Check
SiME341909EA
276
Part 6 Service Diagnosis
FXDQ-PD, FXDQ-ND
1. Turn OFF the power supply.
2. Measure the resistance between phases of U, V, W at the motor side connectors (3-core
wire) to check that the values are according to the judgment criteria and there is no short
circuiting, while connector or relay connector is disconnected.
Model
Judgment criteria
Black-Red
Black-White
FXDQ20-32PD
81.0
Ω
± 10%
102
Ω
± 10%
FXDQ40ND
81.0
Ω
± 10%
102
Ω
± 10%
FXDQ50/63ND
44.0
Ω
± 10%
44.0
Ω
± 10%
Red
White
Black
W
V
U
Measure the resistance
values between phases
U,V,W.