Troubleshooting by Error Code
SiME341909EA
154
Part 6 Service Diagnosis
L1 - 42
IPM error: Compressor M2C (Slave 2)
The inverter PCB may be defective or a PCB other than
the specified is mounted.
Refer to the
L1
flowchart and make a diagnosis based
on the Error code shown to the left.
L1 - 43
Defective current sensor: Compressor M2C (Slave 2)
L1 - 44
Current offset: Compressor M2C (Slave 2)
L1 - 45
IGBT error: Compressor M2C (Slave 2)
L1 - 46
Jumper settings error: Compressor M2C (Slave 2)
L1 - 47
Power supply voltage abnormality: Compressor M1C
(Master)
L1 - 48
Power supply voltage abnormality: Compressor M2C
(Master)
L1 - 49
Power supply voltage abnormality: Compressor M1C
(Slave 1)
L1 - 50
Power supply voltage abnormality: Compressor M2C
(Slave 1)
L1 - 51
Power supply voltage abnormality: Compressor M1C
(Slave 2)
L1 - 52
Power supply voltage abnormality: Compressor M2C
(Slave 2)
L2 - 01
Momentary power failure (Master)
Refer to the
L2
flowchart and make a diagnosis based
on the Error code shown to the left.
L2 - 02
Momentary power failure (Slave 1)
L2 - 03
Momentary power failure (Slave 2)
L2 - 04
Power ON (Master)
L2 - 05
Power ON (Slave 1)
L2 - 06
Power ON (Slave 2)
L4 - 01
Radiation fin temperature rise: Inverter PCB for M1C
(Master)
Refer to the
L4
flowchart and make a diagnosis based
on the Error code shown to the left.
L4 - 02
Radiation fin temperature rise: Inverter PCB for M1C
(Slave 1)
L4 - 03
Radiation fin temperature rise: Inverter PCB for M1C
(Slave 2)
L4 - 06
Radiation fin temperature rise: Fan M1F (Master)
L4 - 07
Radiation fin temperature rise: Fan M2F (Master)
L4 - 09
Radiation fin temperature rise: Inverter PCB for M2C
(Master)
L4 - 10
Radiation fin temperature rise: Inverter PCB for M2C
(Slave 1)
L4 - 11
Radiation fin temperature rise: Inverter PCB for M2C
(Slave 2)
L4 - 18
Radiation fin temperature rise: Fan M1F (Slave 1)
L4 - 19
Radiation fin temperature rise: Fan M2F (Slave 1)
L4 - 20
Radiation fin temperature rise: Fan M1F (Slave 2)
L4 - 21
Radiation fin temperature rise: Fan M2F (Slave 2)
L5 - 03
Current offset error (Master)
Refer to the
L5
flowchart and make a diagnosis based
on the Error code shown to the left.
L5 - 05
Current offset error (Slave 1)
L5 - 07
Current offset error (Slave 2)
L5 - 14
Compressor M2C instantaneous overcurrent (Master)
L5 - 15
Compressor M2C instantaneous overcurrent (Slave 1)
L5 - 16
Compressor M2C instantaneous overcurrent (Slave 2)
L8 - 03
Compressor M1C overcurrent error (Master)
Refer to the
L8
flowchart and make a diagnosis
of the relevant compressor based
on the Error code shown to the left.
L8 - 06
Compressor M1C overcurrent error (Slave 1)
L8 - 07
Compressor M1C overcurrent error (Slave 2)
L8 - 11
Compressor M2C overcurrent error (Master)
L8 - 12
Compressor M2C overcurrent error (Slave 1)
L8 - 13
Compressor M2C overcurrent error (Slave 2)
Error code
Troubleshooting
Description of error
Diagnosis
Summary of Contents for VRV X RXQ6-48ANR Series
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ6 48A N R Series SiME341909EA...
Page 289: ...SiME341909EA Wiring Diagrams Part 7 Appendix 283 RXQ10 12ARYFK 2D124184...
Page 290: ...Wiring Diagrams SiME341909EA 284 Part 7 Appendix RXQ14 16ARYFK 2D124183...
Page 295: ...SiME341909EA Wiring Diagrams Part 7 Appendix 289 FXMQ40 50 63 80 100ARV1 3D127112 04 59...