COOLING ONLY

Cooling Only

50 Hz

ED 34 - 862

Большая библиотека технической документации

http://splitoff.ru/tehn-doc.html   

каталоги, инструкции, сервисные мануалы, схемы.

Summary of Contents for VRV III

Page 1: ...COOLING ONLY Cooling Only 50 Hz ED 34 862 Большая библиотека технической документации http splitoff ru tehn doc html каталоги инструкции сервисные мануалы схемы ...

Page 2: ...ounted Type 331 Floor Standing Type Concealed Floor Standing Type 359 Ceiling Suspended Cassette Type Connection Unit Series 381 Part 3 Outdoor Air Processing Unit 415 Outdoor Air Processing Unit 417 Part 4 Outdoor Units Normal Series Space Saving Series 451 Cooling Only 50Hz 453 Part 5 Outdoor Units High COP Series Energy Saving Series 533 Cooling Only 50Hz 535 Part 6 Installation of Outdoor Unit...

Page 3: ...complete air conditioning systems itself Our commitment to offering the best for people as well as the environment inspires us to develop new systems that make the most effective use of energy resources Daikin the first in the industry to develop the VRV system has now enhanced the R 410A R 22 with the Inverter that features an upgraded capacity of up to 54 horsepower to further refine all the fea...

Page 4: ...odel change of Remote Controller as follows BRC1A61 62 BRC1C62 BRC8A61 May 2006 ED30 653A 60Hz H P 60Hz H R RWEYQ10 20 30M YL TL VRV W II Heat Pump Heat Recovery 60Hz Correction of errors Jan 2008 INVERTER P ED30 842 50 60Hz H P H R RWEYQ P Y1 YL TL VRV W III Heat Pump Heat Recovery Preliminary Oct 2008 R 22 Air Cooled INVERTER K K ED35 211A 50 60Hz 50 60Hz RXY 16K K 30K K RX 16K K 30K K Following...

Page 5: ...umbers 1 Obtain the maximum heat load for the area s to be conditioned 2 Indoor unit specifications Outdoor unit specifications Capacity correction factor Air velocity and temperature distributions P 49 124 145 165 205 245 297 317 333 361 363 383 420 P 454 536 P 516 568 P 393 3 Selection of refrigerant pipes joints headers P 592 4 Selection of the control system Control wiring method Description o...

Page 6: ...tdoor Units 7 4 Nomenclature 9 5 Capacity Range 11 6 Features 13 6 1 Technologies 13 6 2 Flexible Design 15 6 3 A sense of responsibility 18 6 4 Enhanced Comfort 19 6 5 Control Systems 20 6 6 Advanced Control Systems 22 6 7 HRV Heat Reclaim Ventilation 26 6 8 HRV With DX Coil Heat Reclaim Ventilation VKM GA M Series 34 Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 7: ... FXDQ NBVE 40NB 50NB 63NB FXDQ NBVET 40NB 50NB 63NB Ceiling Mounted Built In Type FXSQ 20M 25M 32M 40M 50M 63M 80M 100M 125M Ceiling Mounted Duct Type Middle and high static pressure FXMQ 20P 25P 32P 40P 50P 63P 80P 100P 125P Ceiling Mounted Duct Type FXMQ 200MA 250MA Ceiling Suspended Type FXHQ 32MA 63MA 100MA Wall Mounted Type FXAQ 20MA 25MA 32MA 40MA 50MA 63MA Floor Standing Type FXLQ 20MA 25MA...

Page 8: ...RXQ18PA RXQ18PA HP 48HP 50HP 52HP 54HP Model name RXQ48PA RXQ50PA RXQ52PA RXQ54PA Outdoor unit 1 RXQ12PA RXQ14PA RXQ16PA RXQ18PA Outdoor unit 2 RXQ18PA RXQ18PA RXQ18PA RXQ18PA Outdoor unit 3 RXQ18PA RXQ18PA RXQ18PA RXQ18PA HP 16HP 18HP 24HP 26HP 28HP 30HP 32HP Model name RXQ16PAH RXQ18PAH RXQ24PAH RXQ26PAH RXQ28PAH RXQ30PAH RXQ32PAH Outdoor unit 1 RXQ8PA RXQ8PA RXQ8PA RXQ8PA RXQ8PA RXQ8PA RXQ8PA O...

Page 9: ...A FXAQ40MA FXAQ50MA FXAQ63MA Slim Ceiling Mounted Duct Type FXDQ20PB FXDQ40NB FXDQ25PB FXDQ50NB FXDQ32PB FXDQ63NB with Drain Pump VE without Drain Pump VET Floor Standing Type FXLQ20MA FXLQ25MA FXLQ32MA FXLQ40MA FXLQ50MA FXLQ63MA Ceiling Mounted Built In Type FXSQ20M FXSQ25M FXSQ32M FXSQ40M FXSQ50M FXSQ63M FXSQ80M FXSQ100M FXSQ125M Concealed Floor Standing Type FXNQ20MA FXNQ25MA FXNQ32MA FXNQ40MA ...

Page 10: ...Series RXQ5PA RXQ8PA 10PA RXQ20PA 22PA 24PA 26PA 28PA RXQ30PA 32PA 34PA 36PA RXQ38PA 40PA 42PA 44PA 46PA RXQ48PA 50PA 52PA 54PA RXQ12PA 14PA 16PA 18PA 5HP 8 10HP 12 14 16 18HP 20 22 24 26 28HP 38 40 42 44 46HP 30 32 34 36HP 48 50 52 54HP Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 11: ... Series Energy Saving Series RXQ16PAH 18PAH RXQ24PAH 26PAH RXQ28PAH 30PAH 16 18HP 24 26HP 28 30HP RXQ32PAH 34PAH RXQ36PAH 38PAH 40PAH 42PAH 44PAH 46PAH 48PAH 50PAH 32 34HP 36 38 40 42 44 46 48 50HP Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 12: ...Unit Multi Connection Piping Kit is required System Capacity Number of units Module Outdoor Unit Multi Connection Piping Kit Option 5 8 10 12 14 16 18 5HP 1 8HP 1 10HP 1 12HP 1 14HP 1 16HP 1 18HP 1 20HP 2 BHFP22P100 22HP 2 24HP 2 26HP 2 28HP 2 30HP 2 32HP 2 34HP 2 36HP 2 38HP 3 BHFP22P151 40HP 3 42HP 3 44HP 3 46HP 3 48HP 3 50HP 3 52HP 3 54HP 3 Все каталоги и инструкции здесь http splitoff ru tehn ...

Page 13: ... Daikin Outdoor Unit Multi Connection Piping Kit is required System Capacity Number of units Module Outdoor Unit Multi Connection Piping Kit Option 8 10 12 14 16 18 16HP 2 BHFP22P100 18HP 2 24HP 3 BHFP22P151 26HP 3 28HP 3 30HP 3 32HP 3 34HP 3 36HP 3 38HP 3 40HP 3 42HP 3 44HP 3 46HP 3 48HP 3 50HP 3 Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 14: ... 1 25 HP 71 3 HP 200 8 HP 40 1 6 HP 80 3 2 HP 250 10 HP Refrigerant R 410A Type of Unit F Ceiling Mounted Cassette Type Round Flow C Ceiling Mounted Cassette Type Double Flow K Ceiling Mounted Cassette Corner Type D Slim Ceiling Mounted Duct Type S Ceiling Mounted Built In Type M Ceiling Mounted Duct Type H Ceiling Suspended Type A Wall Mounted Type L Floor Standing Type N Concealed Floor Standing...

Page 15: ...1 Y1 54 Q RX PA Power Supply Symbol Y1 3 phase 380 to 415V 50Hz Indicates Major Design Category PA Normal Series Space Saving Series PAH High COP Series Energy Saving Series 5 5HP 14 14 HP 22 22 HP 30 30 HP 40 40 HP 48 48 HP 8 8 HP 16 16 HP 24 24 HP 32 32 HP 42 42 HP 50 50 HP 10 10 HP 18 18 HP 26 26 HP 34 34 HP 44 44 HP 52 52 HP 12 12 HP 20 20 HP 28 28 HP 36 36 HP 46 46 HP 54 54 HP 38 38 HP Refrig...

Page 16: ... 48 HP 625 to 1 625 1 625 50 HP Note For multiple connection of 20 HP systems and above the above Daikin optional kit separately sold is required Values inside brackets are based on connection of indoor units rated at maximum capacity 200 for single outdoor units 160 for double outdoor units and 130 for triple outdoor units Refer to page 15 for notes on connection capacity of indoor units Note For...

Page 17: ...ssette Corner Type FXKQ 25MA 32MA 40MA 63MA Slim Ceiling Mounted Duct Type FXDQ PBVE 20PB 25PB 32PB FXDQ PBVET 20PB 25PB 32PB FXDQ NBVE 40NB 50NB 63NB FXDQ NBVET 40NB 50NB 63NB Ceiling Mounted Built In Type FXSQ 20M 25M 32M 40M 50M 63M 80M 100M 125M Ceiling Mounted Duct Type Middle and high static pressure FXMQ 20P 25P 32P 40P 50P 63P 80P 100P 125P Ceiling Mounted Duct Type FXMQ 200MA 250MA Ceilin...

Page 18: ...or each casing This greatly reduces pressure loss resulting in a higher external static pressure The three bladed fan on the 10 HP unit with a diameter of 700 mm has been redesigned to include four blades and now has a diameter of 680 mm Blade area has been increased by 25 1 Newly improved fans and grilles Heat exchanger New aero spiral fan and aero asymmetrical fan Aero smooth grille New aero asy...

Page 19: ...ncy Powerful magnets Secret to raising energy efficiency Powerful magnets Neodymium magnets are much more powerful than the widely used ferrite magnets Neodymium magnet Reluctance DC motor Improving the high efficiency compressor to achieve a high COP and larger capacity Reluctance DC scroll compressor High torque and efficiency is attained with the adoption of neodymium magnets Achieves 70 reduct...

Page 20: ...MA series indoor units Refer to page 11 for the maximum number of connectable indoor units Maximum number of connectable indoor units Up to Up to Note For the FXFQ25 models maximum connection ratio is 130 for the entire range of outdoor units If the operational capacity of indoor units is more than 130 low airflow operation is enforced in all the indoor units 50 200 Connection capacity Single outd...

Page 21: ...Maximum allowable piping length Between the outdoor units and the indoor units Between the indoor units Between the outdoor units Multiple use Between the first indoor branch and the farthest indoor unit Between the outdoor branch and the last outdoor unit Total extension length Refrigerant piping length 15 m or less 90 m or less 5 m or less 90 m or less q s r r a b c d e f g h i a f g h i f g h i...

Page 22: ...h floor often requested for large sized buildings VRVII MA series 78 4 Pa Easier installation and maintenance Automatic test operation Memory function for operational data Simply press the test operation button and the unit performs an automatic system check including wiring shutoff valves and sensors The results are returned automatically after the check finishes Operating data for the preceding ...

Page 23: ...oling operation Approx 51 increase Compared to VRV II MA series 2 81 3 18 RoHS Directive The RoHS Restriction of Hazardous Substances in electrical and electronic equipment Directive is an environmental directive enacted to regulate the use of designated chemical substances lead cadmium hexavalent chromium mercury polybrominated biphenyls and polybrominated diphenylether in electrical equipment Al...

Page 24: ...he night mode Mode 1 Automatic mode Mode 1 Starting time and ending time can be input An external control adaptor for outdoor unit DTA104A53 61 62 and a locally obtained timer are necessary Manual mode Mode2 Combinations of modes 1 and 2 can be used depending on your needs Combined mode Mode 3 1 Initial setting Can be selected from 6 8 and 10 hours 2 Initial setting Can be selected from 8 9 and 10...

Page 25: ...tandard remote controllers BRC1C62 not required 2 If the BRC1D61 is connected to the centralised remote controllers DCS303A51 DCS302CA61 DCS301BA61 DST301BA61 the schedule function is not available Outdoor unit Indoor unit Forced OFF input Remote controller Remote controller Remote controller Remote controller Remote controller Remote controller Remote controller Remote controller HRV The indoor u...

Page 26: ...ntroller The concealed type remote controller smartly fits into a night table or console panel in a hotel room Exposed type BRC2C51 Concealed type For hotel use BRC3A61 Wireless remote controller Option Simple remote controller Option Wired remote controller BRC1C62 Wired remote controller with weekly schedule timer BRC1D61 Wireless remote controller Installed signal receiver unit Wireless remote ...

Page 27: ... proportional distribution function Option RS 232C Public phone line Air Conditioning Network Service System modem for connections CSV output of power proportional distribution results Option PCMCIA Flash Memory Remote monitor ing and control Mobile Phone PC Trouble reports D NET Plus Adaptor DCS601A52 Option Number of indoor units expanded from 64 to 128 D NET Function 1 Function 2 Function 3 Fun...

Page 28: ...or use in BACnet Local dealers I F unit 4 Automatic data transfer Mainfunction information by E mail INTERNET ACC centre Maintenance services that boost profits and customer satisfaction Air Conditioning Network Service System 24 hour on line diagnostic system Energy saving and extention of aircon operating life Maintenance management via A C network service system reports Reliable service at shor...

Page 29: ...ntrol and monitoring of VRV system functions 1 Air Conditioning Network Service System Optional Maintenance Service New Features 2 Monitor and control from the remote site by Web browser Option PPD data can be managed from the remote site by Web browser Option Send malfunction report through the Internet by E mail Option Compliant with the RoHS Directive DAM602B51 52 refer to page 18 for details D...

Page 30: ...rictions in applicable areas and release times therefore please consult us separately for details Interfacing requirements vary depending on model and some systems may not be suitable Please contact your distributor for details Information on these systems is preliminary only Please contact Daikin for formal information on the products Floor visual navigation Graphical report Multi PC access Analo...

Page 31: ...kin s HRV Daikin s HRV greatly reduces the total power consumption by operation interlocked with air conditioner such as VRV or SkyAir The total heat exchange mode and the ventilation mode can be automatically selected by setting to the automatic ventilation mode Main Features 1 The operation is available when the outdoor air temperature is down to 15 C 2 Interlocked operation with VRV SkyAir 3 Au...

Page 32: ... air from outdoor EA Exhaust air Exhaust air to outdoor 1 Hanger bracket 2 Duct connecting flange 3 Exhaust fan 5 Damper 4 Air filter Long life filter 8 Heat exchange elements 11 Remote controller Optional accessory 7 Maintenance cover 6 Control box 10 Air supply fan SA Supply air Feed air to room RA Return air Exhaust air from room OA Outdoor air Fresh air from outdoor EA Exhaust air Exhaust air ...

Page 33: ... can be set at the initial setting only Installation Examples Type Interlocked operation with air conditioner HRV independent operation Structure Features Simultaneous operation by air conditioner s remote controller is available Operation Stop Ventilation mode changeover Fresh up changeover Timer mode start stop Malfunction digital display Connectable Indoor unit VRV all indoor unit SkyAir Daikin...

