This data is for reference purposes only.
Thermistor
temperature
(°C)
Resistance (k
Ω
)
Type A
Type B
Type C
–30
363.8
361.7719
–
–25
266.8
265.4704
–
–20
197.8
196.9198
–
–15
148.2
147.5687
–
–10
112.0
111.6578
111.8
–5
85.52
85.2610
85.42
0
65.84
65.6705
65.80
5
51.05
50.9947
51.07
10
39.91
39.9149
39.97
15
31.44
31.4796
31.51
20
24.95
25.0060
25.02
25
19.94
20.0000
20.00
30
16.04
16.1008
16.10
35
12.99
13.0426
13.04
40
10.58
10.6281
10.63
45
8.669
8.7097
8.711
50
7.143
7.1764
7.179
55
5.918
5.9407
–
60
4.928
4.9439
–
65
4.123
4.1352
–
70
3.467
3.4757
–
75
–
2.9349
–
80
–
2.4894
–
85
–
2.1205
–
90
–
1.8138
–
95
–
1.5575
–
100
–
1.3425
–
105
–
1.1614
–
Drawing No.
3SA48018
3SA48019
3S480003
(AD94A045)
3SA48001
(AD87A001)
3S480014
(AD150384)