![background image](http://html1.mh-extra.com/html/daikin/vrv-x-rxq6-48anr-series/vrv-x-rxq6-48anr-series_service-manual_4705220218.webp)
Troubleshooting by Error Code
SiME341909EA
212
Part 6 Service Diagnosis
Note(s)
Reference
∗
1. Error codes and thermistors
CHECK 11
Refer to page 269.
Error
Code
Applicable
Thermistor
RXQ6-12AR
RXQ14/16AR
Electric
symbol
Connector
Electric
symbol
Connector
H9
Outdoor air
R1T
X18A
R1T
X18A
J3
Discharge pipe
thermistor
(for M1C)
R21T
X19A (Group
connector)
R21T
X19A (Group
connector)
Discharge pipe
thermistor
(for M2C)
—
R22T
Compressor body
thermistor (for M1C)
R8T
R8T
Compressor body
thermistor (for M2C)
—
R9T
J5
Suction pipe
R3T
X30A (Group
connector)
R3T
X30A (Group
connector)
J7
Subcooling heat
exchanger liquid pipe
thermistor
R5T
R5T
J8
Heat exchanger
liquid pipe thermistor
R4T
R4T
J9
Heat exchanger gas
pipe thermistor
R6T
R6T