Page 34: ...cooling load Exhaust Air Exhaust Air Outdoor Air Heat Exchanger Element Heat Recovery Return Air Supply Air HC0230 Approx 8 reduction of heating cooling load By setting to automatic ventilation mode Operation Sensor of ventilation Decision of mode Which is more energy efficient Difference between indoor outdoor temp Cooling Indoor temp Outdoor temp Indoor temp Outdoor temp Normal ventilation Bypas...

Page 35: ... to off in the factory settings so request your dealer to turn it on if you intend to use it Operation image a Outside temperature b Indoor temperature c Set temperature d Operating state of Air conditioner e Operating state of Total heat exchanger EXPLANATION OF NIGHTTIME FREE COOLING OPERATION IMAGE The unit compares the indoor and outdoor temperatures after the air conditioning operation stops ...

Page 36: ... etc Sheet structure Outdoor Exhaust air SA Indoor RA unclean indoor air Outdoor air fresh air Conventional element New ultra thin film element Moisture absorption is less effective due to the thickness of the partition sheets It also limits the effective area that supply and exhaust air can be exposed to RA unclean indoor air Outdoor air fresh air Exhaust air SA Outdoor Indoor Thickness of the pa...

Page 37: ...y to make a trap Because the trap of wiring can protect against ingress of water Upside down installation is available It allows the common use of the inspection hole and reduces the space and installation work For 2 units closely installed only one inspection hole of 450 450 mm will do for maintenance or replacement of the heat exchanger element etc Long life filter is equipped SA RA EA OA HC0234...

Page 38: ... stops operation to prevent any defect such as dew condensation and freezing The unit does not ventilate But to detect the elevation of the outdoor air temperature the unit operates for 5 minutes per hour The control by the external damper local purchase is available When the unit is not operating the unit prevents the cool outdoor air from invading The power is applied from the connector X15A to ...

Page 39: ...ut taking an interlock with indoor units is possible however temperature setting by remote controller is impossible In this ON OFF operation by thermostat depends on factory setting however this value is changeable by setting mode on site Model selection should be done not by cooling capacity but by ventilating air flow rate 6 8 2 Design Flexibility 6 8 2 1 Efficient Fan Performance Produces a Hig...

Page 40: ...e and higher than outdoor temperature operation is started 3 Operation will be stopped if indoor temperature falls to air conditioning machine preset temperature Effect Field Setting by remote controller It is reduction of about 5 of air conditioning load at the time of cooling operation Air conditioning operation carries out to April to October and air conditioning load is calculated only with se...

Page 41: ...ooling Operation Flow Chart Fan operation Temperature monitor 5Min Fan operation ON H or U H tap Lapsed time setup 2hr 4hr 6hr 8hr No Air conditioner Operation RUN Temp monitor operation time Lapsed time 60hr Indoor temp Outdoor temp Indoor temp Preset temp Fan operation Lapsed time Lapsed time 60Min Standard mode Fan operation STOP Standby mode 60 Min Fan ON time is included Exhaust fan Air suppl...

Page 42: ...the noise output of the 1 000m3 h type system to 38dB 50Hz 240V High mode Heating and cooling heat recovery humidifying 5 0 5 10 15 20 Dry bulb temperature CDB 25 30 35 40 Relative humidity 20 40 60 80 100 Eff Effect of full heat e ect of full heat exc xchang hange Effect of full heat exchange Effect of full heat exchange Effect of cooling Outdoor air temperature in summer Indoor temperature durin...

Page 43: ...ernal Air Quality Note 4 6 can be set at the initial setting only When using the remote controller BRC1C62 Note 1 In case of the direct duct connection system operate interlocking with indoor units 2 Do not connect the duct with discharge air side of indoor units Type Interlocked operation with air conditioner Structure Features Simultaneous operation by air conditioner s remote controller is avai...

Page 44: ...007 HC0008 By heat recovery operation Approx 20 reduction of heating cooling load Exhaust Air Exhaust Air Outdoor Air Heat Exchanger Element Heat Recovery Return Air Supply Air HC0230 Approx 6 reduction of heating cooling load By setting to automatic ventilation mode Operation Sensor of ventilation Decision of mode Which is more energy efficient Difference between indoor outdoor temp Cooling Indoo...

Page 45: ...ply Fresh up Excessive outdoor air supply Exhaust Fresh up Excessive exhaust air supply Detail Supply air volume can be set at a higher level than the exhaust air by the remote controller Exhaust air volume can be set at a higher level than the supply air by the remote controller Major effects Prevents inflow of toilet odor Prevents inflow of outdoor air in winter Prevents outflow of airborne bact...

Page 46: ... lower than 15 C the unit stops operation to prevent any defect such as dew condensation and freezing The unit does not ventilate But to detect the elevation of the outdoor air temperature the unit operates for 5 minutes per hour 6 8 7 7 The High Efficiency Filter that has 65 of Average Dust Collecting Efficiency is Suitable 6 8 7 8 Additional Optional Accessories Built in optional high efficiency...

Page 47: ...oratory etc to find out the number of hourly ventilation of the room air Selection example Place Living room of common household Required ventilation 6 times h See Table 2 Area of room Approx 30 m2 Height of ceiling 2 4 m Required ventilating air flow rate 6 30 2 4 Required ventilating air flow rate and the unit size 500 is almost equal So select the close size of the unit In this case select VKM5...

Page 48: ...ion room 15 Washroom Toilet 10 Painting shop 15 Cooking room 15 Welding plant 15 Laundry room 15 Chemical plant 15 Engine room 20 Food plant 20 Boiler room 20 Wood working plant 20 Hospitals Consultation office 6 Casting plant 50 General buildings Office room 6 Waiting room 10 Show room Toilet 10 Conference room 12 Comfort stations 20 Dark rooms Dark rooms for photo 16 Sick room 6 Guest rooms of s...

Page 49: ...Features ED34 862 44 General Information Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 50: ...nted Duct Type 163 FXSQ M Ceiling Mounted Built In Type 201 FXMQ P Ceiling Mounted Duct Type Middle and High Static Pressure 243 FXMQ MA Ceiling Mounted Duct Type 295 FXHQ MA Ceiling Suspended Type 315 FXAQ MA Wall Mounted Type 331 FXLQ MA FXNQ MA Floor Standing Type Concealed Floor Standing Type 359 FXUQ MA Ceiling Suspended Cassette Type Connection Unit Series 381 Все каталоги и инструкции здесь...

Page 51: ...ED34 862 46 Indoor Units Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 52: ...ications 49 3 Dimensions 51 4 Piping Diagrams 54 5 Wiring Diagrams 55 6 Electric Characteristics 56 7 Capacity Tables 57 7 1 Cooling Capacity 57 8 Sound Levels 58 9 Center of Gravity 60 10 Installation Manual 61 11 Accessories 85 Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 53: ...ng the growth of slime mould and bacteria that cause blockages and odours The horizontal louvres prevent dew condensation Their non flocking surfaces which repel dirt are easy to clean The air filter has an anti mould and antibacterial treatment that prevents the growth of mould generated from dust or moisture that may adhere to the filter Example of airflow patterns 360 airflow is available as we...

Page 54: ...ection φ6 4 Flare Connection φ6 4 Flare Connection Gas Pipes mm φ12 7 Flare Connection φ12 7 Flare Connection φ12 7 Flare Connection φ12 7 Flare Connection Drain Pipe mm VP25 External Dia 32 Internal Dia 25 VP25 External Dia 32 Internal Dia 25 VP25 External Dia 32 Internal Dia 25 VP25 External Dia 32 Internal Dia 25 Mass Weight kg 19 5 19 5 19 5 19 5 4 Sound Level HH H L 220 240V dBA 30 28 5 27 30...

Page 55: ... Connection φ9 5 Flare Connection φ9 5 Flare Connection Gas Pipes mm φ15 9 Flare Connection φ15 9 Flare Connection φ15 9 Flare Connection φ15 9 Flare Connection Drain Pipe mm VP25 External Dia 32 Internal Dia 25 VP25 External Dia 32 Internal Dia 25 VP25 External Dia 32 Internal Dia 25 VP25 External Dia 32 Internal Dia 25 Mass Weight kg 22 22 25 25 4 Sound Level HH H L 220 240V dBA 34 31 28 36 33 5...

Page 56: ...RFACE 2 IN CASE OF USING WIRELESS REMOTE CONTROLLER THIS POSITION WILL BE A SIGNAL RECEIVER REFER TO THE DRAWING OF WIRELESS REMOTE CONTROLLER IN DETAIL 3 WHEN THE TEMPERATURE AND HUMIDITY IN THE CEILING EXCEED 30 C AND RH 80 OR THE FRESH AIR IS INDUCTED INTO THE CEILING OR THE UNIT CONTINUES 24 HOUR OPERATION AN ADDITIONAL INSULATION THICKNESS 10mm OR MORE OF GLASSWOOL OR POLYETHYLENE FORM IS REQ...

Page 57: ...ANUFACTURE S LABEL FOR DECORATION PANEL DECORATION PANEL S CORNER DECORATION COVER INNER SURFACE 2 IN CASE OF USING WIRELESS REMOTE CONTROLLER THIS POSITION WILL BE A SIGNAL RECEIVER REFER TO THE DRAWING OF WIRELESS REMOTE CONTROLLER IN DETAIL 3 WHEN THE TEMPERATURE AND HUMIDITY IN THE CEILING EXCEED 30 C AND RH 80 OR THE FRESH AIR IS INDUCTED INTO THE CEILING OR THE UNIT CONTINUES 24 HOUR OPERATI...

Page 58: ... CONNECTION WIRING REMOTE CONTROL WIRING CONNECTION GAS PIPE CONNECTION AIR OUTLET POWER SOURCE WIRING AND A UNIT WIRING CONNECTION LIQUID PIPE CONNECTION 9 8 7 6 5 4 3 2 1 DECORATION PANEL REQUIRED SPACE 1500mm OR MORE 1500mm OR MORE 1500mm OR MORE 1500mm OR MORE 200mm OR MORE 200mm OR MORE WHEN THE BLOW OFF GRILL IS CLOSING THE REQUIRED SPACE IS 500mm OR MORE WHEN UNITING AND CLOSING A CORNER PA...

Page 59: ... FXFQ P 4 Piping Diagrams Refrigerant pipe connection port diameters mm Model Gas Liquid FXFQ25P 32P 40P 50PVE φ12 7 φ6 4 FXFQ63P 80P 100P 125PVE φ15 9 φ9 5 4D024460B Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 60: ...CH MAIN SUB CONNECTOR FOR OPTIONAL PARTS LIGHT EMITTING DIODE TIMER GREEN INDOOR UNIT PRINTED CIRCUIT BOARD NOISE FILTER POWER SUPPLY CIRCUIT PUSH BUTTON ON OFF TERMINAL STRIP PRINTED CIRCUIT BOARD ELECTRONIC EXPANSION VALVE THERMISTOR AIR MOTOR DRAIN PUMP MAGNETIC RELAY TERMINAL STRIP FLOAT SWITCH MOTOR INDOOR FAN MAGNETIC RELAY M1P DIODE BRIDGE THERMISTOR COIL LIQUID MOTOR SWING FLAP THERMISTOR ...

Page 61: ...Electric Characteristics ED34 862 56 FXFQ P 6 Electric Characteristics C 4D060238A Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 62: ...6 3 9 4 6 1 39 0 2 4 2 4 2 9 2 8 3 4 3 1 3 5 3 1 3 5 3 1 3 6 3 0 3 7 2 9 39 0 6 1 5 1 7 2 5 9 8 4 6 6 8 7 6 5 8 8 6 4 9 0 6 3 9 3 6 1 40 10 0 3 0 2 9 3 6 3 4 4 2 3 7 4 5 3 8 4 8 3 8 5 4 3 9 5 7 3 9 100 10 0 7 6 6 8 9 0 7 8 10 5 8 7 11 2 8 9 11 9 9 0 13 4 9 3 14 2 9 2 12 0 3 0 2 9 3 6 3 4 4 2 3 7 4 5 3 8 4 8 3 8 5 4 3 9 5 6 3 8 12 0 7 6 6 8 9 0 7 8 10 5 8 7 11 2 8 9 11 9 9 0 13 4 9 3 14 0 9 1 14 0 ...

Page 63: ...depending on a range of factors such as the construction acoustic absorption coefficient of the particular room in which the equipments installed dBA Model 220 240V 50Hz HH H L FXFQ25P 32P 30 28 5 27 FXFQ40P 31 29 27 FXFQ50P 32 29 5 27 FXFQ63P 34 31 28 FXFQ80P 36 33 5 31 FXFQ100P 43 37 5 32 FXFQ125P 44 39 34 FXFQ25 32PVE FXFQ40PVE FXFQ50PVE FXFQ63PVE FXFQ80PVE FXFQ100PVE 4D060231 4D060231 4D060232...

Page 64: ...ED34 862 Sound Levels FXFQ P 59 2 FXFQ125PVE 4D060237 Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 65: ...Center of Gravity ED34 862 60 FXFQ P 9 Center of Gravity FXFQ25P 32P 40P 50P 63P 80P 100P 125PVE 4D052237B Unit mm Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 66: ...nces not accessible to the general public This unit is a class A product In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures Meaning of WARNING and CAUTION notices WARNING Failure to follow these instructions properly may result in personal injury or loss of life CAUTION Failure to observe these instructions properly ...

Page 67: ...rts Do not directly touch refrigerant that has leaked from refrigerant pipes or other areas as there is a danger of frostbite Be sure to earth the air conditioner Do not earth the unit to a utility pipe lightning conductor or telephone earth lead Imperfect earthing may result in electric shocks or fire A high surge current from lightning or other sources may cause damage to the air conditioner Be ...

Page 68: ...er to the paper pattern This unit is suitable for installation in a household commercial and light industrial environment Do not install or operate the unit in rooms mentioned below Laden with mineral oil or filled with oil vapor or spray like in kitchens Plastic parts may deteriorate Where corrosive gas like sulfurous gas exists Copper tubing and brazed spots may corrode Where volatile flammable ...

Page 69: ...properly done what is likely to occur Check Are the indoor unit and outdoor unit fixed firmly The unit may drop vibrate or make noise Is the outdoor unit fully installed The unit may malfunction or the compo nents burn out Is the gas leak test finished It may result in insufficient cooling Is the unit fully insulated Condensate water may drip Does drainage flow smoothly Condensate water may drip D...

Page 70: ...ith the customer s approval which matches the following conditions A location from which cool warm air will reach the whole room A location with no objects blocking the air passage A location where drainage can be done with no problem A location strong enough to support the weight of the indoor unit Locations where the wall is not significantly tilted A location which leaves enough room for instal...

Page 71: ...eight is 2 7m 3 2m for the 100 and 125 or more field settings will have to be made with the remote controller See 11 FIELD SETTING for details 3 Air direction The air direction shown in Fig 3 is an example Select the appropriate number of directions according to the shape of the room and the location of the unit Field settings have to be made using the remote controller and the outlet vents have t...

