Installation Guide
ECL Comfort 210 / 310, application A214 / A314
MENU > Settings > Fan / acc. control
Optional function (relay 3, X3)
1x090
Circuit
Setting range
Factory setting
All
*
*
Desired function for relay 3 (X3). The codes have different meanings.
* See Appendix “Parameter ID overview”
Code:
0
1
2
3
4
A214.1
Pu-cool
Sch-1
Sch-2
Cool dem.
A214.2
Pu-heat
Sch-1
Sch-2
A214.3
Pu-heat
Sch-1
Sch-2
Room stat.
A214.4
Pu-heat
Sch-1
Sch-2
Cool dem.
Pu-cool
A214.5
Pu-heat
Sch-1
Sch-2
Cool dem.
Pu-cool
A214.6
Pu-heat
Sch-1
Sch-2
Room stat.
A314.1
Pu-heat
Sch-1
Sch-2
Cool dem.
Pu-cool
A314.2
Pu-heat
Sch-1
Sch-2
Cool dem.
Pu-cool
A314.3
Pu-heat
Sch-1
Sch-2
Room stat.
Pu-cool:
Control of circulation pump in cooling circuit
Pu-heat:
Control of circulation pump in heating circuit
Sch-1:
Follows Schedule 1
Sch-2:
Follows Schedule 2
Cool-dem.:
ON at cooling demand
Room stat.:
Room thermostat function
MENU > Settings > Fan / acc. control
Acc. time control (Accessory time control, relay 2, P2)
1x091
Circuit
Setting range
Factory setting
All
*
*
The connected unit can follow schedule 1 or schedule 2.
* See Appendix “Parameter ID overview”
1:
Relay 2 follows schedule 1.
2:
Relay 2 follows schedule 2.
Danfoss District Energy
VI.GU.A2.02
DEN-SMT/DK
145