SiME341909EA
Troubleshooting by Error Code
Part 6 Service Diagnosis
153
J9 - 01
Defective subcooling heat exchanger outlet thermistor
(Master)
Refer to the
J9
flowchart and make a diagnosis
of the relevant thermistor based
on the Error code shown to the left.
J9 - 02
Defective subcooling heat exchanger outlet thermistor
(Slave 1)
J9 - 03
Defective subcooling heat exchanger outlet thermistor
(Slave 2)
J9 - 08
Error detection of subcooling heat exchanger outlet
pipe thermistor (Master)
J9 - 09
Error detection of subcooling heat exchanger outlet
pipe thermistor (Slave 1)
J9 - 10
Error detection of subcooling heat exchanger outlet
pipe thermistor (Slave 2)
JA - 06
Defective high pressure sensor: Open (Master)
Refer to the
JA
flowchart and make a diagnosis
of the relevant sensor based
on the Error code shown to the left.
JA - 07
Defective high pressure sensor: Short (Master)
JA - 08
Defective high pressure sensor: Open (Slave 1)
JA - 09
Defective high pressure sensor: Short (Slave 1)
JA - 10
Defective high pressure sensor: Open (Slave 2)
JA - 11
Defective high pressure sensor: Short (Slave 2)
JC - 06
Defective low pressure sensor: Open (Master)
Refer to the
JC
flowchart and make a diagnosis
of the relevant sensor based
on the Error code shown to the left.
JC - 07
Defective low pressure sensor: Short (Master)
JC - 08
Defective low pressure sensor: Open (Slave 1)
JC - 09
Defective low pressure sensor: Short (Slave 1)
JC - 10
Defective low pressure sensor: Open (Slave 2)
JC - 11
Defective low pressure sensor: Short (Slave 2)
L1 - 01
IPM error: Compressor M1C (Master)
The inverter PCB may be defective or a PCB other than
the specified is mounted.
Refer to the
L1
flowchart and make a diagnosis based
on the Error code shown to the left.
L1 - 02
Defective current sensor: Compressor M1C (Master)
L1 - 03
Current offset: Compressor M1C (Master)
L1 - 04
IGBT error: Compressor M1C (Master)
L1 - 05
Jumper settings error: Compressor M1C (Master)
L1 - 07
IPM error: Compressor M1C (Slave 1)
L1 - 08
Defective current sensor: Compressor M1C (Slave 1)
L1 - 09
Current offset: Compressor M1C (Slave 1)
L1 - 10
IGBT error: Compressor M1C (Slave 1)
L1 - 11
IPM error: Compressor M1C (Slave 2)
L1 - 12
Defective current sensor: Compressor M1C (Slave 2)
L1 - 13
Current offset: Compressor M1C (Slave 2)
L1 - 14
IGBT error: Compressor M1C (Slave 2)
L1 - 15
Jumper settings error: Compressor M1C (Slave 1)
L1 - 16
Jumper settings error: Compressor M1C (Slave 2)
L1 - 17
IPM error: Compressor M2C (Master)
L1 - 18
Defective current sensor: Compressor M2C (Master)
L1 - 19
Current offset: Compressor M2C (Master)
L1 - 20
IGBT error: Compressor M2C (Master)
L1 - 21
Jumper settings error: Compressor M2C (Master)
L1 - 22
IPM error: Compressor M2C (Slave 1)
L1 - 23
Defective current sensor: Compressor M2C (Slave 1)
L1 - 24
Current offset: Compressor M2C (Slave 1)
L1 - 25
IGBT error: Compressor M2C (Slave 1)
L1 - 26
Jumper settings error: Compressor M2C (Slave 1)
L1 - 36
EEPROM abnormality: Compressor M1C (Master)
L1 - 37
EEPROM abnormality: Compressor M2C (Master)
L1 - 38
EEPROM abnormality: Compressor M1C (Slave 1)
L1 - 39
EEPROM abnormality: Compressor M2C (Slave 1)
L1 - 40
EEPROM abnormality: Compressor M1C (Slave 2)
L1 - 41
EEPROM abnormality: Compressor M2C (Slave 2)
Error code
Troubleshooting
Description of error
Diagnosis
Summary of Contents for VRV X RXQ6-48ANR Series
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ6 48A N R Series SiME341909EA...
Page 289: ...SiME341909EA Wiring Diagrams Part 7 Appendix 283 RXQ10 12ARYFK 2D124184...
Page 290: ...Wiring Diagrams SiME341909EA 284 Part 7 Appendix RXQ14 16ARYFK 2D124183...
Page 295: ...SiME341909EA Wiring Diagrams Part 7 Appendix 289 FXMQ40 50 63 80 100ARV1 3D127112 04 59...