Installation Guide
ECL Comfort 210 / 310, application A214 / A314
ID
Parameter Name
A214.x
A314.x
Setting range
Factory
Unit
Own settings
11081
Filter constant
3
1 ... 80
50
11082
Accum. filter
4, 5
1, 2, 6, 7
1 ... 250
25
Sec
11086
Fan cut-in delay
1
0 ... 900
5
Sec
-||-
2, 3, 4, 5
1, 2
0 ... 900
30
Sec
-||-
6
0 ... 900
0
Sec
-||-
3
0 ... 900
10
Sec
-||-
4, 5, 6, 7
0 ... 900
60
Sec
-||-
9
0 ... 900
20
Sec
11087
Acc. cut-in delay
1, 2, 3, 4, 5, 6
1, 2, 3, 4, 5, 6, 7, 9
0 ... 900
0
Sec
11088
Fan output func.
1, 2, 3, 4, 5
1, 2, 3, 4, 5, 6, 7, 9
0 ... 3
1
-||-
6
0 ... 3
3
11089
Acc. output func.
1, 2, 3, 4, 5, 6
1, 2, 3, 4, 5, 6, 7, 9
0 ... 3
1
11090
Optional function
1, 3
3
0 ... 3
0
-||-
2
0 ... 2
0
-||-
4, 5
1, 2
0 ... 4
0
-||-
6
0 ... 3
3
11091
Acc. time control
1, 2, 3, 4, 5, 6
1, 2, 3
1 ... 2
1
-||-
4, 5, 6, 7, 9
1 ... 3
1
11093
Frost pr. T
2, 4
1
0 ... 40
6
°C
-||-
4, 5, 6, 7, 9
5 ... 40
10
°C
11105
Infl. - min.
2, 3, 4, 5
1, 2, 3, 4, 5, 6, 7, 9
0.0 ... 9.9
2.0
-||-
6
0.0 ... 9.9
0.0
11107
Adapt. time
2, 3, 4, 5, 6
1, 2, 3, 4, 5, 6, 7, 9
OFF, 1 ... 50
OFF
Sec
11108
Limit T frost
2, 3, 4, 5, 6
1, 2, 3
0 ... 50
10
°C
-||-
4, 5, 6, 7, 9
0 ... 50
12
°C
11137
Fan function
2, 3, 4, 5, 6
1, 2
OFF ; ON
OFF
-||-
3, 4, 5, 6, 7, 9
OFF ; ON
ON
11140
Comp. T select
1, 2, 3, 4, 5, 6
1, 2, 3
OFF ; ON
ON
11141
Ext. input
1, 2, 3, 4, 5, 6
3
OFF ; S1 ; S2 ; S3 ;
S4 ; S5 ; S6 ; S7 ; S8
OFF
-||-
1, 2
OFF ; S1 ; S2 ; S3 ;
S4 ; S5 ; S6 ; S7 ; S8
; S9 ; S10
OFF
-||-
4, 5, 6, 7, 9
OFF ; S1 ; S2 ; S3
; S4 ; S5 ; S6 ; S7 ;
S8 ; S9 ; S10 ; S11
; S12 ; S13 ; S14 ;
S15 ; S16
OFF
11142
Ext. mode
1, 2, 3, 4, 5, 6
1, 2, 3, 4, 5, 6, 7, 9
COMFORT ;
SAVING
COMFORT
11147
Upper difference
2, 3, 4, 5, 6
1, 2, 3, 4, 5, 6, 7, 9
OFF, 1 ... 30
OFF
K
11148
Lower difference
2, 3, 4, 5, 6
1, 2, 3, 4, 5, 6, 7, 9
OFF, 1 ... 30
OFF
K
11149
Delay
2, 3, 4, 5, 6
1, 2, 3, 4, 5, 6, 7, 9
1 ... 99
10
Min
11150
Lowest temp.
2, 3, 4, 5, 6
1, 2, 3, 4, 5, 6, 7, 9
10 ... 50
30
°C
204
DEN-SMT/DK
VI.GU.A2.02
Danfoss District Energy