Troubleshooting by Error Code
SiME341909EA
152
Part 6 Service Diagnosis
H9 - 01
Defective outdoor air thermistor (Master)
Refer to the
H9
flowchart and make a diagnosis based
on the Error code shown to the left.
H9 - 02
Defective outdoor air thermistor (Slave 1)
H9 - 03
Defective outdoor air thermistor (Slave 2)
J3 - 16
Defective discharge pipe 1 thermistor: Open (Master)
Refer to the
J3
flowchart and make a diagnosis
of the relevant compressor based
on the Error code shown to the left.
J3 - 17
Defective discharge pipe 1 thermistor: Short (Master)
J3 - 18
Defective discharge pipe 2 thermistor: Open (Master)
J3 - 19
Defective discharge pipe 2 thermistor: Short (Master)
J3 - 22
Defective discharge pipe 1 thermistor: Open (Slave 1)
J3 - 23
Defective discharge pipe 1 thermistor: Short (Slave 1)
J3 - 24
Defective discharge pipe 2 thermistor: Open (Slave 1)
J3 - 25
Defective discharge pipe 2 thermistor: Short (Slave 1)
J3 - 28
Defective discharge pipe 1 thermistor: Open (Slave 2)
J3 - 29
Defective discharge pipe 1 thermistor: Short (Slave 2)
J3 - 30
Defective discharge pipe 2 thermistor: Open (Slave 2)
J3 - 31
Defective discharge pipe 2 thermistor: Short (Slave 2)
J3 - 38
Defective compressor body thermistor for
M1C: Open (Master)
J3 - 39
Defective compressor body thermistor for
M1C: Short (Master)
J3 - 42
Defective compressor body thermistor for
M1C: Open (Slave 1)
J3 - 43
Defective compressor body thermistor for
M1C: Short (Slave 1)
J3 - 44
Defective compressor body thermistor for
M1C: Open (Slave 2)
J3 - 45
Defective compressor body thermistor for
M1C: Short (Slave 2)
J3 - 47
Defective compressor body thermistor for
M2C: Open (Master)
J3 - 48
Defective compressor body thermistor for
M2C: Short (Master)
J3 - 49
Defective compressor body thermistor for
M2C: Open (Slave 1)
J3 - 50
Defective compressor body thermistor for
M2C: Short (Slave 1)
J3 - 51
Defective compressor body thermistor for
M2C: Open (Slave 2)
J3 - 52
Defective compressor body thermistor for
M2C: Short (Slave 2)
J3 - 56
Discharge pipe warning (Master)
J3 - 57
Discharge pipe warning (Slave 1)
J3 - 58
Discharge pipe warning (Slave 2)
J5 - 01
Defective suction pipe thermistor (Master)
Refer to the
J5
flowchart and make a diagnosis
of the relevant thermistor based
on the Error code shown to the left.
J5 - 03
Defective suction pipe thermistor (Slave 1)
J5 - 05
Defective suction pipe thermistor (Slave 2)
J7 - 06
Defective subcooling heat exchanger liquid pipe
thermistor (Master)
Refer to the
J7
flowchart and make a diagnosis
of the relevant thermistor based
on the Error code shown to the left.
J7 - 07
Defective subcooling heat exchanger liquid pipe
thermistor (Slave 1)
J7 - 08
Defective subcooling heat exchanger liquid pipe
thermistor (Slave 2)
J8 - 01
Defective heat exchanger liquid pipe thermistor
(Master)
Refer to the
J8
flowchart and make a diagnosis
of the relevant thermistor based
on the Error code shown to the left.
J8 - 02
Defective heat exchanger liquid pipe thermistor
(Slave 1)
J8 - 03
Defective heat exchanger liquid pipe thermistor
(Slave 2)
Error code
Troubleshooting
Description of error
Diagnosis
Summary of Contents for VRV X RXQ6-48ANR Series
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ6 48A N R Series SiME341909EA...
Page 289: ...SiME341909EA Wiring Diagrams Part 7 Appendix 283 RXQ10 12ARYFK 2D124184...
Page 290: ...Wiring Diagrams SiME341909EA 284 Part 7 Appendix RXQ14 16ARYFK 2D124183...
Page 295: ...SiME341909EA Wiring Diagrams Part 7 Appendix 289 FXMQ40 50 63 80 100ARV1 3D127112 04 59...