Outline of Control (Indoor Unit)
SiME341909EA
72
Part 4 Functions and Control
8.2.2 With Optional Infrared Presence/Floor Sensor
The thermostat ON/OFF condition is determined by the difference between the remote
controller set temperature and the detected temperature around people.
Normal operation
Cooling operation
Dry operation
When Tro ≤ 24.5°C
When Tro > 24.5°C
ΔT = Detected room temperature – Remote controller set temperature
Tro: Detected room temperature at the start of dry operation
Tr: Determined by the room temperature detected by the thermistor
Control range of temperature around people
When the floor temperature is very low, operation using the temperature around people may
cause the suction air temperature to operate outside of use range.
To avoid the above condition, a limit based on the suction air temperature is set for the use
range of the temperature around people.
Cooling operation
When the floor temperature is lower than suction air thermistor detection temperature
(R1T), R1T will be treated as the control target temperature for operation.
When the temperature around people is 15°C or lower, R1T will be treated as the control
temperature for operation.
Thermostat OFF
Normal operation
(Thermostat ON)
Δ
T ≤
–1.0°C
Δ
T ≥
+
1.0°C
Thermostat OFF
Dry operation
Tr
<
Tro – 1.0°C
Tr
>
Tro + 1.0°C
Thermostat OFF
Dry operation
Tr
<
Tro – 1.5°C
Tr
>
Tro + 0.5°C
Summary of Contents for VRV X RXQ6-48ANR Series
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ6 48A N R Series SiME341909EA...
Page 289: ...SiME341909EA Wiring Diagrams Part 7 Appendix 283 RXQ10 12ARYFK 2D124184...
Page 290: ...Wiring Diagrams SiME341909EA 284 Part 7 Appendix RXQ14 16ARYFK 2D124183...
Page 295: ...SiME341909EA Wiring Diagrams Part 7 Appendix 289 FXMQ40 50 63 80 100ARV1 3D127112 04 59...