Installation Guide
ECL Comfort 210 / 310, application A214 / A314
MENU > Settings > Flow temperature
MENU > Settings > Inlet temperature
Des. T Comfort
1x018
Circuit
Setting range
Factory setting
All
*
*
Setting of desired flow temperature when the ECL controller is in comfort
mode.
* See Appendix “Parameter ID overview”
This setting has no influence if the controller receives an external value
for the desired flow temperature.
MENU > Settings > Flow temperature
MENU > Settings > Inlet temperature
Des. T Saving
1x019
Circuit
Setting range
Factory setting
All
*
*
Setting of desired flow temperature when the ECL controller is in saving
mode.
* See Appendix “Parameter ID overview”
This setting has no influence if the controller receives an external value
for the desired flow temperature.
MENU > Settings > Flow temperature
MENU > Settings > Inlet temperature
Temp. min. (duct / flow / inlet temp. limit, min.)
1x177
Circuit
Setting range
Factory setting
All
*
*
* See Appendix “Parameter ID overview”
Set the min. duct / flow / inlet temperature for the system. The
desired duct / flow / inlet temperature will not be lower than this
setting. Adjust the factory setting, if required.
‘Temp. min.’ is overruled if 'Total stop' is active in Saving mode or
'Cut-out' is active.
‘Temp. min.’ can be overruled by the influence from the return
temperature limitation (see 'Priority').
The setting for ‘Temp. max.’ has higher priority than ‘Temp. min.’.
MENU > Settings > Flow temperature
MENU > Settings > Inlet temperature
Temp. max. (duct / flow / inlet temp. limit, max.)
1x178
Circuit
Setting range
Factory setting
All
*
*
* See Appendix “Parameter ID overview”
Set the max. flow / duct / inlet temperature for the system. The
desired temperature will not be higher than this setting. Adjust
the factory setting, if required.
The setting of ‘heat curve’ is possible for heating circuits only.
The setting for ‘Temp. max.’ has higher priority than ‘Temp. min.’.
118
DEN-SMT/DK
VI.GU.A2.02