SiME341909EA
Outline of Control (Indoor Unit)
Part 4 Functions and Control
81
8.11 Circulation Airflow (FXFSQ-AR only)
Unevenness of room temperature and the startup time are improved by repeating 2-direction
horizontal blow-off and swing alternately.
8.11.1 Initiation Conditions of Circulation Operation
When operation starts (in the startup state)
Circulation airflow operation is performed.
During normal operation
The unit automatically determines operation based on the room temperature condition and time
to switch circulation airflow operation and the normal auto airflow rate and direction (eco full
automatic control).
8.11.2 Operational Concept (Standard Panel)
Cooling
: Factory setting
Circulation airflow operation continues for up to 90 minutes
Set temp.
Target temp.
Δ
t
Circulation airflow
Auto airflow rate and direction
Circulation airflow
Time
Room temp.
Movement pattern
(a)
(b)
(c)
(d)
Appearance
Time (seconds)
13 (23)-14
01: Pattern 1
120
600
120
600
02: Pattern 2
120
600
0
0
03: Pattern 3
0
0
120
600
04: Pattern 4
120
600
120
600
Indicates the horizontal flap is in the position of reducing airflow volume (the flap is inverted).
Summary of Contents for VRV X RXQ6-48ANR Series
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ6 48A N R Series SiME341909EA...
Page 289: ...SiME341909EA Wiring Diagrams Part 7 Appendix 283 RXQ10 12ARYFK 2D124184...
Page 290: ...Wiring Diagrams SiME341909EA 284 Part 7 Appendix RXQ14 16ARYFK 2D124183...
Page 295: ...SiME341909EA Wiring Diagrams Part 7 Appendix 289 FXMQ40 50 63 80 100ARV1 3D127112 04 59...