Page 72: ...ess If the spacing between ceiling and the unit is over 35mm attach ceiling material to part or recover the ceiling 950 Decoration panel 780 Suspension bolt pitch 840 Indoor unit 860 910 Ceiling opening 710 Suspension bolt pitch 950 Decoration panel 860 910 Ceiling opening 840 Indoor unit Refrigerant piping Suspension bolt 4 Fig 4 A False ceiling View as seen from A Hanger bracket 125 130 Fig 5 Di...

Page 73: ... indoor unit is easier However for existing ceilings install fresh air inlet component kit and branch duct before installing the unit As for the parts to be used for installation work be sure to use the provided accessories and specified parts designated by our company 1 For new ceilings 1 1 Install the indoor unit temporarily Attach the hanger bracket to the suspension bolt Be sure to fix it secu...

Page 74: ...function and cause water to drip 1 5 Remove the washer fixing plate 7 used for preventing the washer from falling and tighten the upper nut 1 6 Remove the paper pattern for installation 5 2 For existing ceilings 2 1 Install the indoor unit temporarily Perform step 1 1 in 1 For new ceilings 2 2 Adjust the height and position of the unit Refer to 4 PREPARATIONS BEFORE INSTALLATION 1 and 1 3 in 1 For...

Page 75: ...rant gas leaks while working on the unit ventilate the room thoroughly right away Do not mix air or other gas with the specified refrigerant in the refrig eration cycle Ventilate the room if refrigerant gas leaks during the work The outdoor unit is charged with refrigerant Be sure to use both a spanner and torque wrench together as shown in the drawing when connecting or disconnecting pipes to fro...

Page 76: ...metal BCuP 2 JIS Z 3264 B Cu93P 710 795 ISO 3677 which does not require flux Flux has extremely harmful influence on refrigerant piping systems For instance if the chlorine based flux is used it will cause pipe corrosion or in particular if the flux contains fluorine it will damage the refrigerant oil Pipe size Further tightening angle Recommended arm length of tool φ 6 4 1 4 60 to 90 degrees Appr...

Page 77: ...in pipe short and sloping downwards at a gradient of at least 1 100 to prevent air pockets from forming If the drain pipe cannot be sufficiently set on a slope execute the drain raising piping To keep the drain pipe from sagging space hanging wires every 1 to 1 5m CAUTION Water pooling in the drainage piping can cause the drain to clog Use the attached drain hose 1 and Metal clamp 2 Insert the dra...

Page 78: ...fer to the figure on the following after checking the draining of water and mount the thermal insulation material for drainage 14 and thermal insulate the drain socket WHEN ELECTRIC WIRING WORK IS NOT FINISHED CAUTION Electrical wiring work should be done by a certified electrician If someone who does not have the proper qualifications performs the work perform the following after the test run is ...

Page 79: ...he drain pump When the power is turned on the drain pump will operate and you can check the draining of water through the transparent part of the drain socket The drain pump will stop automatically in 10 minutes After checking the draining of water mount the thermal insulation material for drainage 14 and thermal insulate the drain socket After confirming drainage Fig 23 Fig 24 turn off the power ...

Page 80: ...d switch and wiring instructions Be sure to ground the air conditioner Do not connect the ground wire to gas pipes plumbing pipes lightning rods or telephone ground wires Gas pipes might cause explosions or fire if gas leaks Plumbing no grounding effect if hard vinyl piping is used Telephone ground wires or lightning rods might cause abnormally high electric potential in the ground during lighting...

Page 81: ...it of simultaneous operation system Remove the terminal box lid and pull the wires inside through the hole and connect to the terminal block for remote controller 6 P no polarity Securely fix the remote controller cord with the included clamp 4 2 points After connection attach sealing pad 13 Be sure to attach it to prevent the infiltration of water from the outside PRECAUTIONS 1 Use round crimp st...

Page 82: ...e 5 For remote controller wiring refer to the INSTALLATION MANUAL OF REMOTE CONTROLLER attached to the remote controller 6 Never connect power supply wiring to the terminal block for remote controller A mistake of the sort could damage the entire system 7 Use only specified wire and tightly connect wires to terminals Be careful wires do not place external stress on terminals Keep wiring in neat or...

Page 83: ...0 mm so that they do not pass through the same place together Proximity may cause electrical interference malfunctions and breakage Fig 27 Inter unit wiring Ground wire Sheaths Remote controller cord weak electric 10 15mm 70 90mm Clamp 4 Approximately 7mm Peel back the sheath on the power line and twist Length of sheath to peel back Cut off any excess material after tightening Wiring through holes...

Page 84: ...ocessing method of wiring through holes Power supply wiring Transmission wiring Switch Fuse Power supply Main switch Remote controller Indoor unit BS unit Only for Heat recovery system Fig 28 L N L N IN D OUT D F1 F2 F1 F2 Terminal box L N P1 P2 P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 F1 F2 T1 T2 L N Outdoor unit No 1 System Indoor unit A Fig 29 Indoor unit B ...

Page 85: ...he address is automatically set when power is activated Terminal box Outdoor unit No 2 System Indoor unit A Fig 30 Indoor unit B Indoor unit C Most down stream indoor unit For use with 2 remote controllers IN D OUT D F1 F2 F1 F2 P1 P2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 L N L N L N L N L N Power supply 220 240V 50Hz IN D OUT D F1 F2 F1 F2 IN D OUT D ...

Page 86: ...id 4 Add remote control 2 slave to the terminal block for remote controller P1 P2 in the terminal box There is no polarity Refer to Fig 30 and 8 3 9 4 Computerised control forced off and on off operation 1 Wire specifications and how to perform wiring Connect the input from outside to terminals T1 and T2 of the terminal block for remote controller Wire specification Sheathed vinyl cord or cable 2 ...

Page 87: ...inal box lids are closed on the indoor and outdoor units Field setting must be made from the remote controller and in accordance with installation conditions Setting can be made by changing the Mode No FIRST CODE NO and SECOND CODE NO For setting procedures and instructions see Field settings provided with the remote controller 11 1 Setting ceiling height Select the SECOND CODE NO that corresponds...

Page 88: ...ere no cleaning display is required e g at the time of regular maintenance servicing The air conditioner is provided with a long life filter as a standard accessory Explain to the customer the necessity of cleaning the filter periodically along with the set time for filter cleaning for the prevention of clogging When using wireless remote controllers When using wireless remote controllers wireless...

Page 89: ...conditioner until the interior work is completed if the interior work has not been finished at the end of the test run If the air conditioner is operated substances discharged from the paint adhesive etc can contaminate the indoor unit and they may cause splashing or leakage of water NOTE After the test run is finished check the items listed in 2 Items to be checked at time of delivery Remote cont...

Page 90: ...cement ultra long life filter KAFP55H160H Fresh air intake kit Chamber type Without T joint pipe and fan KDDP55K160 WithT joint pipe without fan KDDP55K160K Direct installation type KDDP55X160 Branch duct chamber KDJP55H80 KDJP55H160 Chamber connection kit KKSJ55K160 Insulation kit for high humidity KDTP55K80 KDTP55K160 C 3D060297 Name 1 Drain hose 2 Metal clamp 3 Washer for hanger bracket 4 Clamp...

Page 91: ... flap The swing flap may malfunction 1 Remove the suction grille from the decoration panel 1 Press the lever on the suction grille and lift the lever side Refer to Fig 1 2 Detach the suction grille from the decoration panel by lifting the grille up approximately 45 degrees Refer to Fig 2 3 Remove the transporting cardboard in 4 locations from the main unit Refer to Fig 3 4 Remove the transporting ...

Page 92: ...o the hooks around the main indoor unit body Make sure at this time that the swing motor lead wire does not get caught between the decoration panel and the main unit 3 Screw all 4 hexagon head screws located right beneath the latches in approximately 5 mm Panel will rise 4 Adjust the decoration panel by turning it to the arrowed direction in Fig 6 so that the ceiling opening is completely covered ...

Page 93: ...talled on the decoration panel 8 Replace the electric components box lid reversing the procedure to remove it Make sure that the swing flap motor lead wire is not caught between the electric components box and its lid and between the indoor unit body and the decoration panel Fig 7 Air leak Air leak from ceiling Contamination Dew formation dew dripping Fig 8 No gap is allowed Adjustment of the indo...

Page 94: ...tation of the indoor unit is changed for purposes of description Fig 9 Install the suction grill 1 Tilt the suction grill at a 45 angle and fix 3 hooks to the decoration panel 3 Slowly push the suction grill up and lastly ensure the grill is fastened to the decoration panel body keeping pressing 2 knobs 2 Hook up the strings of the suction grill to the fixtures of the body corners 2 places as show...

Page 95: ...o the pin of the decoration panel Refer to Fig 10 2 Install the corner section decoration cover over the decoration panel Refer to Fig 11 Hole Hole Hole Tab Tab Tab Attach by inserting the five tabs on the corner section decoration cover into the holes on the decoration panel Fig 10 Fig 11 Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 96: ...rocedure 2 Stick the sealing material to the tape for fixing the sealing material Sealing material 3 Tape for fixing the sealing material 8 Air outlet B1 When the indoor unit s main body belongs to classes 28 to 56 Sealing material 5 Tape for fixing the sealing material 8 Air outlet C Sealing material 4 Tape for fixing the sealing material 8 Air outlet B2 Air outlet D Sealing material 6 When the i...

Page 97: ...cessary Sticking reference Sticking reference Upper surface Air outlet Sticking not necessary Sticking reference Sticking reference Sticking reference Centre reference Sticking reference Upper surface Sticking reference Centre reference Sticking reference Centre reference Stickingreference Sticking reference Sticking reference Sticking reference Upper surface Sticking reference Upper surface Stick...

Page 98: ...rence 16 Sticking reference 16 For a wiring takeoff point with two sections make a slit on the side insulator plate as shown in the figure below then route the wiring Wiring Wiring Slit Slit 16 Side insulator plate 16 Side insulator plate Wiring takeoff point Superimpose the surplus section Perform the operation on soft cloth to prevent damage to the panel Perform sticking for the horizontal blade...

Page 99: ...e air conditioner Hides the gap between the decoration panel and the ceiling Dimensions Unit mm Model KDBP55H160FA Item Exterior Fresh White Material Outside frame Resin Insulation Foam polyethylene Component Panel spacer Insulation Sealant Mounting screws Installation manual Mass kg 1 2 Hole Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 100: ...ED34 862 Accessories FXFQ P 95 2 1P136564E Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 101: ...Accessories ED34 862 96 FXFQ P 1P136564E Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 102: ... an inspection hole Ceiling opening dimension KDDP55K160K with T shape without Fan Caution 1 Maximum length of the duct is 4 meters 2 When installing this kit an inspection hole is required in order to maintain this kit Establish an inspection holes on either side 3 This kit is field assembly 4 Install the hanging fixing for the T joint Otherwise the load from T shape pipe assembly etc could creat...

Page 103: ...ngthesealingmaterial 9 Mounting screw for sensor Inspection opening ceiling opening dimension 1 Install the suspension bracket for the T joint section Because of the load from T joint etc a gap may be created in between the indoor unit and suction chamber 2 Establish an inspection opening 450 or more Establish an inspection opening to either side Refer to 2 Inspection opening 450 or more Refer to ...

Page 104: ...rough the gap of the split pin then lightly tighten by hand 3 Using a standard tool driver pliers etc turn the split pin to the direction shown in the figure to tighten the band 4 This completes the mounting Because the split pin has a structure to prevent counter rotation be careful with the turning direction When a counter rotation is forced the ratchet will be damaged and the tightening force w...

Page 105: ...ons Unit mm Model KDDP55X160 Item Material Hot dip zinc coated carbon steel sheet Diameter of connection duct φ100 Accessories Mounting screws 4 Insulating material 1 unit Installation manual 124 φ126 φ137 67 φ98 4 φ 5 Hole cyclotomic Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 106: ...e outside and prevent rainwater from leaking in Gradient of 1 100 to 1 50 To prevent the intrusion of small animals such as birds and bugs be sure to attach a netting to sections open to outside air Parts content Check the following parts Name Shape 1 Duct flange 5 Sealing pad retainer 6 Installation manual 4 Main body opening insulator 3 Duct flange insulator 2 Mounting screws Number of pieces 1 ...

Page 107: ...ad retainer 5 Be careful not to block the air outlet Insulator Duct Connection Duct Nominal diameter φ100 1 Connect the duct to the outside of the duct flange Figure 5 2 After the connection wrap the connection area with tape field supplied to prevent an air leak Duct flange 1 Wrap with tape to prevent an air leak Indoor unit main body Precautions Perform insulation for all ducts Do not perform du...

Page 108: ...age efficiency 65 colorimetric method 90 colorimetric method Number of sheets included 1 1 1 1 Air flow rate l sec 317 583 317 583 m3 min 19 35 19 35 Initial pressure loss Pa 34 or less Final pressure loss Pa 98 or less Filter element Non woven fabric of synthetic fiber Life h 2 500 dust concentration 0 15 mg m3 1 800 dust concentration 0 15 mg m3 Mass kg 3 6 4 2 3 6 4 2 Replacement filter optiona...

Page 109: ... Installation manual For the installation parts accessory parts and specified components must always be used If the specified components are not used the kit may fall or an air leak may occur After the completion of installation perform a test run to check that no abnormality is present This product can be mounted to a ceiling mounted cassette type air conditioner round flow According to the table...

Page 110: ...igure to the right When mounting the high efficiency filter unit to the existing indoor unit main body change the installation height of the indoor unit main body to height in the figure to the right Mount the supplied installation pattern paper to the indoor unit using screws to cure the indoor unit Refer to the installation manual for the indoor unit main body Refer to the figure below After tem...

Page 111: ...80 KAFP552H160 KAFP553H80 KAFP553H160 Average efficiency 65 colorimetric method 90 colorimetric method Number of sheets included Air flow rate m3 min 19 1 1 1 1 35 19 35 Initial pressure loss Pa 34 Final pressure loss Pa 98 Filter element Non woven fabric of synthetic fiber Life h 2 500 dust concentration 0 15 mg m3 1 800 dust concentration 0 15 mg m3 Mass kg 0 6 1 2 0 6 1 2 2 0 540 10 10 560 560 ...

Page 112: ...erage efficiency 50 Gravity method Number of sheets included 1 Air flow rate l sec 492 m3 min 29 5 Initial pressure loss Pa 8 or less Final pressure loss Pa 49 or less Filter element Polypropylene honeycomb with mould proof Life h 5 000 dust concentration 0 3 mg m3 Mass kg 4 7 Mounting locations Filter cleaning period Locations with much dust Approximately every 5 000 hours Locations with little d...

Page 113: ...m the installation Filter clasp Combination table Ultra long life filter Ultra long life filter unit Indoor unit main body Suspension bracket Hook Suspension bracket Indoor unit main body Refrigerant piping Ultra long life filter unit Ultra long life filter unit Recommendations Match the contour Suspension bracket 4 positions Hook Indoor unit main body Control box cover Hook 4 positions Mounting o...

Page 114: ...stall the indoor unit main body and ultra long life filter unit At the time of installation perform engineering work according to the installation manual attached to the air conditioner s main body For the installation height refer to the figure to the right When mounting the ultra long life filter unit to the existing indoor unit main body change the installation height of the indoor unit main bo...

