Installation Guide
ECL Comfort 210 / 310, application A214 / A314
MENU > Settings > Application
MENU > Settings > Fan / acc. control
Stop difference
1x194
Circuit
Setting range
Factory setting
All
*
*
When the difference between outdoor temperature and room temperature
gets higher than the set value, the related function is enabled.
* See Appendix “Parameter ID overview”
Application A214.6:
8
7
H
1
4
8
1
.1
0
D
a
n
fo
s
s
X
Y
# 3 #
# 2 #
# 1 #
#
4 #
# 5 #
X
=
Time
Y
=
Temperature
# 1 #
=
Desired room temperature
# 2 #
=
'Room T diff.' (ID 1x027)
# 3 #
=
'Stop diff.' (ID 1x194)
# 4 #
=
Room temperature
# 5 #
=
X3 status
Application A314.4 . . . A314.7:
8
7
H
1
4
8
4
.1
0
D
a
n
fo
s
s
X
Y
# 3 #
# 2 #
# 1 #
#
4 #
X
=
Time
Y
=
Temperature
# 1 #
=
'Stop diff.' (ID 1x194)
# 2 #
=
Room temperature
# 3 #
=
Outdoor temperature
# 4 #
=
Night cooling possible / not possible
Danfoss District Energy
VI.GU.A2.02
DEN-SMT/DK
147