![background image](http://html1.mh-extra.com/html/daikin/vrv-x-rxq6-48anr-series/vrv-x-rxq6-48anr-series_service-manual_4705220194.webp)
Troubleshooting by Error Code
SiME341909EA
188
Part 6 Service Diagnosis
Troubleshooting
Diagnosis procedure 2
Infrared floor sensor error
(Error code
CE-02
)
Turn off the power and then reconnect.
Check infrared floor sensor output; refer to sensor
and address data No. 26.
Connect the connector correctly.
Connect the connector correctly.
NO
YES
YES
Is the
connection
of the connector
on infrared floor
sensor PCB (A2P) and
the connector
X81A on A1P
normal?
NO
YES
YES
Is the
connection of the
sensor connector
normal?
Normal.
NO
Displays
"--" by the above
verification method.
Normal.
NO
Displays
CE-02
again or "--" for
sensor and
address data.
Replace the sensor.
Summary of Contents for VRV X RXQ6-48ANR Series
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ6 48A N R Series SiME341909EA...
Page 289: ...SiME341909EA Wiring Diagrams Part 7 Appendix 283 RXQ10 12ARYFK 2D124184...
Page 290: ...Wiring Diagrams SiME341909EA 284 Part 7 Appendix RXQ14 16ARYFK 2D124183...
Page 295: ...SiME341909EA Wiring Diagrams Part 7 Appendix 289 FXMQ40 50 63 80 100ARV1 3D127112 04 59...