SiME341909EA
Troubleshooting by Error Code
Part 6 Service Diagnosis
209
5.33 Harness Abnormality (between Outdoor Unit Main PCB
and Inverter PCB)
Applicable
Models
All outdoor unit models
Error Code
H3
Method of Error
Detection
Check for the transmission conditions of the following harnesses between the PCBs using
microcomputer:
RXQ6-12AR: Inverter 1
Between X28A (A1P) and X6A (A3P)
RXQ14/16AR: Inverter 2
Between X28A (A1P) and X6A (A3P)
Between X61A (A3P) and X6A (A6P)
Error Decision
Conditions
When normal transmission between PCBs is disabled during the compressor stops running.
Supposed
Causes
Defective connection of harnesses between PCBs
Defective outdoor unit main PCB
Defective inverter PCB (A3P, A6P)
Troubleshooting
Check for the transmission
conditions of the following
jumpers between the PCBs:
• RXQ6-12AR
Between X28A (A1P) and
X6A (A3P)
• RXQ14/16AR
Between X28A (A1P) and
X6A (A3P)
Between X61A (A3P) and
X6A (A6P)
Replace the outdoor unit main
PCB.
Replace the inverter PCB.
RXQ6-12AR: A3P
RXQ14/16AR: A3P, A6P
YES
NO
YES
Complete countermeasures.
Return the relevant harness to
normal.
NO
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Harness error
H3
error recurs.
Summary of Contents for VRV X RXQ6-48ANR Series
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ6 48A N R Series SiME341909EA...
Page 289: ...SiME341909EA Wiring Diagrams Part 7 Appendix 283 RXQ10 12ARYFK 2D124184...
Page 290: ...Wiring Diagrams SiME341909EA 284 Part 7 Appendix RXQ14 16ARYFK 2D124183...
Page 295: ...SiME341909EA Wiring Diagrams Part 7 Appendix 289 FXMQ40 50 63 80 100ARV1 3D127112 04 59...