Installation Guide
ECL Comfort 210 / 310, application A214 / A314
MENU > Settings > Fan / acc. control
MENU > Settings > Flow / power limit
MENU > Settings > Wind influence
Filter constant
1x081
Circuit
Setting range
Factory setting
All
*
*
The filter constant dampens the measured input data by the set factor.
* See Appendix “Parameter ID overview”
Minor
value:
Minor dampening (low filter constant)
Major
value:
Major dampening (high filter constant)
MENU > Settings > Fan / acc. control
MENU > Settings > Flow temperature
Control voltage
1x104
Circuit
Setting range
Factory setting
All
*
Output voltage in relation to measured wind speed.
* See Appendix “Parameter ID overview”
The measured and converted wind speed signal controls the
output signal 'Control voltage'. Typically, the higher the wind
speed, the higher the 'control voltage' for the fan speed.
Push the dial to see the graph and enter the value sets for the wind
speed values (0 and 10 m/s) and control voltage.
Control voltage: 0.0 ... 10.0 V
Fixed wind speed settings: 0 (zero) m/s and 10 m/s.
Factory settings: (0 , 2.0) and (10 , 10.0).
This means that the ‘Control voltage’ is 2.0 volt at 0 m/s and 10.0
volt at 10 m/s.
Typically, the higher the wind speed, the higher the 'Control
voltage'.
Example: Relationship between displayed wind speed and control voltage
Control voltage
10. 0
2.0
0
10
Wind
speed
(m/s)
This example shows that 0 (zero) m/s corresponds to 2.0 volt and 10 m/s
corresponds to 10.0 volt.
The 'Control voltage' is only available from the internal module ECA 32.
Danfoss District Energy
VI.GU.A2.02
DEN-SMT/DK