![background image](http://html1.mh-extra.com/html/daikin/vrv-x-rxq6-48anr-series/vrv-x-rxq6-48anr-series_service-manual_4705220285.webp)
SiME341909EA
Check
Part 6 Service Diagnosis
279
Indoor unit
FXFSQ-AR, FXMQ-PB
FXDQ-PD, FXDQ-ND
Orange (1)
Red (2)
Yellow
(3)
Black (4)
Gray (6)
—
(5)
Orange (1)
Gray (6)
Yellow (3)
φ
1
φ
3
Red (2)
Black (4)
φ
2
φ
4
M
Measuring points
Judgment criteria
1-2
No continuity
1-3
92
Ω
1-6
46
Ω
2-4
92
Ω
2-6
46
Ω
(1) White
(2) Yellow
(3) Orange
(4) Blue
(6) Red
(5) —
White (1)
Red (6)
Orange (3)
φ
1
φ
3
Yellow
(2)
Blue
(4)
φ
2
φ
4
M
Measuring point
Judgment criteria
1-2
No continuity
1-3
92
Ω
1-6
46
Ω
2-4
92
Ω
2-6
46
Ω