Installation Guide
ECL Comfort 210 / 310, application A214 / A314
MENU > Settings > Application
Send desired T
1x500
Circuit
Setting range
Factory setting
All
*
*
When the controller acts as a slave controller in a master / slave system,
information about the desired flow temperature can be sent to the master
controller via the ECL 485 bus.
* See Appendix “Parameter ID overview”
OFF:
Information about the desired flow temperature is not
sent to the master controller.
ON:
Information about the desired flow temperature is sent
to the master controller.
In the master controller, 'Demand offset' must be set to a value in order
to react on a desired flow temperature from a slave controller.
When the controller acts as a slave, its address must be 1, 2, 3 ... 9 in
order to send the desired temperature to the master (see the section
‘Miscellaneous’, ‘Several controllers in the same system’).