Field Settings for Indoor Unit
SiME341909EA
98
Part 5 Field Settings and Test Operation
FXFSQ-AR with Designer panel
: Factory setting
FXAQ-AR
: Factory setting
1.4.17 Airflow Direction Setting
Set the airflow direction of indoor units as given in the table below. (Set when sealing material
kit of air discharge outlet has been installed.) The second code No. is factory set to
01
.
: Factory setting
1.4.18 Swing Pattern Settings
Set the flap operation in swing mode.
With the factory swing, flaps facing each other are synchronized to operate, and flaps placed
side by side are set to swing in an opposite direction to agitate airflow to reduce temperature
irregularity.
Conventional swing operation (all direction synchronized swing) can be set onsite.
: Factory setting
Mode
No.
First
Code No.
Second
Code No.
Contents
FXFSQ25-80
(All round outlet)
FXFSQ100-140
(All round outlet)
13 (23)
0
01
Standard
Lower than
2.4 m
Lower than
3.2 m
02
High Ceiling (1)
Lower than
2.7 m
Lower than
3.6 m
03
High Ceiling (2)
Lower than
3.2 m
Lower than
4.2 m
Mode
No.
First Code
No.
Second
Code No.
Contents
13 (23)
0
01
Standard
02
Slightly higher
03
High
Mode
No.
First
Code No.
Second
Code No.
Contents
13 (23)
1
01
4-way airflow
02
3-way airflow
03
2-way airflow
Mode
No.
First
Code No.
Second
Code No.
Contents
13 (23)
2
01
All direction synchronized swing
02
—
03
Facing swing
Summary of Contents for VRV X RXQ6-48ANR Series
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ6 48A N R Series SiME341909EA...
Page 289: ...SiME341909EA Wiring Diagrams Part 7 Appendix 283 RXQ10 12ARYFK 2D124184...
Page 290: ...Wiring Diagrams SiME341909EA 284 Part 7 Appendix RXQ14 16ARYFK 2D124183...
Page 295: ...SiME341909EA Wiring Diagrams Part 7 Appendix 289 FXMQ40 50 63 80 100ARV1 3D127112 04 59...