Page 115: ...ber KDDFP55H160 is required when the ultra long life filter will be installed Model KAFP55H160H Item Average efficiency 50 Gravity method Number of sheets included 1 Air flow rate l sec 492 m3 min 29 5 Initial pressure loss Pa 8 or less Final pressure loss Pa 49 or less Filter element Mould proof resin net Life h 5 000 dust concentration 0 3 mg m3 Mass kg 3 4 Все каталоги и инструкции здесь http s...

Page 116: ...ions when attached 842 842 Model KDDFP55H160 Item Inserted filter High efficiency filter 65 colorimetric method KAFP552H80 KAFP552H160 90 colorimetric method KAFP553H80 KAFP553H160 Ultra long life filter KAFP55H160H Mass kg 8 0 Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 117: ...n the indoor unit main body is newly installed 1 Mount the filter chamber to the indoor unit main body using the hooks 4 positions Figure 1 to Figure 3 For the fixing method of the hooks refer to the figure to the right Mount at 4 positions Ultra long life filter 1 Name KAFP552H80 or KAFP553H80 2 Check the following parts Mounting status KAFP552H160 or KAFP553H160 BYCP125K W1 When using ultra long...

Page 118: ...te all the refrigerant and drain piping work for the indoor unit main body 02 Where there is considerable fouling Example Pachinko parlor etc 0 13 or 23 Setting switch number Installation height guideline 01 Setting position number 0 Where there is minimal fouling Example Office etc BYCP125K W1 Filter clasp 80 only Filter sign display interval time 1 Mounting of filter After the completion of wiri...

Page 119: ...Can be reused Model KAFP551K160 Item Average efficiency 60 Gravity method Number of sheets included 1 Air flow rate l sec 300 m3 min 18 Initial pressure loss Pa 4 9 or less Final pressure loss Pa 49 or less Filter element Mould proof and antibacterial resin net Life h 5 000 dust concentration 0 15 mg m3 Mass kg 0 2 Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 120: ... φ 156 φ 148 232 15 176 6 6 10 oblong holes 4 φ6 holes 179 256 382 167 200 232 177 11 φ 198 366 240 φ 206 106 Model KDJP55H80 KDJP55H160 Item Material Hot dip zinc coated carbon steel sheet with insulation Caution 1 When mounting refer to the installation manuals for the indoor unit and the decoration panel Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 121: ...iate for the room shape and installation position Blow directions other than those in the figure to the right cannot be selected From the external static pressure air volume characteristics refer to the technical guide select the duct length and air outlet Precautions Mounting of Branch Duct Chamber When an installation is performed after mounting the branch duct chamber to the indoor unit main bo...

Page 122: ... fire protection 3 When penetrating a wooden construction wall with a metal duct apply electrical insulation to the duct and wall Mounting of Sealing Material to Indoor Unit With the sealing material supplied in this kit blocking of two openings can be performed For the block position refer to then determine the position Always block the branch duct mounting surface Air outlet 1 Air outlet 3 3 way...

Page 123: ...Accessories ED34 862 118 FXFQ P KKSJ55K160 Chamber Connection Kit Dimensions Unit mm 3P089651D FOR FCQ KVLT FCQ N KVEA FXFQ PVE D Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 124: ...el insulation 2 t10 1 Side panel insulation 3 t10 1 Side panel insulation 4 t10 1 slit slit slit slit perforation 2 hole Top panel insulation 1 t10 1 Top panel insulation 2 t10 1 Top panel insulation 3 t10 1 Insulation for decoration panel t5 4 Model KDTP55K80 KDTP55K160 Item Material Polyethylene foam Maximum temperature 40 CDB RH85 Accessories Insulation for hanger bracket Installation manual Вс...

Page 125: ...ween Figure 1 When mounting the fresh air intake kit KDDP55X160 cut off the side insulator plate 2 with a cutter knife along the perforation The cut off insulator is no longer needed 2 Stick the top insulator plates 1 to 3 without leaving any gap in between Also stick the top insulator plates without leaving any gap against the side insulator plates all the way around Figure 2 3 Hang the product 4...

Page 126: ...122 2 Specifications 124 3 Dimensions 126 4 Piping Diagrams 130 5 Wiring Diagrams 131 6 Electric Characteristics 133 7 Capacity Tables 134 7 1 Cooling Capacity 134 8 Sound Levels 135 9 Installation 136 10 Accessories 139 Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 127: ... industry with whisper quietness Low operation sound Less weight Improvement in installation and design flexibility Reduction of weight of both main unit and panel Standardized sectional module Matching the center of main unit and panel Less maintenance Flat type suction grille of easy cleaning Detachable blade To minimize the soiling of the ceiling Все каталоги и инструкции здесь http splitoff ru...

Page 128: ...e suction grille Easy to clean because of flat shape Cleaning of the air discharge flap Detachability The flap can be detached with one touch without removing the panel Detachment of air discharge flap Position of Auto Swing Standard Position Ceiling Soiling Prevention Position Operation of Auto Swing Flaps swing within the range of 0 60 5 Steps of Direction 5 steps within the range of 0 60 5 step...

Page 129: ... φ6 4 Flare Connection Gas Pipes mm φ12 7 Flare Connection φ12 7 Flare Connection φ12 7 Flare Connection φ12 7 Flare Connection Drain Pipe mm VP25 External Dia 32 Internal Dia 25 VP25 External Dia 32 Internal Dia 25 VP25 External Dia 32 Internal Dia 25 VP25 External Dia 32 Internal Dia 25 Machine Weight Mass kg 26 26 26 31 4 Sound Level H L 220V dBA 32 27 34 28 34 28 34 29 Safety Devices Fuse Ther...

Page 130: ...n φ9 5 Flare Connection Gas Pipes mm φ12 7 Flare Connection φ15 9 Flare Connection φ15 9 Flare Connection φ15 9 Flare Connection Drain Pipe mm VP25 External Dia 32 Internal Dia 25 VP25 External Dia 32 Internal Dia 25 VP25 External Dia 32 Internal Dia 25 VP25 External Dia 32 Internal Dia 25 Machine Weight Mass kg 32 35 47 48 4 Sound Level H L 220V dBA 34 29 37 32 39 34 44 38 Safety Devices Fuse The...

Page 131: ...2 I D φ25 Drain hose φ12 7mm flare connection Require space Socket for drain Air discharge port Drain pipe connection port Power wiring port Description 1500mm or more Gas pipe connection port Number 5 7 4 9 6 1 2 8 3 Port for water supply Air suction grille φ6 4mm flare connection Notes 1 Location of unit s Name plate For Main body Filter install plate inside surface of suction grille For decorat...

Page 132: ... 20 1000 or more 350 or more 360 45 85 45 55 1205 Ceiling opening 8 40 290 1245 175 160 185 4 M8 M10 20 3 9 6 2 135 1035 Suspension position 360 1 4 990 305 600 8 520 Suspension position 20 135 680 290 300 or less 90 40 Branch duct connection 175 7 B View A View Notes 1 Location of unit s Name plate For Main body Filter install plate inside surface of suction grille For decoration panel Panel fram...

Page 133: ...nection Require space Socket for drain Air discharge port Drain pipe connection port Power wiring port Description 1500mm or more Gas pipe connection port Number 5 7 4 9 6 1 2 8 3 Port for water supply Air suction grille φ9 5mm flare connection Notes 1 Location of unit s Name plate For Main body Filter install plate inside surface of suction grille For decoration panel Panel frame inside surface o...

Page 134: ...5 Drain hose φ15 9mm flare connection Require space Socket for drain Air discharge port Drain pipe connection port Power wiring port Description 1500mm or more Gas pipe connection port Number 5 7 4 9 6 1 2 8 3 Port for water supply Air suction grille φ9 5mm flare connection Notes 1 Location of unit s Name plate For Main body Filter install plate inside surface of suction grille For decoration pane...

Page 135: ...n port diameters Electronic expansion valve Filter M Heat exchanger Filter Fan Liquid pipe connection port Gas pipe connection port 4D034245C mm Model Gas Liquid FXCQ20 25 32 40 50M φ12 7 φ6 4 FXCQ63 80 125M φ15 9 φ9 5 Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 136: ...TRONIC EXPANSION VALVE WIRED REMOTE CONTROLLER THERMISTOR AIR SELECTOR SWITCH MAIN SUB TERMINAL BLOCK CONTROL TERMINAL BLOCK POWER R1T R2T R3T S1L S1Q T1R X2M Y1E X1M R1T SS1 B RECEIVER DISPLAY UNIT ATTACHED TO WIRELESS REMOTE CONTROLLER PRINTED CIRCUIT BOARD A2P PRINTED CIRCUIT BOARD A3P PUSH BUTTON ON OFF BS1 LIGHT EMITTING DIODE ON RED H1P LIGHT EMITTING DIODE TIMER GREEN H2P LIGHT EMITTING DIO...

Page 137: ...HE INSTALLATION MANUAL ATTACHED THE UNIT 6 SYMBOLS SHOWS AS FOLLOWS PNK PINK WHT WHITE YLW YELLOW ORG ORANGE BLU BLUE BLK BLACK RED RED BRN BROWN GRN GREEN 7 USE COPPER CONDUCTORS ONLY INDOOR UNIT CAPACITOR M1F FUSE 5A 250V LIGHT EMITTING DIODE SERVICE MONITOR GREEN MAGNETIC RELAY M1F MAGNETIC RELAY M1S MAGNETIC RELAY M1P MOTOR INDOOR FAN MOTOR DRAIN PUMP MOTOR SWING FLAP THERMO SWITCH M1F EMBEDDE...

Page 138: ...D34 862 Electric Characteristics FXCQ M 133 3 6 Electric Characteristics C 4D034243A FXCQ20M FXCQ25 32M FXCQ40 50M FXCQ63M FXCQ80M FXCQ125M Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 139: ... 0 4 8 3 8 5 7 4 2 6 6 4 7 7 1 4 9 7 4 4 8 7 5 4 5 7 7 4 3 39 0 1 9 1 7 2 3 1 9 2 6 2 1 2 8 2 2 2 9 2 2 2 9 2 0 3 0 1 9 39 0 4 8 3 8 5 7 4 2 6 6 4 7 7 1 4 9 7 2 4 7 7 4 4 5 7 6 4 3 32 10 0 2 4 2 1 2 9 2 3 3 4 2 5 3 6 2 6 3 8 2 6 4 3 2 7 4 7 2 7 80 10 0 6 1 5 2 7 2 5 7 8 4 6 2 9 0 6 3 9 6 6 5 10 8 6 8 11 8 6 7 12 0 2 4 2 1 2 9 2 3 3 4 2 5 3 6 2 6 3 8 2 6 4 3 2 7 4 7 2 7 12 0 6 1 5 2 7 2 5 7 8 4 6 2...

Page 140: ...g on a range of factors such as the construction acoustic absorption coefficient of the particular room in which the equipments installed dBA Model 220V 50Hz 240V 50Hz H L H L FXCQ20M 32 27 34 29 FXCQ25M FXCQ32M 34 28 36 30 FXCQ40M FXCQ50M 34 29 37 32 FXCQ63M 37 32 39 34 FXCQ80M 39 34 41 36 FXCQ125M 44 38 46 40 FXCQ20MVE FXCQ25 32MVE FXCQ40 50MVE FXCQ63MVE FXCQ80MVE FXCQ125MVE Microphone 4D034329 ...

Page 141: ...s 3PR01906 7R Model A B C D FXCQ20 25 32MVE 990 820 775 1030 FXCQ40 50MVE 1205 1035 990 1245 FXCQ63MVE 1390 1220 1175 1430 FXCQ80 125MVE 1880 1710 1665 1920 3PR01906 7R Decoration panel Ceiling opening Indoor unit Suspension bolt 4 D Panel outside dimensions A Ceiling opening B Suspension pitch C Unit outside dimensions 20 20 20 20 680 Panel outside dimensions 640 Ceiling opening 600 Unit outside ...

Page 142: ...e into the drain socket up to the tape Tighten the clamp until the screw head is less than 4 mm from the hose Wrap the attached sealing pad over the clamp and drain hose to insulate Insulate the drain hose inside the building PRECAUTIONS FOR DRAIN RAISING PIPING Install the drain raising pipes at a height of less than 310 mm Install the drain raising pipes at a right angle to the indoor unit and n...

Page 143: ...de selector button until selecting FAN OPERATION Then press the ON OFF button The indoor unit fan and drain pump will start up Check that the water has drained from the unit Press to go back to the first mode Be careful when doing so because the fan is turning at the same time Attach the electric parts box lid as before CAUTION Drain piping connections Do not connect the drain piping directly to s...

Page 144: ...pe Large Small Name Washer for hanging bracket Clamp Screws M5 Other Operation manual Installation manual Quantity 8 pcs 8 pcs 4 pcs Shape For paper pattern for installation Type FXCQ20M FXCQ25M FXCQ32M FXCQ40M FXCQ50M FXCQ63M FXCQ80M FXCQ125M Item Decoration panel BYBC32G W1 BYBC50G W1 BYBC63G W1 BYBC125G W1 Filter related 1 High efficiency filter 65 KAFJ532G36 KAFJ532G56 KAFJ532G80 KAFJ532G160 1...

Page 145: ...50 50 50 50 W 780 995 1180 1670 D 600 600 600 600 Applicable Models 20 25 32 Class 40 50 Class 63 Class 80 125 Class Model Item KAFJ532G36 KAFJ532G56 KAFJ532G80 KAFJ532G160 KAFJ533G36 KAFJ533G56 KAFJ533G80 KAFJ533G160 External Dimensions H W D mm 30 460 145 2 30 675 145 2 30 860 145 2 30 660 145 4 30 460 145 2 30 675 145 2 30 860 145 2 30 660 145 4 Dust Collection Efficiency 65 Colorimetric method...

Page 146: ... plate located at the center of the indoor unit 2 Fasten the screw of the metal bracket tightly Replacement guide of capacitor for fan motor In case of KAFJ532G160 and KAFJ533G160 There are four filter frames of 2 kinds of each having different position of the metal bracket Install the filter frames to the indoor unit as shown below Capacity of a capacitor to be replaced Model Capacitor s Capacity...

Page 147: ...Accessories ED34 862 142 FXCQ M Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 148: ...44 2 Specifications 145 3 Dimensions 146 4 Piping Diagrams 148 5 Wiring Diagrams 149 6 Electric Characteristics 150 7 Capacity Tables 151 7 1 Cooling Capacity 151 8 Sound Levels 152 9 Installation 153 10 Accessories 156 Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 149: ...rovided by mounting an air discharge unit optional to the front of the body can be mounted even with difficult elements such as suspended ceilings and sagging walls A combination of front and downward discharge is also possible Auto swing cannot be used with front discharge Equipped with a programmed drying mechanism that dehumidifies while inhibiting changes in room temperature Includes as standa...

