Installation Guide
ECL Comfort 210 / 310, application A214 / A314
MENU > Settings > Application
MENU > Settings > Control par. 2
1. step level
1x368
Circuit
Setting range
Factory setting
All
*
*
The total control range is covered by M2 within the set % value.
* See Appendix “Parameter ID overview”
MENU > Settings > Application
MENU > Settings > Control par. 2
2. step level
1x369
Circuit
Setting range
Factory setting
All
*
*
From the set % value and up to 100 %, the control is covered by M1.
* See Appendix “Parameter ID overview”
MENU > Settings > Control par., fan
MENU > Settings > Control par., inlet
MENU > Settings > Control par., outlet
X1
1x406
Circuit
Setting range
Factory setting
All
*
*
Definition of which voltage value corresponds to which pressure value.
The voltage (as a 0 - 10 volt signal) comes from a pressure transmitter and is
applied to the relevant input.
This input voltage is converted to display a pressure value (in Pascal).
See also "Pressure" and "X2".
* See Appendix “Parameter ID overview”
X
=
Volt
Y
=
Pressure
# 1 #
=
'X1'
138
DEN-SMT/DK
VI.GU.A2.02
Danfoss District Energy