Troubleshooting by Error Code
SiME341909EA
180
Part 6 Service Diagnosis
5.15 Transmission Error (between Indoor Unit PCB and Auto
Grille Control PCB)
Applicable
Models
FXFSQ-AR (when auto grille panel BYCQ125EASF is installed)
Error Code
C1-06
Method of Error
Detection
The status of communication between the indoor unit PCB (X70A) and the auto grille control
PCB (X12A) is checked with the microcomputer.
Error Decision
Conditions
When transmission communication between the indoor unit PCB and the auto grille control PCB
is not normally performed for a certain period or time or more.
Supposed
Causes
Defective connection of the transmission communication connector between the indoor unit
PCB and the auto grille control PCB
Defective indoor unit PCB
Defective auto grille control PCB
External factors (e.g. noise)