Outline of Control (Indoor Unit)
SiME341909EA
76
Part 4 Functions and Control
8.7 Drain Pump Control
8.7.1 Normal Operation
The float switch is ON in normal operation.
When cooling operation starts (thermostat ON), the drain pump turns ON simultaneously.
After the thermostat turns OFF, the drain pump continues to operate for another 5 minutes.
The aim of residual operation after thermostat OFF is to eliminate the dew that condenses
on the indoor heat exchanger during cooling operation.
8.7.2 If the Float Switch is OFF with the Thermostat ON in Cooling
Operation
When the float switch turns OFF, the thermostat turns OFF simultaneously.
After the thermostat turns OFF, the drain pump continues to operate for another 5 minutes.
∗
1: If the float switch turns ON again during the residual operation of the drain pump, cooling
operation also turns on again (thermostat ON).
∗
2: If the float switch remains OFF even after the residual operation of the drain pump has
ended, the error code
A3
is displayed on the remote controller.
The drain pump turns OFF once residual operation has ended, then turns ON again after 5
seconds.
∗
3: After
A3
is displayed and the unit comes to an abnormal stop, the thermostat will remain
OFF even if the float switch turns ON again.
Float s
w
itch
Error display
Thermostat
(r
u
nning)
OFF
OFF
O
N
O
N
O
N
OFF
Drain p
u
mp
O
N
OFF
5 min.
OFF
OFF
ON
ON
ON
OFF
ON
OFF
5 min.
5 min.
5 sec.
Float switch
Error display
Thermostat
(running)
Drain pump
A3
∗
1
∗
3
∗
2
5 sec.
Summary of Contents for VRV X RXQ6-48ANR Series
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ6 48A N R Series SiME341909EA...
Page 289: ...SiME341909EA Wiring Diagrams Part 7 Appendix 283 RXQ10 12ARYFK 2D124184...
Page 290: ...Wiring Diagrams SiME341909EA 284 Part 7 Appendix RXQ14 16ARYFK 2D124183...
Page 295: ...SiME341909EA Wiring Diagrams Part 7 Appendix 289 FXMQ40 50 63 80 100ARV1 3D127112 04 59...