Page 150: ...e Connection φ12 7 Flare Connection φ15 9 Flare Connection Drain Pipe mm VP25 External Dia 32 Internal Dia 25 VP25 External Dia 32 Internal Dia 25 VP25 External Dia 32 Internal Dia 25 VP25 External Dia 32 Internal Dia 25 Machine Weight Mass kg 31 31 31 34 4 Sound Level H L 220V dBA 38 33 38 33 40 34 42 37 Safety Devices Fuse Thermal Fuse for Fan Motor Fuse Thermal Fuse for Fan Motor Fuse Thermal F...

Page 151: ...ing 10 Discharge Gas pipe connection Grounding terminal Notes 1 Location of unit s Name plate For main body Bottom part of fan housing inside of Air suction grille For decoration panel Service lid face inside of Air suction grille 2 When installing an optional accessory refer to the installation drawings 3 φ12 7 flare connection 1 5 Inside switch box M4 Number 9 7 4 M8 M10 2 Long life filter φ6 4 ...

Page 152: ...ischarge Gas pipe connection Grounding terminal Notes 1 Location of unit s Name plate For main body Bottom part of fan housing inside of Air suction grille For decoration panel Service lid face inside of Air suction grille 2 When installing an optional accessory refer to the installation drawings φ15 9 flare connection Inside switch box M4 Number Long life filter φ9 5 flare connection VP25 O D φ32...

Page 153: ...nection port diameters Electronic expansion valve Filter M Heat exchanger Filter Fan Liquid pipe connection port Gas pipe connection port 4D034245C mm Model Gas Liquid FXKQ25 32 40MA φ12 7 φ6 4 FXKQ63MA φ15 9 φ9 5 Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 154: ... MOTOR SWING FLAP THERMO SWITCH M1F EMBEDDED A1P A2P C1 F1U HAP K1R K3R KAR KPR M1F M1P M1S Q1M THERMISTOR AIR THERMISTOR COIL FLOAT SWITCH LIMIT SWITCH SWING FLAP TRANSFORMER 220 240V 22V ELECTRONIC EXPANSION VALVE WIRED REMOTE CONTROLLER THERMISTOR AIR SELECTOR SWITCH MAIN SUB CONNECTOR ADAPTOR FOR WIRING CONNECTOR WIRING ADAPTOR FOR ELECTORICAL APPENDICES CONNECTOR FOR OPTIONAL PARTS TERMINAL B...

Page 155: ...Electric Characteristics ED34 862 150 FXKQ MA 6 Electric Characteristics FXKQ25MA FXKQ32MA FXKQ40MA FXKQ63MA C 4D037076B Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 156: ... 9 2 7 4 0 2 6 37 0 2 4 2 2 2 9 2 5 3 4 2 6 3 6 2 7 3 7 2 8 3 8 2 7 3 9 2 6 39 0 2 4 2 2 2 9 2 5 3 4 2 6 3 6 2 7 3 7 2 8 3 8 2 7 3 8 2 6 40 10 0 3 0 2 6 3 6 2 8 4 2 3 2 4 5 3 2 4 8 3 3 5 4 3 5 5 9 3 5 12 0 3 0 2 6 3 6 2 8 4 2 3 2 4 5 3 2 4 8 3 3 5 4 3 5 5 8 3 5 14 0 3 0 2 6 3 6 2 8 4 2 3 2 4 5 3 2 4 8 3 3 5 4 3 5 5 8 3 4 16 0 3 0 2 6 3 6 2 8 4 2 3 2 4 5 3 2 4 8 3 3 5 4 3 5 5 7 3 4 18 0 3 0 2 6 3 6...

Page 157: ...ined in a dead room conversion values Sound level will vary depending on a range of factors such as the construction acoustic absorption coefficient of the particular room in which the equipments installed dBA Model 220V 50Hz 240V 50Hz H L H L FXKQ25MA FXKQ32MA 38 33 40 35 FXKQ40MA 40 34 42 36 FXKQ63MA 42 37 44 39 FXKQ25 32MAVE FXKQ40MAVE FXKQ63MAVE 4D037071 4D037072 4D037073 Все каталоги и инстру...

Page 158: ...0 1200 1240 FXKQ63MAVE 1310 1350 1400 1440 Indoor unit Drain pump kit FXKQ MA Standard Equipped with indoor unit C 4D037079A Unit mm 200 or more 200 or more 1000 or more 2500 or more For installation in high places 20 or more Suction side Discharge side 220 or more 1500 or more 3P086156 8V D C B A 800 760 710 350 Decoration panel Indoor unit Suspension bolt 4 Ceiling opening Все каталоги и инструк...

Page 159: ...he figure on the right insulate the clamp and drain hose with the large sealing pad If the drain hose cannot be sufficiently set on a slope execute the drain raising piping Secure a downward gradient of 1 100 or more for the drain pipe To accomplish this mount supporting brackets at an interval of 1 1 5 m Precautions when doing drain up piping work Make sure the drain up piping is at most 330 mm h...

Page 160: ...n the remote controller The unit will engage the test operation mode Press the operation mode selector button until selecting FAN OPERATION Then press the ON OFF button The indoor unit fan and drain pump will start up Check that the water has drained from the unit Press to go back to the first mode CAUTION Drain piping connections Do not connect the drain piping directly to sewage pipes that smell...

Page 161: ...jig for installation Air outlet blocking pad Other Operation manual Installation manual Quantity 8 pcs 8 pcs 2 each 1 pc Shape Type FXKQ25MA FXKQ32MA FXKQ40MA FXKQ63MA Item Panel related Decoration panel BYK45FJW1 BYK71FJW1 Long life replacement filter KAFJ521F56 KAFJ521F80 Air inlet and air discharge outlet related Air discharge grill K HV7AW K HV9AW Air discharge blind panel KDBJ52F56W KDBJ52F80...

Page 162: ...bove ceiling Contents of Kit Prior to installation check whether you have the complete kit of parts as shown below including the installation manual Model Item KPBJ52F56W KPBJ52F80W Color White Dimensions mm Height 20 Width 1 240 1 440 Depth 800 Materials Outer Frame Resin Molding Thermal Insulation Foam Polyethylene Contents Panel Spacer 1 2 3 Thermal Insulation 1 2 Screws Applicable Decoration P...

Page 163: ...od Filter Mildew Proof Resin Net Mildew Proof Resin Net Required Quantity for One Unit Two pieces Two pieces Applicable Models 25 32 40 Class 63 Class Model A KAFJ521F56 403 KAFJ521F80 503 JC D3K1145A Model Items K HV7AW K HV9AW Air Flow Rate m min 5 12 7 17 Type HV type Horizontal blade and vertical blade movable External Color White White Materials Steel plate A cryptomeria only at the tip of th...

Page 164: ... KFDJ52FA56 KFDJ52FA80 External Dimension mm H 132 W 532 732 D Max 353 Materials Outer frame Steel plate Flexible Duct Glass wool Vinyl chloride sheet Contents Flexible duct Shutter Duct s set plate Insulator Outlet seal pad Set screw Shutter Open shut tool Blade adjusting tool Applicable Models 25 32 40 Class 63 Class Pressure Loss Air Flow Rate m s Discharge Velocity 91 AC AA AE 4 6 10 Oblong ho...

Page 165: ...Installation Model Applicable Model A B C D E F KFDJ52FA56 For Indoor Unit 25 40 Class 260 520 466 498 530 4 φ Hole KFDJ52FA80 For Indoor Unit 63 Class 460 720 666 698 730 6 φ7 Hole Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 166: ...6W KDBJ52F80W External color White White External Dimension mm T 18 W 1 126 1 326 D 119 Materials Steel plate Contents Outlet decoration panel assembly Decoration panel suspension plate Name Plate Caution plate set board Applied Decoration Panel BYK45FJW1 BYK71FJW1 Applicable Models 25 32 40 Class 63 Class Model A B KDBJ52F56 1125 5 1040 KDBJ52F80 1325 5 1240 Все каталоги и инструкции здесь http s...

Page 167: ...Accessories ED34 862 162 FXKQ MA Dimensions with the Optional Accessories Panel Spacer FXKQ25 40MA FXKQ63MA Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 168: ...grams 173 5 Wiring Diagrams 174 6 Electric Characteristics 176 7 Capacity Tables 177 7 1 FXDQ PB 177 7 2 FXDQ NB 178 8 Fan Performances 179 8 1 FXDQ PB 179 8 2 FXDQ NB 180 9 Sound Levels 181 9 1 FXDQ PB 181 9 2 FXDQ NB 182 10 Center of Gravity 183 10 1 FXDQ PB 183 10 2 FXDQ NB 184 11 Installation 185 12 Accessories 199 12 1 FXDQ PB FXDQ NB 199 Все каталоги и инструкции здесь http splitoff ru tehn ...

Page 169: ... 100 mm in width for the FXDQ63NB model 200 mm 900 mm Suction grille AIR AIR Discharge grille Air filter Suspension bolt 240 mm To be obtained locally FXDQ PB and FXDQ NB models are available in two types to suit different installation conditions FXDQ PBVE FXDQ NBVE with a drain pump 750 mm lift as a standard accessory FXDQ P NBVET without a drain pump Control of the airflow rate has been improved...

Page 170: ...Direct Drive Direct Drive Direct Drive Temperature Control Microprocessor Thermostat for Cooling and Heating Microprocessor Thermostat for Cooling and Heating Microprocessor Thermostat for Cooling and Heating Sound Absorbing Thermal Insulation Material Foamed Polyethylene Foamed Polyethylene Foamed Polyethylene Air Filter Removal Washable Mildew Proof Removal Washable Mildew Proof Removal Washable...

Page 171: ...Direct Drive Direct Drive Direct Drive Temperature Control Microprocessor Thermostat for Cooling and Heating Microprocessor Thermostat for Cooling and Heating Microprocessor Thermostat for Cooling and Heating Sound Absorbing Thermal Insulation Material Foamed Polyethylene Foamed Polyethylene Foamed Polyethylene Air Filter Removal Washable Mildew Proof Removal Washable Mildew Proof Removal Washable...

Page 172: ...ERVICE SPACE OF INSTALLATION BOX FOR ADAPTOR PCB IN CASE OF BOTTOM SUCTION 240 OR MORE IN CASE OF BACK SUCTION 3 NAME CONTROL BOX NUMBER VP20 O D φ 26 I D φ 20 2 GAS PIPE CONNECTION 7 POWER SUPPLY CONNECTION TRANSMISSION WIRING CONNECTION I D φ 25 OUTLET DESCRIPTION DRAIN PIPE CONNECTION SUSPENSION BRACKET 8 4 5 DRAIN HOSE ACCESSORY φ 6 4 FLARE CONNECTION φ 12 7 FLARE CONNECTION 1 9 6 LIQUID PIPE ...

Page 173: ...53 16 M5 HOLES ALL AROUND 620 80 63 16 M5 HOLES ALL AROUND 400 OR MORE IN CASE OF BOTTOM SUCTION 47 10 140 20 90 57 5 140 60 680 300 OR MORE 170 20 OR MORE 21 5 P100 500 180 20 OR MORE 12 5 600 580 5 P100 500 620 10 5 P100 500 80 50 90 170 330 200 20 100 4 P150 600 200 500 50 740 100 300 OR MORE 100 14 M4 HOLES ALL AROUND 660 700 100 620 30 600 580 620 SUSPENSION BOLT 4 M8 M10 90 700 160 130 160 1...

Page 174: ...SPENSION BRACKET POWER SUPPLY CONNECTION TRANSMISSION WIRING CONNECTION CONTROL BOX DRAIN HOSE ACCESSORY DRAIN PIPE CONNECTION GAS PIPE CONNECTION LIQUID PIPE CONNECTION 620 200 300 OR MORE SERVICE SPACE OF INSTALLATION BOX FOR ADAPTOR PCB IN CASE OF BOTTOM SUCTION 820 6 90 50 800 20 80 11 100 7 P100 700 160 200 180 130 20 M5 HOLES ALL AROUND 100 10 780 90 SUSPENSION BOLT 7 P100 700 50 20 100 7 15...

Page 175: ...TALLATION BOX FOR ADAPTOR PCB IN CASE OF BOTTOM SUCTION IN CASE OF BOTTOM SUCTION NOTE 1 IN CASE OF BACK SUCTION MOUNT CHAMBER COVER TO BOTTOM SIDE OF THE UNIT IN CASE OF BOTTOM SUCTION MOUNT CHAMBER COVER TO BACK SIDE OF THE UNIT 2 LOCATION OF UNIT S NAME PLATE CONTROL BOX COVER 3 MOUNT THE AIR FILTER AT THE SUCTION SIDE SELECT ITS COLORIMETHOD GRAVITY METHOD 50 OR MORE IT CAN NOT BE EQUIPPED WIT...

Page 176: ...G SUSPENSION BOLT 330 180 63 57 5 900 170 SERVICE SPACE OF INSTALLATION BOX FOR ADAPTOR PCB A 3 NAME CONTROL BOX NUMBER VP20 O D φ 26 I D φ 20 2 GAS PIPE CONNECTION 7 POWER SUPPLY CONNECTION TRANSMISSION WIRING CONNECTION I D φ 25 OUTLET DESCRIPTION SOCKET FOR DRAIN SUSPENSION BRACKET 8 4 5 DRAIN HOSE ACCESSORY φ 6 4 FLARE CONNECTION φ 12 7 FLARE CONNECTION 1 9 AIR FILTER ACCESSORY 6 LIQUID PIPE C...

Page 177: ...ORE 20 1000 20 9 P100 900 153 9 P100 900 2 57 5 7 130 90 300 160 170 24 M5 HOLES 18 M4 HOLES 5 1060 60 9 160 23 1100 500 24 M5 HOLES 47 80 1020 1140 63 100 10 240 OR MORE 170 900 1000 980 200 20 OR MORE 8 330 300 OR MORE 300 300 OR MORE 6 P150 900 10 P100 1000 9 200 180 980 6 CEILING 180 620 1080 10 3 100 SUSPENSION BOLT 130 80 90 100 12 5 4 90 150 80 100 SERVICE SPACE OF INSTALLATION BOX FOR ADAP...

Page 178: ... pipe connection port diameters mm Model Gas Liquid FXDQ20 25 32PBVE T 40 50NBVE T φ12 7 φ6 4 FXDQ63NBVE T φ15 9 φ9 5 Fan Indoor heat exchanger Filter Filter Electronic expansion valve Liquid side Gas side 4D060927 Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 179: ...A MOTOR INDOOR FAN CAPACITOR M1F X7A R2T WHT THERMISTOR AIR HAP X4A X27A NOTE 3 THERMISTOR AIR BLU C1 X2M YLW RED THERMISTOR COIL 2 YLW R3T CONNECTOR WIRING ADAPTOR FOR ELECTRICAL APPENDICES FUSE F5A 250V X12A t t t F2 T2 F1 P1 P2 T1 F1U FLOAT SWITCH PRP NOTE 5 50Hz 60Hz A1P C1 F1U HAP KPR M1F M1P Q1M R1T R2T R3T S1L T1R V1TR X1M X2M Y1E Z1C Z2C R1T SS1 X16A X18A NOTES 1 TERMINAL CONNECTOR 2 FIELD...

