SiME341909EA
Troubleshooting by Error Code
Part 6 Service Diagnosis
219
Subcode L4-06, 07, 18, 19, 20, 21
YES
Rectify troubles.
NO
Normal?
Continue operation.
Field factor. Heat sink radiation fin
temperature may have risen due to
high outdoor air temperature.
NO
Replace the fan PCB.
RXQ6/8AR: A4P
RXQ10-16AR: A4P, A7P
YES
Turn
ON the power
supply. Does the error
recur when operation
starts?
Check the cooling conditions
of the inverter heat sink.
(1) Is the insulation sheet
(blue) properly fixed?
(2) Is the heat sink properly
fixed with screws?
(3) Error code
U0
is displayed
on the Error History screen.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.