is
switched OFF.
Depending on application, the control of fan F1 can furthermore be
related to:
- Saving mode with or without 'Total stop'
- Setting of 'Fan function'