Page 180: ...LS AND CATALOGS ETC BEFORE CONNECTING 5 WHEN CONNECTING THE INPUT WIRES FROM OUTSIDE FORCED OFF OR ON OFF CONTROL OPERATION CAN BE SELECTED BY REMOTE CONTROLLER IN DETAILS REFER TO THE INSTALLATION MANUAL ATTACHED THE UNIT 6 SYMBOLS SHOW AS FOLLOWS RED RED BLK BLACK WHT WHITE YLW YELLOW PRP PURPLE GRY GRAY BLU BLUE PNK PINK ORG ORANGE GRN GREEN SELECTOR SWITCH MAIN SUB TRANSFORMER 220V 22V CONNECT...

Page 181: ...Electric Characteristics ED34 862 176 FXDQ PB FXDQ NB 6 Electric Characteristics C 4D060922 Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 182: ...2 2 3 4 2 2 21 0 1 9 1 6 2 3 1 9 2 6 2 1 2 8 2 1 3 0 2 2 3 4 2 2 3 4 2 2 23 0 1 9 1 6 2 3 1 9 2 6 2 1 2 8 2 1 3 0 2 2 3 3 2 2 3 4 2 1 25 0 1 9 1 6 2 3 1 9 2 6 2 1 2 8 2 1 3 0 2 2 3 3 2 2 3 3 2 1 27 0 1 9 1 6 2 3 1 9 2 6 2 1 2 8 2 1 3 0 2 2 3 2 2 2 3 3 2 1 29 0 1 9 1 6 2 3 1 9 2 6 2 1 2 8 2 1 3 0 2 2 3 2 2 1 3 2 2 1 31 0 1 9 1 6 2 3 1 9 2 6 2 1 2 8 2 1 3 0 2 2 3 1 2 1 3 2 2 1 33 0 1 9 1 6 2 3 1 9 2...

Page 183: ...0 21 0 3 8 3 1 4 5 3 5 5 2 3 9 5 6 4 0 6 0 4 0 6 7 4 2 6 8 4 0 23 0 3 8 3 1 4 5 3 5 5 2 3 9 5 6 4 0 6 0 4 0 6 6 4 2 6 7 3 9 25 0 3 8 3 1 4 5 3 5 5 2 3 9 5 6 4 0 6 0 4 0 6 5 4 1 6 6 3 9 27 0 3 8 3 1 4 5 3 5 5 2 3 9 5 6 4 0 6 0 4 0 6 4 4 1 6 6 3 9 29 0 3 8 3 1 4 5 3 5 5 2 3 9 5 6 4 0 6 0 4 0 6 3 4 0 6 5 3 8 31 0 3 8 3 1 4 5 3 5 5 2 3 9 5 6 4 0 6 0 4 0 6 2 4 0 6 4 3 8 33 0 3 8 3 1 4 5 3 5 5 2 3 9 5 6...

Page 184: ...h ESP High high ESP Low standard ESP U p p e r l i m i t o f e x t e r n a l s t a t i c p r e s s u r e h i g h E S P Upper limit of external static pressure standard ESP Lower limit of external static pressure high ESP 3D052156A 6 8 7 9 10 Pa 5 6 External static pressure 50 Air flow rate m 3 min 4 40 30 2 60 Pa 1 3 20 mmH2O mmH2O 3 4 5 2 6 1 mmH2O mmH2O High standard ESP Low high ESP High high E...

Page 185: ... External static pressure 50 Air flow rate m 3 min 4 70 40 30 2 60 Pa 1 3 7 20 mmH2O mmH2O 3 4 5 2 6 1 7 mmH2O mmH2O High standard ESP Low high ESP High high ESP Low standard ESP U p p e r l i m i t o f e x t e r n a l s t a t i c p r e s s u r e h i g h E S P U p p e r l i m i t o f e x t e r n a l s t a t i c p r e s s u r e s t a n d a r d E S P Lower limit of external static pressure standard ...

Page 186: ...alues were obtained in a dead room conversion values Sound level will vary depending on a range of factors such as the construction acoustic absorption coefficient of the particular room in which the equipments installed dBA Model 220 240V 50Hz HH H L FXDQ20PBVE T 33 31 29 FXDQ25PBVE T 33 31 29 FXDQ32PBVE T 33 31 29 FXDQ20PBVE T FXDQ25PBVE T FXDQ32PBVE T 4D060945 4D060946 4D060947 Все каталоги и и...

Page 187: ...re obtained in a dead room conversion values Sound level will vary depending on a range of factors such as the construction acoustic absorption coefficient of the particular room in which the equipments installed dBA Model 220 240V 50Hz HH H L FXDQ40NBVE T 34 32 30 FXDQ50NBVE T 35 33 31 FXDQ63NBVE T 36 34 32 FXDQ40NBVE T FXDQ50NBVE T FXDQ63NBVE T 4D060948 4D060949 4D060950 Все каталоги и инструкци...

Page 188: ...ED34 862 Center of Gravity FXDQ PB FXDQ NB 183 5 10 Center of Gravity 10 1 FXDQ PB FXDQ20 25 32PBVE T 4D049300D Unit mm Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 189: ...Center of Gravity ED34 862 184 FXDQ PB FXDQ NB 10 2 FXDQ NB FXDQ40 50NBVE T FXDQ63NBVE T 4D043886J Unit mm 4D043887H Unit mm Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 190: ...e to do so during installation work may result in the unit falling and causing accidents Make sure that a separate power supply circuit is provided for this unit and that all electrical work is carried out by qualified personnel according to local laws and regulations and this installation manual An insufficient power supply capacity or improper electrical construction may lead to electric shocks ...

Page 191: ...the type of R410A refrigerant to be used before installing the unit Using an incorrect refrigerant will prevent normal opera tion of the unit For the installation of an outdoor unit refer to the installation manual attached to the outdoor unit 2 1 PRECAUTIONS Be sure to instruct customers how to properly operate the unit operating different functions and adjusting the temper ature by having them c...

Page 192: ...order to prevent image interference or noise Depending on the radio waves a distance of 1 m may not be sufficient enough to eliminate the noise If installing the wireless kit in a room with electronic fluo rescent lighting inverter or rapid start type the remote controller s transmission distance may be shortened Indoor units should be installed as far away from fluores cent lighting as possible 2...

Page 193: ... to M10 suspension bolts Use a hole in anchor for existing ceilings and a sunken insert sunken anchor or other part to be procured in the field to reinforce the ceiling to bearing the weight of the unit for new ceiling Refer to Fig 3 5 For bottom intake replace the chamber lid and protec tion net in the procedure listed in Fig 4 1 Remove the protection net 6 locations PBVE T type only Remove the c...

Page 194: ... the tempera ture above the ceiling might reach 30 C or the humidity RH80 Condensation may form on the surface of the insu lation CAUTION Follow the points at below Use a pipe cutter and flare suitable for the type of refrigerant Apply ester oil or ether oil to the flare section when using a flare connection Only use the flare nuts included with the unit Using different flare nuts may cause the re...

Page 195: ...CuP 2 JIS Z 3264 B Cu93P 710 795 ISO 3677 which does not require flux Using a flux containing chlorine may cause the piping to corrode Using a welding flux containing fluorine may cause the refrigerant lubricant to deteriorate and affect adversely the refrigerant piping system Not recommendable but in case of emergency You must use a torque wrench but if you are obliged to install the unit without...

Page 196: ...vertically and make sure it is no further than 300mm from the unit Refer to Fig 13 PRECAUTIONS Drain piping connections Do not connect the drain piping directly to sewage pipes that smell of ammonia The ammonia in the sewage might enter the indoor unit through the drain piping and corrode the heat exchanger Do not twist or bend the drain hose 2 so that excessive force is not applied to it This typ...

Page 197: ...l to the diameter of the connecting pipe vinyl tube pipe size 20 mm outer dimension 26 mm not including the riser Keep the drain piping short and sloping downwards at a gra dient of at least 1 100 to prevent air pockets from forming Refer to Fig 14 CAUTION Water accumulating in the drain piping can cause the drain to clog To keep the drain piping from sagging space hanging bracket every 1 to 1 5 m...

Page 198: ... off the power before doing any work All field supplied parts and materials electric works must conform to local codes Use copper wire only See also the Wiring Diagram plate attached to the control box lid when laying electrical wiring For details on hooking up the remote controller refer to the REMOTE CONTROLLER INSTALLATION MANUAL All wiring must be performed by an authorized electrician This sy...

Page 199: ...ey do not pass through the same place together Proximity may cause electrical interference malfunctions and breakage Outdoor unit Indoor unit Max 1000m Total wiring length 2000m Indoor unit Remote controller Max 500m Units Power supply Fan motor Model Hz Volts Voltage range MCA MFA KW FLA 20 25 32 PBVE 50 220 240 Min 198 Max 264 0 8 15 0 062 0 6 20 25 32 PBVET 0 7 0 062 0 6 40 NBVE T 1 0 0 062 0 8...

Page 200: ...r supply wiring For wiring use the designated power supply wiring and con nect firmly then secure to prevent outside pressure being exerted on the terminal board Use the correct screwdriver for tightening the terminal screws If the blade of screwdriver is too small the head of the screw might be damaged and the screw will not be prop erly tightened If the terminal screws are tightened too hard scr...

Page 201: ... unit address when using group control It is automatically set when the power is turned on Indoor unit A Indoor unit B Most down stream indoor unit For use with 2 remote controllers Case of group control L N Fig 20 Remotecontroller Remote controller Remotecontroller 1 P 2 P 1 P 2 P 1 P 2 P 1 P P 2 1 F 2 N F L N L 1 2 F F1 2 F F1 2 T T 1 P P 2 1 F 2 F1 2 T T N L 1 P P 2 1 F 2 F1 2 T T IN D OUT D op...

Page 202: ...F operation should be selected by selecting the SECOND CODE NO as shown in the table below The SECOND CODE NO is set to 01 when shipped Input A of forced off and ON OFF operation work as shown in the table below 11 3 SETTING THE FILTER SIGN DISPLAY INTERVAL Explain the following to the customer if the filter dirt settings have been changed The filter sign display time is set to 2500 hours equivale...

Page 203: ... the display shows any of the following there is a possi bility that the wiring was done incorrectly or that the power is not on so check again CAUTION Always stop the test run using the remote controller to stop operation 4 After finishing the test run make sure to check drain age in the drain pump according to 7 DRAIN PIPING WORK Remote control display Content display There is a short circuit at...

Page 204: ...kit for high humidity KDT25N32 KDT25N50 KDT25N63 Type Item FXDQ20PBVE T FXDQ25PBVE T FXDQ32PBVE T FXDQ40NBVE T FXDQ50NBVE T FXDQ63NBVE T Remote controller Wired BRC1C62 Wireless C O BRC4C66 Wired remote controller with weekly schedule timer BRC1D61 Simplified remote controller Exposed type BRC2C51 Remote controller for hotel use Concealed type BRC3A61 Adaptor for wiring KRP1B56 Wiring adaptor for ...

Page 205: ...T25N32 50 63 Insulation Kit for High Humidity Dimensions Unit mm Model KDT25N32 KDT25N50 KDT25N63 Item Material Foam polyethylene with Japanese paper Accessories Installation manual Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 206: ... 3 Dimensions 208 4 Piping Diagrams 216 5 Wiring Diagrams 217 6 Electric Characteristics 218 7 Capacity Tables 219 7 1 Cooling Capacity 219 8 Fan Performances 220 8 1 50Hz 220 9 Sound Levels 221 10 Installation 223 11 Accessories 226 Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 207: ...in pipe opening Quiet type air conditioner doesn t destroy the quiet mood of your office Two types of high efficiency filters 65 and 90 colorimetric method are available Cannot be used if using rear suction type Suction half panel is thin and unimposing Ceiling materials adhere to its surface and it provides an excellent finishing touch for the ceiling A wide variety of optional accessories are av...

Page 208: ...XSQ125M Necessary Options Remote Controller BRC1C62 Half Panel BYBS32DJW1 BYBS45DJW1 BYBS71DJW1 BYBS125DJW1 High Efficiency Filter NBS65 KAFJ252L36 KAFJ252L56 KAFJ252L80 KAFJ252L160 NBS90 KAFJ253L36 KAFJ253L56 KAFJ253L80 KAFJ253L160 Air Suction Canvas KSA 25K36 KSA 25K56 KSA 25K80 KSA 25L160 Bottom Suction Filter Chamber KAJ25L36D KAJ25L56D KAJ25L80D KAJ25L160D The access panel should be fitted be...

Page 209: ...TBJ25K36W KTBJ25K56W KTBJ25K80W KTBJ25K160W The access panel should be fitted beneath the main body of the unit Model FXSQ20M FXSQ25M FXSQ32M FXSQ40M FXSQ50M FXSQ63M FXSQ80M FXSQ100M FXSQ125M Necessary Options Remote Controller BRC1C62 Access Panel KTBJ25K36W KTBJ25K56W KTBJ25K80W KTBJ25K160W Screening Door KBBJ25K36 KBBJ25K56 KBBJ25K80 KBBJ25K160 Air Suction Flange KDJ2507K36 KDJ2507K56 KDJ2507K8...

Page 210: ...oprocessor Thermostat for Cooling and Heating Microprocessor Thermostat for Cooling and Heating Sound Absorbing Thermal Insulation Material Glass Fiber Glass Fiber Glass Fiber Air Filter Resin Net with Mold Resistant Resin Net with Mold Resistant Resin Net with Mold Resistant Piping Connections Liquid Pipes mm φ6 4 Flare Connection φ6 4 Flare Connection φ6 4 Flare Connection Gas Pipes mm φ12 7 Fla...

Page 211: ...r Thermostat for Cooling and Heating Microprocessor Thermostat for Cooling and Heating Sound Absorbing Thermal Insulation Material Glass Fiber Glass Fiber Glass Fiber Air Filter Resin Net with Mold Resistant Resin Net with Mold Resistant Resin Net with Mold Resistant Piping Connections Liquid Pipes mm φ6 4 Flare Connection φ6 4 Flare Connection φ9 5 Flare Connection Gas Pipes mm φ12 7 Flare Connec...

Page 212: ...ostat for Cooling and Heating Microprocessor Thermostat for Cooling and Heating Sound Absorbing Thermal Insulation Material Glass Fiber Glass Fiber Glass Fiber Air Filter Resin Net with Mold Resistant Resin Net with Mold Resistant Resin Net with Mold Resistant Piping Connections Liquid Pipes mm φ9 5 Flare Connection φ9 5 Flare Connection φ9 5 Flare Connection Gas Pipes mm φ15 9 Flare Connection φ1...

Page 213: ... position when installing the duct Position of Natural evaporating pan type humidifier Required installation space 2 65 130 595 Air suction panel center 3 1 Interunit wiring port Name VP25 O D φ32 I D φ25 6 Power wiring port 2 Drain hole φ12 7 flare connection 5 Gas pipe connection Liquid pipe connection VP25 O D φ32 I D φ25 7 Air filter 4 φ6 4 flare connection Number Description Drain pipe connec...

