Service Settings Menu, Maintenance Menu
SiME341909EA
54
Part 3 Remote Controller
∗
1: Displays suction air temperature after correction for all models.
∗
2: Displays temperature only for applicable models.
∗
3: Displays floor temperature used for control (including correction) when the round flow with
sensing is connected.
∗
4: Displays control temperature (temperature near the person when the round flow with
sensing is connected).
∗
5: Displays suction air temperature after correction when the round flow with sensing is
connected.
∗
6: Areas mean four areas shown on the below.
∗
7: For human presence detection rate (%), human motion is recognized by digital output
ranging from 0 to 5 V. (5 V is output when no human presence is detected, and 0 V is output
when human presence is detected.)
Reference
(1) 0% detection rate: Human presence is not detected at all.
(2) 25% detection rate: Human presence is detected, but the sensor does not recognize human
presence.
(3) 50% detection rate: The sensor recognizes human presence (small human motion).
(4) 75% detection rate: The sensor recognized human presence (large human motion).
(5) 100% detection rate: The sensor constantly outputs 0 V. Continuing this condition will
display an error.
∗
8: Directly displays a measured value sent from the adaptor PCB.
Maintenance
Menu
Item 2
Remarks
Addressed
Sensor
Value
Unit No.: 0 - 15
Select the unit number you want to check.
Code
00:
01:
02:
03:
04:
05:
06:
07:
08:
09:
22:
23:
24:
25:
26:
Remote controller thermistor (°C)
Suction air thermistor (°C)
∗
5
Heat exchanger liquid pipe thermistor (°C)
Heat exchanger gas pipe thermistor (°C)
Indoor unit address No.
Outdoor unit address No.
BS unit address No.
Zone control address No.
Cooling/Heating batch address No.
Demand/low-noise address No.
Displays human presence detection rate (%) (see
∗
7) in
Area 1 (see
∗
6). Display value × 10%. Displays
15
for
units with no sensing type mounted.
Displays human presence detection rate (%) (see
∗
7) in
Area 2 (see
∗
6). Display value × 10%. Displays
15
for
units with no sensing type mounted.
Displays human presence detection rate (%) (see
∗
7) in
Area 3 (see
∗
6). Display value × 10%. Displays
15
for
units with no sensing type mounted.
Displays human presence detection rate (%) (see
∗
7) in
Area 4 (see
∗
6). Display value × 10%. Displays
15
for
units with no sensing type mounted.
Infrared sensor (°C) (See
∗
8). Displays – for units with
no sensing type mounted.
Data
The corresponding data will be displayed, based on the
Unit No. and Code selected.
2
4
3
1
80 cm above the floor
Detection areas of presence sensor
(Corresponding to the punched mark
on the inner frame of the panel:
~
)
Summary of Contents for VRV X RXQ6-48ANR Series
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ6 48A N R Series SiME341909EA...
Page 289: ...SiME341909EA Wiring Diagrams Part 7 Appendix 283 RXQ10 12ARYFK 2D124184...
Page 290: ...Wiring Diagrams SiME341909EA 284 Part 7 Appendix RXQ14 16ARYFK 2D124183...
Page 295: ...SiME341909EA Wiring Diagrams Part 7 Appendix 289 FXMQ40 50 63 80 100ARV1 3D127112 04 59...