Installation Guide
ECL Comfort 210 / 310, application A214 / A314
A214.1 example b
Ventilation system with cooling and constant room temperature control. Chiller has constant flow.
S 3
S 4
S 5
M2
X3
F1
S 8
S 1
D
a
n
fo
s
s
8
7
H
2
1
1
4
.1
2
ECL 210 / 310
A1
Setting advice:
Set desired room temperature, for example 20 °C.
Set desired balance temperature, for example 12 °C.
If a room temperature sensor is not connected, the desired duct temperature at S3 will correspond to the desired room temperature.
A214.1 example c
Ventilation system (fan coils) with cooling and constant room temperature control
S 4
F1
F1
S 1
D
a
n
fo
s
s
8
7
H
2
1
1
5
.1
2
ECL 210 / 310
A1
S 3
M2
X3
S 5
Setting advice:
Set desired room temperature, for example 5 °C.
Set desired balance temperature, for example 1 °C.
If a room temperature sensor is not connected, the desired flow temperature at S3 will correspond to the desired room temperature.
26
DEN-SMT/DK
VI.GU.A2.02
Danfoss District Energy