Installation Guide
ECL Comfort 210 / 310, application A214 / A314
MENU > Alarm > Frost T
Alarm value
1x676
Circuit
Setting range
Factory setting
All
*
*
When the actual temperature, measured by S6, gets below the set value, the
frost alarm will be activated.
* See Appendix “Parameter ID overview”
Value:
Set the alarm value
An activated frost alarm opens the control valve fully, closes the
damper, starts the circulation pump and stops the fan.
MENU > Alarm > Digital S10
Alarm value
1x696
Circuit
Setting range
Factory setting
All
*
*
A differential pressure switch can be connected to the S10 input. When the
differential pressure, measured by the differential pressure switch, gets
above the set value, the S10 input will be activated.
The alarm can be activated when the contacts in the differential pressure
switch open or close.
* See Appendix “Parameter ID overview”
0:
The alarm is activated when the contacts in the
differential pressure switch close.
1:
The alarm is activated when the contacts in the
differential pressure switch open.
MENU > Alarm > Digital S10
Alarm time-out
1x697
Circuit
Setting range
Factory setting
All
*
*
The alarm is activated when the alarm reason has been present for a longer
time (in seconds) than the set value.
* See Appendix “Parameter ID overview”
Value:
Set the alarm time-out