Installation Guide
ECL Comfort 210 / 310, application A214 / A314
Heating with room temperature and air pressure control
(continued)
Ventilation during saving period:
A desired reduced pressure can be set.
•
Room temperature signal must be present
•
The night damper P8 will open
•
The fan V2 will operate at reduced speed
•
The fan V3 is OFF
•
P2 is OFF
•
M2 is OFF
Summer cut-out:
When outdoor temperature exceeds a selectable value, the heating
system closes totally.
M1 is 3-point controlled, whereas M2 is 0-10 V controlled.
For a description of alarms, compensation temperature, return
temperature limitation (S5) and frost protection (S6 and S7), please
read the section ‘A214 and A314 in general’.
Danfoss District Energy
VI.GU.A2.02
DEN-SMT/DK
15