Installation Guide
ECL Comfort 210 / 310, application A214 / A314
MENU > Settings > Compensation 2
Infl. - max. (compensation temp., 2. point)
1x066
Circuit
Setting range
Factory setting
All
*
*
Determines how much the desired flow / duct temperature will be influenced
if the compensation temperature is higher than the set limit.
* See Appendix “Parameter ID overview”
Influence higher than 0:
The desired flow / duct temperature is increased, when the
compensation temperature gets above the set limit.
Influence lower than 0:
The desired flow / duct temperature is decreased, when the
compensation temperature gets above the set limit.
Example
The limit value is set to 25 °C.
‘Infl. max.' is set to 2.5.
The actual compensation temperature is 28 °C (3 degrees above limit
value).
The desired flow / duct temperature is changed by 2.5 x 3 = 7.5
degrees.
MENU > Settings > Compensation 2
Infl. - min. (compensation temp., 2. point)
1x067
Circuit
Setting range
Factory setting
All
*
*
Determines how much the desired flow / duct temperature will be influenced
if the compensation temperature is lower than the set limit.
* See Appendix “Parameter ID overview”
Influence higher than 0:
The desired flow / duct temperature is increased, when the
compensation temperature gets below the set limit.
Influence lower than 0:
The desired flow / duct temperature is decreased, when the
compensation temperature gets below the set limit.
Example
The limit value is set to 25 °C.
‘Infl. min.’ is set to 0.5.
The actual compensation temperature is 23 °C (2 degrees below the
limit value).
Result:
The desired flow / duct temperature is changed by 0.5 x 2= 1.0 degree.
128
DEN-SMT/DK
VI.GU.A2.02