SiME341909EA
Troubleshooting with Remote Controller
Part 6 Service Diagnosis
145
4.3 BRC4M Series
When the air conditioner stops in emergency, the operating indicator lamp on the indoor unit
starts blinking.
Take the following steps yourself to read the error code that appears on the display. Contact
your local dealer with this code. It will help pinpoint the cause of the trouble, speeding up the
repair.
1. Press the
INSPECTION
button to select the inspection mode “
”.
0
appears on display and blinks.
“UNIT No.” appears.
2. Press
PROGRAMMING TIMER
button and change the unit number.
Press to change the unit number until the indoor unit beeps and perform the following
operation according to the number of beeps.
Number of beeps
3 short beeps.............Perform all steps from 3 to 6.
1 short beep .............Perform 3 and 6 steps.
1 long beep .............Normal state
3. Press
OPERATION MODE SELECTOR
button.
0
on the left-hand of the error code blinks.
4. Press
PROGRAMMING TIMER
button and change the error code.
Press until the indoor unit beeps twice.
5. Press
OPERATION MODE SELECTOR
button.
0
on the right-hand of the error code blinks.
6. Press
PROGRAMMING TIMER
button and change the error code.
Press until the indoor unit makes a long beep.
The error code is fixed when the indoor unit makes a long beep.
7. Reset of the display
Press the
OPERATION MODE SELECTOR
button to get the display back to the normal
state.
1
3 5
7
2 4
6
Summary of Contents for VRV X RXQ6-48ANR Series
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ6 48A N R Series SiME341909EA...
Page 289: ...SiME341909EA Wiring Diagrams Part 7 Appendix 283 RXQ10 12ARYFK 2D124184...
Page 290: ...Wiring Diagrams SiME341909EA 284 Part 7 Appendix RXQ14 16ARYFK 2D124183...
Page 295: ...SiME341909EA Wiring Diagrams Part 7 Appendix 289 FXMQ40 50 63 80 100ARV1 3D127112 04 59...