![background image](http://html1.mh-extra.com/html/daikin/vrv-x-rxq6-48anr-series/vrv-x-rxq6-48anr-series_service-manual_4705220171.webp)
SiME341909EA
Troubleshooting by Error Code
Part 6 Service Diagnosis
165
∗
1 Check also if the relay connector between the indoor unit control PCB and the fan motor are
correctly connected.
YES
Replace the indoor fan motor
(M1F).
Replace the indoor unit control
PCB (A1P).
The HAP
lamp on the indoor unit
control PCB is
blinking.
NO
A