Page 214: ... air intake position when installing the duct Required installation space 2 65 130 425 or more 595 Air suction panel center The required ceiling depth varies according to configuration of specific system Notes 1 Location of unit s Name Plate Fan housing surface inside of filter 2 When installing an optional accessory refer to the installation drawings 3 Refer to the separate drawing when installin...

Page 215: ...n air intake position when installing the duct 2 65 130 595 Air suction panel center Required installation space The required ceiling depth varies according to configuration of specific system Notes 1 Location of unit s Name Plate Fan housing surface inside of filter 2 When installing an optional accessory refer to the installation drawings 3 Refer to the separate drawing when installing the duct ...

Page 216: ...0 Position of Natural evaporating pan type humidifier Suction air intake position when installing the duct 600 45 P C D φ160 Suspension bolt 25 200 7 The required ceiling depth varies according to configuration of specific system Notes 1 Location of unit s Name Plate Fan housing surface inside of filter 2 When installing an optional accessory refer to the installation drawings 3 Refer to the separ...

Page 217: ... 57 300 315 145 310 4 65 260 228 1 245 150 The required ceiling depth varies according to configuration of specific system Notes 1 Location of unit s Name Plate Fan housing surface inside of filter 2 When installing an optional accessory refer to the installation drawings 3 Refer to the separate drawing when installing the duct 4 Decoration panel and Air suction canvas are optional accessories Suc...

Page 218: ... 600 Note 3 Suction air intake position when installing the duct P C D φ160 Knockout hole φ125 Circumference 6 M5 hole Fresh air intake position View Note 2 Position of Natural evaporating pan type humidifier Notes 1 Location of unit s Name Plate Fan housing surface inside of filter 2 When installing an optional accessory refer to the installation drawings 3 Refer to the separate drawing when inst...

Page 219: ...uction air intake position when installing the duct P C D φ160 Knockout hole φ125 Circumference 6 M5 hole Fresh air intake position Note 2 Position of Natural evaporating pan type humidifier Notes 1 Location of unit s Name Plate Fan housing surface inside of filter 2 When installing an optional accessory refer to the installation drawings 3 Refer to the separate drawing when installing the duct 4 ...

Page 220: ...ng depth varies according to configuration of specific system Note 3 Suction air intake position when installing the duct Knockout hole φ125 P C D φ160 Circumference 6 M5 hole Note 2 Position of Natural evaporating pan type humidifier Notes 1 Location of unit s Name Plate Fan housing surface inside of filter 2 When installing an optional accessory refer to the installation drawings 3 Refer to the ...

Page 221: ...port diameters Electronic expansion valve Filter M Heat exchanger Filter Fan Liquid pipe connection port Gas pipe connection port 4D034245C mm Model Gas Liquid FXSQ20 25 32 40 50M φ12 7 φ6 4 FXSQ63 80 100 125M φ15 9 φ9 5 Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 222: ... K1M S1H X3M R1T SS1 R2T R3T TERMINAL BOARD CAPACITOR M1F FUSE 5A 250V MAGNETIC RELAY M1F MAGNETIC RELAY M1P MOTOR INDOOR FAN MOTOR DRAIN PUMP THERMO SWITCH 135 C OR 145 C NOTE9 M1F EMBEDDED THERMISTOR AIR THERMISTOR COIL FLOAT SWITCH TRANSFORMER 220 240V 22V TERMINAL BLOCK POWER TERMINAL BLOCK CONTROL ELECTRONIC EXPANSION VALVE OPTIONAL PARTS ELECTRIC HEATER FUSE 15A 250V HUMIDIFIER HUMIDISTAT TE...

Page 223: ...Electric Characteristics ED34 862 218 FXSQ M 6 Electric Characteristics C 4D036936A Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 224: ... 0 7 1 10 5 7 6 11 2 7 9 11 9 8 3 13 4 8 5 14 4 8 3 16 0 2 4 2 0 2 9 2 3 3 4 2 5 3 6 2 5 3 8 2 7 4 3 2 8 4 6 2 7 16 0 7 6 6 2 9 0 7 1 10 5 7 6 11 2 7 9 11 9 8 3 13 4 8 5 14 2 8 2 18 0 2 4 2 0 2 9 2 3 3 4 2 5 3 6 2 5 3 8 2 7 4 3 2 8 4 5 2 6 18 0 7 6 6 2 9 0 7 1 10 5 7 6 11 2 7 9 11 9 8 3 13 4 8 5 14 0 8 1 20 0 2 4 2 0 2 9 2 3 3 4 2 5 3 6 2 5 3 8 2 7 4 3 2 8 4 4 2 6 20 0 7 6 6 2 9 0 7 1 10 5 7 6 11 ...

Page 225: ...ard ESP High Low ESP Low Lower limit of external static pressure high ESP Lower limit of external static pressure standard ESP Lower limit of external static pressure Low ESP Intake panel Long life filter Air flow m 3 min Internal static pressure External static pressure C 3D036963 5 Upper lim it of external static pressure High standard ESP High Low ESP High high ESP Low Lower limit of external s...

Page 226: ...alues Sound level will vary depending on a range of factors such as the construction acoustic absorption coefficient of the particular room in which the equipments installed dBA Model 220V 50Hz 240V 50Hz H L H L FXSQ20M FXSQ25M 37 32 39 34 FXSQ32M FXSQ40M 38 32 40 34 FXSQ50M 41 36 43 38 FXSQ63M 42 35 44 37 FXSQ80M FXSQ100M 43 37 45 39 FXSQ125M 46 41 48 43 4D036937 Все каталоги и инструкции здесь h...

Page 227: ... Level 220V 50Hz 240V 50Hz FXSQ20 25MVE FXSQ32MVE FXSQ40MVE FXSQ50MVE FXSQ63MVE FXSQ80MVE FXSQ100MVE FXSQ125MVE 4D036937 4D036938 4D036939 4D036940 4D036941 4D036942 4D036943 4D036944 Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 228: ... mm Unit mm Indoor unit Drain pump kit FXSQ M Standard Equipped with indoor unit C 4D036946F Maintenance space For installation in high places 300 mm or more 2500 mm or more Drain pipe Liquid pipe Power supply wiring port Maintenance drain hose Transmission wiring port Gas pipe 3P086156 7D B A Pipe Suspension bolt pitch Indoor unit 800 Suspension bolt 4 145 Suspension bolt pitch 630 Model FXSQ20 2...

Page 229: ... PRECAUTIONS FOR DRAIN RAISING PIPING HOW TO INSTALL PIPING 1 Connect the drain hose to the drain raising pipes and insulate them 2 Connect the drain hose to the drain outlet on the indoor unit and tighten it with the metal clamp 3 Insulate both metal clamp and drain hose with the sealing pad If converging multiple drain pipes install according to the procedure shown below Select converging drain ...

Page 230: ...HOW TO CONNECT WIRINGS Next press the inspection test operation button on the remote controller The unit will engage the test operation mode Press the operation mode selector button until selecting FAN OPERATION Then press the ON OFF button The indoor unit fan and drain pump will start up Check that the water has drained from the unit Press to go back to the first mode You can check whether draina...

Page 231: ...XSQ80M FXSQ100M FXSQ125M Item 1 Panel related Decoration panel BYBS32DJW1 BYBS45DJW1 BYBS71DJW1 BYBS125DJW1 Access panel KTBJ25K36W KTBJ25K56W KTBJ25K80W KTBJ25K160W 2 1 Auxiliary electric heater Model 240V 220V KEA25K32VE KEA25K50VE KEA25K63VE KEA25K100VE KEA25K125VE Capacity kW 0 75 1 2 1 4 2 1 2 8 3 Filter related 2 High efficiency filter 65 KAFJ252L36 KAFJ252L56 KAFJ252L80 KAFJ252L160 2 High e...

Page 232: ...difier Auxiliary Electric Heater Filter Chamber For Bottom Suction Air Suction Canvas Half Panel Access Panel High Efficiency Filter 65 95 Long Life Replacement Filter Filter Chamber For Rear Suction Air Suction Flange Air Discharge Flange Screening Door Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 233: ...embly 2 Remove the decoration panel and substitute with the ceiling board 3 Set the ceiling board by retainer removed in step 1 of above CAUTION When the ceiling board is installed the decoration panel is not needed Model Item KTBJ25K36W KTBJ25K56W KTBJ25K80W KTBJ25K160W Color White Applicable Model 20 32 Class 40 50 Class 63 Class 80 125 Class Dimension Model A KTBJ25K36W 626 KTBJ25K56W 776 KTBJ2...

Page 234: ... separately needed for one indoor unit by one piece of the adaptor Model Items KEA25K32VE KEA25K50VE KEA25K63VE KEA25K100VE KEA25K125VE Heater Capacity kW 0 75 1 2 1 4 2 1 2 8 Power Supply Single Phase 220 240V 220V 50 60Hz Applicable Models 20 25 32 Class 40 50 Class 63 Class 80 100 Class 125 Class Installation Characteristics of filter Все каталоги и инструкции здесь http splitoff ru tehn doc ht...

Page 235: ...ter purifier or a water softener if these phenomena are found 3 Use water in the range of water temperature 5 50 C and water pressure 0 049 0 294 MPa 0 5 3kg cm Provide a reducing valve between a strainer and this kit in case of 0 294MPa or more for feed water pressure 4 The feed water pipe can not be connected to a public water route Accordingly if water must be supplied through a public water by...

Page 236: ...Life Time h 2 500 hours Dust density 0 15mg m 1 800 hours Dust density 0 15mg m High Efficiency Filter Chamber for the Bottom Suction KAJ25L36D KAJ25L56D KAJ25L80D KAJ25L160D KAJ25L36D KAJ25L56D KAJ25L80D KAJ25L160D High Efficiency Filter Chamber for the Rear Suction KAJ25L36B KAJ25L56B KAJ25L80B KAJ25L160B KAJ25L36B KAJ25L56B KAJ25L80B KAJ25L160B External Dimension mm T W D 25 500 360 25 650 360 ...

Page 237: ... Initial 10 or less 4 9 or less Final 49 49 or less Materials Mildew Proof Resin Net Number Required per Model 1 1 2 2 Life Time h 2 500 hours dust particle concentration at 0 15 mg m Applicable Model 20 25 32 Class 40 50 Class 63 Class 80 100 125 Class Model Item KSA 25K36 KSA 25K56 KSA 25K80 KSA 25K160 Dimensions mm H 255 255 255 255 W 550 700 1000 1400 D 405 405 405 405 Canvas Duct TOYOBO SL100...

Page 238: ...arge Adaptor Specifications Model Item KDAJ25K36A KDAJ25K56A KDAJ25K71A KDAJ25K140A Connection Dia φmm φ200 1 port φ200 2 port φ200 2 port φ200 4 port Applicable Models 20 25 32 Class 40 50 Class 63 Class 80 100 125 Class Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 239: ...d attach the rear suction type s sealing plate there when the filter chamber for the rear suction type must be installed Note Refer to the appearance figure of optional accessory describing later for further details Model Applicable Model KAJ25L36B 20 25 32 Class KAJ25L56B 40 50 Class KAJ25L80B 63 Class KAJ25L160B 80 100 125 Class Model A KAJ25L36B 600 KAJ25L56B 750 KAJ25L80B 1050 KAJ25L160B 1450 ...

Page 240: ...e appearance figure of optional accessory describing later for further details Model Applicable Model KAJ25L36D 20 25 32 Class KAJ25L56D 40 50 Class KAJ25L80D 63 Class KAJ25L160D 80 100 125 Class Model A KAJ25L36D 550 KAJ25L56D 700 KAJ25L80D 1000 KAJ25L160D 1400 Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 241: ...2507K160 Dimensions mm W 527 677 977 1377 H 278 T 25 Size of Connecting Duct mm W 477 627 927 1327 L 228 Materials Galvanized steel plate Applicable Model 20 25 32 Class 40 50 Class 63 Class 80 100 125 Class Model Item KBBJ25K36 KBBJ25K56 KBBJ25K80 KBBJ25K160 Dimensions mm W 535 685 985 1385 D 404 T 10 Materials Galvanized Steel Plate Applicable Model 20 25 32 Class 40 50 Class 63 Class 80 100 125...

Page 242: ... installed 2 When optional accessory other than these kits will be built in refer to external drawing with optional accessories 3 Parts names show optional accessories Number JC DU425 2111F Note 1 Suspension positions 800 mm or more Service space 300 mm or more Service space 350 or more Required installation space Note 1 An access panel is needed when a half panel will be installed 2 When optional...

Page 243: ... 1 2 For natural evaporating pan type humidifier Description Suspension bolt Access panel with 450 mm square or more Refer to the following note 1 JC DU428 2158G Note 1 Suspension positions 1200 mm or more Service space 300 mm or more Service space Note 1 An access panel is needed when a half panel will be installed 2 When optional accessory other than these kits will be built in refer to external...

Page 244: ...ficiency filter Air suction canvas Suction half panel Built in unit body Name Description 485 or more Required installation space JC DU823 226E Note 1 When optional accessory other than these kits will be built in refer to the external drawing with optional accessories 2 Parts names show optional accessories Number Bottom suction filter chamber High efficiency filter Air suction canvas Suction hal...

Page 245: ... Air suction canvas Suction half panel Built in Hi type body Name Description 485 or more Required installation space JC DU828 215F Note 1 When optional accessory other than these kits will be built in refer to the external drawing with optional accessories 2 Parts names show optional accessories Number Bottom suction filter chamber High efficiency filter Air suction canvas Suction half panel Buil...

Page 246: ...amber for rear suction type details A view At installation of suction flange Suction flange details JC DU425 2115F Note 1 When optional accessory other than these kits will be built in refer to the external drawing with optional accessories 2 Parts names show optional accessories Number Suction inlet flange Suction flange Long life filter High efficiency filter Rear suction sealing plate Rear suct...

Page 247: ...ion space At installation of suction flange Suction flange details 36 φ4 7 hole 14 φ7 hole 4 key shape hole JC DU828 216F Note 1 When optional accessory other than these kits will be built in refer to the external drawing with optional accessories 2 Parts names show optional accessories Number Suction flange Discharge outlet flange Long life filter for rear suction type High efficiency filter Rear...

Page 248: ...ams 253 5 Wiring Diagrams 254 6 Electric Characteristics 255 7 Capacity Tables 256 7 1 Cooling Capacity 256 8 Fan Performances 258 8 1 Fan Performance 258 8 2 Air Flow Auto Adjustment Characteristics 262 9 Sound Levels 266 10 Center of Gravity 268 11 Installation Manual 269 12 Accessories 283 Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 249: ...31 29 20 Sound level HH H L FXMQ P 30 34 32 30 32 39 37 35 40 700 mm Ceiling 30 Pa 100 Pa for FXMQ20P 32P 30 Pa 160 Pa for FXMQ40P 50 Pa 200 Pa for FXMQ50P 125P Low operation sound level Improved ease of installation Improved ease of maintenance Airflow can be controlled using a remote controller With the conventional model the airflow rate was controlled from the PC board It is automatically adju...

Page 250: ...xternal Static Pressure Pa Standard 50 100 30 3 Standard 50 100 30 3 Standard 50 100 30 3 Drive Direct Drive Direct Drive Direct Drive Temperature Control Microprocessor Thermostat for Cooling and Heating Microprocessor Thermostat for Cooling and Heating Microprocessor Thermostat for Cooling and Heating Air Filter 4 4 4 Piping Connections Liquid Pipes mm φ6 4 Flare Connection φ6 4 Flare Connection...

Page 251: ...rive Direct Drive Temperature Control Microprocessor Thermostat for Cooling and Heating Microprocessor Thermostat for Cooling and Heating Microprocessor Thermostat for Cooling and Heating Microprocessor Thermostat for Cooling and Heating Air Filter 4 4 4 4 Piping Connections Liquid Pipes mm φ6 4 Flare Connection φ6 4 Flare Connection φ9 5 Flare Connection φ9 5 Flare Connection Gas Pipes mm φ12 7 F...

Page 252: ...l Type Sirocco Fan Sirocco Fan Motor Output Number of Units W 350 1 350 1 Air Flow Rate HH H L m min 32 27 23 39 33 28 cfm 1 130 953 812 1 377 1 165 988 External Static Pressure Pa Standard 100 200 50 3 Standard 100 200 50 3 Drive Direct Drive Direct Drive Temperature Control Microprocessor Thermostat for Cooling and Heating Microprocessor Thermostat for Cooling and Heating Air Filter 4 4 Piping C...

Page 253: ...spection hatch 2 or more Unit base Air outlet Air inlet or more 300 Notes 1 Location of MANUFACTURE S LABEL Control box surface 2 Mount the air filter at the suction side Select its colorimethod gravity method 50 or more 3 Do not locate things should not be wet under the indoor unit Dews may drop when humidity reaches over 80 or a drain gets stuck or air filters are not clean 4 Space for Service W...

Page 254: ...IT SIZE OR MORE Inspection hatch 2 or less or more 200 700 Notes 1 Location of MANUFACTURE S LABEL Control box surface 2 Mount the air filter at the suction side Select its colorimethod gravity method 50 or more 3 Do not locate things should not be wet under the indoor unit Dews may drop when humidity reaches over 80 or a drain gets stuck or air filters are not clean 4 Space for Service Works 1 On...

Page 255: ...let From the Air inlet CASE 1 Control box 200 Inspection hatch 1 450mm 450mm or less View B 2 Control box CASE 2 3 Inspection hatch 1 450mm 450mm Control box View B 1 20 Control box B or more Ceiling Inspection hatch 1300 SAME AS THE INDOOR UNIT SIZE 300 OR MORE Inspection hatch 3 700 or more Fig A Inspection hatch Ceiling Control box or more 300 Unit base Air inlet Air outlet or more or more 700 ...

Page 256: ... inlet Unit base or more 300 Service space 450 or more or more Notes 1 Location of MANUFACTURE S LABEL Control box surface 2 Mount the air filter at the suction side Select its colorimethod gravity method 50 or more 3 Do not locate things should not be wet under the indoor unit Dews may drop when humidity reaches over 80 or a drain gets stuck or air filters are not clean 4 Space for Service Works ...

Page 257: ...eiling B Inspection hatch 20 or more Control box 300 From the Air inlet 40 φ 4 7 hole Notes 1 Location of MANUFACTURE S LABEL Control box surface 2 Mount the air filter at the suction side Select its colorimethod gravity method 50 or more 3 Do not locate things should not be wet under the indoor unit Dews may drop when humidity reaches over 80 or a drain gets stuck or air filters are not clean 4 S...

Page 258: ... 253 7 4 Piping Diagrams Refrigerant pipe connection port diameters mm Model Gas Liquid FXMQ20P 25P 32P 40P 50PVE φ12 7 φ6 4 FXMQ63P 80P 100P 125PVE φ15 9 φ9 5 4D034245C Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 259: ...0A N M1F F2 T1 P2 P1 T2 F1 R4T YLW HAP X3A WHT X15A X16A YLW BLU WIRED REMOTE CONTROLLER OPTIONAL ACCESSORY X1A M1P PNK BLU X1M X2A RED FOR FXMQ50PVE 63PVE 80PVE 100PVE 125PVE FOR FXMQ20PVE 25PVE 32PVE 40PVE PS PS PS X33A X35A X28A Z 1 C A 3 P X1M A2P Z2C L1P X2M A 1 P INDOOR UNIT C1 C2 C3 KPR K1R L1R M1F M1P A1P A2P A3P HAP F1U F3U F2U F4U LIGHT EMITTING DIODE SERVICE MONITOR GREEN A1P A2P MAGNET...

Page 260: ...ED34 862 Electric Characteristics FXMQ P 255 7 6 Electric Characteristics C 4D060439A Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 261: ... 6 4 0 21 0 1 9 1 8 2 3 2 0 2 6 2 3 2 8 2 3 3 0 2 3 3 2 2 3 3 3 2 3 21 0 3 8 3 6 4 5 4 1 5 2 4 5 5 6 4 6 6 0 4 6 6 4 4 6 6 6 4 0 23 0 1 9 1 8 2 3 2 0 2 6 2 3 2 8 2 3 3 0 2 3 3 2 2 3 3 2 2 3 23 0 3 8 3 6 4 5 4 1 5 2 4 5 5 6 4 6 6 0 4 6 6 4 4 6 6 5 4 0 25 0 1 9 1 8 2 3 2 0 2 6 2 3 2 8 2 3 3 0 2 3 3 1 2 3 3 2 2 3 25 0 3 8 3 6 4 5 4 1 5 2 4 5 5 6 4 6 6 0 4 6 6 3 4 5 6 4 3 9 27 0 1 9 1 8 2 3 2 0 2 6 2 ...

Page 262: ... 5 8 3 11 2 8 5 11 9 8 7 12 7 8 7 13 0 8 4 25 0 7 6 6 4 9 0 7 3 10 5 8 3 11 2 8 5 11 9 8 7 12 5 8 6 12 8 8 3 27 0 7 6 6 4 9 0 7 3 10 5 8 3 11 2 8 5 11 9 8 7 12 3 8 5 12 6 8 2 29 0 7 6 6 4 9 0 7 3 10 5 8 3 11 2 8 5 11 9 8 6 12 2 8 4 12 4 8 1 31 0 7 6 6 4 9 0 7 3 10 5 8 3 11 2 8 5 11 7 8 5 12 0 8 3 12 2 8 0 33 0 7 6 6 4 9 0 7 3 10 5 8 3 11 2 8 5 11 5 8 5 11 8 8 2 12 1 7 9 35 0 7 6 6 4 9 0 7 3 10 5 8...

Page 263: ...per lim it of ESP rating ESP H min ESP Lower limit of ESP rating ESP min ESP Upper limit of ESP L rating ESP 3D062537 70Pa Notes 90Pa m a x E S P 60Pa 80Pa max ESP 100Pa min ESP HH rating ESP 50Pa Note 7 rating ESP HH 6 ESP external static pressure max ESP H max ESP HH min ESP 30Pa max ESP L rating ESP H change HH H and L 5 The remote controller can be used to in rating air flow 7 The value in thi...

Page 264: ...P min ESP L o w e r li m it o f E S P m a x E S P L min ESP L rating ESP 3D060456A 250 250 25 25 25 25 200 200 20 20 20 20 HH max ESP 200Pa Note 7 max ESP 180Pa H max ESP 160Pa Note 7 max ESP 150 150 15 15 15 15 150Pa 140Pa L max ESP 130Pa 120Pa 110Pa 100 100 10 10 10 10 HH rating ESP 100Pa rating ESP External static pressure External static pressure 90Pa H rating ESP 80Pa 70Pa 50 50 L rating ESP ...

Page 265: ... of remote controller Fan characteristics 2 Fan characteristics 1 Lower limit of ESP min ESP 3D060458A Air flow m3 min Air flow m3 min mmH2O mmH2O mmH2O mmH2O 21 19 20 17 18 22 23 24 25 26 27 28 21 20 5 28 5 22 23 24 25 26 27 28 0 0 0 50Pa min ESP H min ESP HH min ESP 60Pa 5 5 100 50 70Pa 80Pa 90Pa External static pressure External static pressure 100Pa rating ESP HH rating ESP L rating ESP H rati...

Page 266: ...ss For local setting of remote controller Fan characteristics 2 Fan characteristics 1 3D060460A 250 250 25 25 25 25 200 200 20 20 20 20 HH max ESP 200Pa Note 7 max ESP 180Pa 150 150 15 15 15 15 160Pa 150Pa H max ESP 140Pa 130Pa 120Pa 100 100 10 10 10 10 110Pa HH rating ESP 100Pa rating ESP 90Pa 80Pa L max ESP 70Pa H rating ESP 50 50 60Pa 5 5 5 5 50Pa min ESP HH min ESP 0 0 0 0 0 0 29 39 42 43 35 3...

Page 267: ...ristics at the time of HH H and L 7 The remote controller can be used to change HH H and L 8 ESP external static pressure Notes 1 As for this machine less than 10 of the volume of blow off air is automatically adjusted to the rated quantity by airflow auto adjustment at the time of installation 2 After duct construction completion please perform local setting airflow auto adjustment by remote cont...

Page 268: ...ssure 9 Please set the external static pressure of the suction duct at 150Pa or less 3D060577A 250 25 25 Upper limit of ESP NOTE 8 200 20 20 Upper limit of ESP by airflow auto adjustment 150 15 15 HH H 100 10 10 External static pressure L Lower limit of ESP by airflow auto adjustment 50 5 5 Lower limit of ESP 0 0 0 13 21 15 18 16 17 20 19 14 Notes 1 As for this machine less than 10 of the volume o...

Page 269: ...pressure 9 Please set the external static pressure of the suction duct at 150Pa or less 3D060579A 17 28 27 21 18 19 26 23 22 25 20 24 0 0 0 Lower limit of ESP 5 5 50 Lower limit of ESP by airflow auto adjustment External static pressure L 10 10 100 H HH 15 15 150 Upper limit of ESP by airflow auto adjustment 20 20 200 Upper limit of ESP NOTE 8 25 25 250 mmH2O Pa mmH2O Air flow m3 min mmH2O mmH2O N...

Page 270: ...c pressure 9 Please set the external static pressure of the suction duct at 150Pa or less 3D060581A 250 25 25 Upper limit of ESP by airflow auto adjustment Upper limit of ESP NOTE 8 200 20 20 150 15 15 HH 100 10 10 H External static pressure L Lower limit of ESP by airflow auto adjustment 50 5 5 Lower limit of ESP 0 0 0 25 27 29 41 23 33 37 39 43 35 31 mmH2O Pa mmH2O Air flow m3 min mmH2O mmH2O No...

Page 271: ... a range of factors such as the construction acoustic absorption coefficient of the particular room in which the equipments installed dBA Model 220 240V 50Hz HH H L FXMQ20P 25P 33 31 29 FXMQ32P 34 32 30 FXMQ40P 39 37 35 FXMQ50P 41 39 37 FXMQ63P 42 40 38 FXMQ80P 43 41 39 FXMQ100P 43 41 39 FXMQ125P 44 42 40 FXMQ20P 25PVE FXMQ32PVE FXMQ40PVE FXMQ50PVE FXMQ63PVE FXMQ80PVE 4D060446 4D062535 4D062536 4D...

Page 272: ...ED34 862 Sound Levels FXMQ P 267 7 FXMQ100PVE FXMQ125PVE 4D060448 4D060449 Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 273: ...Center of Gravity ED34 862 268 FXMQ P 10 Center of Gravity FXMQ20P 25P 32P 40P 50P 63P 80P 100P 125PVE Unit mm 4D060438A Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 274: ... insufficient strength may result in the equip ment falling and causing injury Carry out the specified installation work after taking into account strong winds typhoons or earthquakes Failure to do so during installation work may result in the unit falling and causing accidents Make sure that a separate power supply circuit is provided for this unit and that all electrical work is carried out by q...

Page 275: ...e the unit to fall out of place or could lead to leaks Where corrosive gas like sulfurous gas exists Cop per tubing and brazed spots may corrode which could eventually lead to refrigerant leaks Where exposed to combustible gases and where vol atile flammable gas like thinner or gasoline is used Gas in the vicinity of the unit could ignite Where machines can generate electromagnetic waves Control s...

Page 276: ...units power supply wiring and connecting wires at least 1 meter away from televisions or radios in order to prevent image interference or noise Depending on the radio waves a distance of 1 meter may not be sufficient enough to eliminate the noise Remote controller Wired type Wireless type Heat pump type Cooling only type Items to be checked If not properly done what is likely to occur Check Are th...

Page 277: ...efer to the installation manual provided with the wireless remote controller Refer to 6 REFRIGERANT PIPING WORK 7 DRAIN PIPING WORK and 10 WIRING EXAMPLE AND HOW TO SET THE REMOTE CONTROLLER The ceiling framework may need reinforcement in order to keep the ceiling horizontal and prevent the vibration of the ceiling after the installation holes are opened For details consult your construction or in...

Page 278: ...fer to the installation manual provided to the outdoor unit Perform heat insulation work on both gas piping and liquid piping or otherwise water leakage may result Use the insulation material that withstands a temperature of 120 C Reinforce the insulation material for the refrigerant piping if the ambient temperature is high or otherwise dew conden sation may result on the surface of the insulatio...

Page 279: ...7 around the insula tion for fitting 4 and 5 for the joint flare nut part CAUTION Be sure to perform the heat insulation of the local piping up to the piping joint If the piping is exposed dew condensation may result Fur thermore a burn may be caused if a human body comes in contact with the piping Pipe size Tightening torque Flare dimensions A mm Flare shape φ 6 4 14 2 17 2N m 8 7 9 1 φ 9 5 32 7 ...

Page 280: ...t at 1 to 1 5 m intervals for the prevention of piping deflection Be sure to use the drain hose 2 and metal clamp 1 Insert the drain hose 2 deep into the base of the drain socket and securely fasten the metal clamp 1 within the taped part on the insertion front end of the hose Be sure to fasten the screw of the metal clamp 1 until the margin of the screw thread decreases to 4 mm or less NOTE Be su...

Page 281: ... onto the electric parts of the drain pump and others 3 Be sure to conduct heat insulation work on the follow ing portions or otherwise water leakage may occur as a result of dew condensation Drain piping indoors Drain socket On completion of the drainage check refer to the follow ing illustration and use the provided large sealing pad 6 and heat insulate the metal clamp 1 and drain hose 2 8 DUCT ...

Page 282: ...d vinyl piping is used Telephone ground wires or lightning rods might cause abnormally high electric potential in the ground during lighting storms 9 2 ELECTRICAL CHARACTERISTICS MCA Min Circuit Amps A MFA Max Fuse Amps A kW Fan Motor Rated Output kW FLA Full Load Amps A 9 3 SPECIFICATIONS FOR FIELD SUPPLIED FUSES AND WIRE Allowable length of transmission wirings and remote controller wiring are a...

Page 283: ... may result if the control box lid catches any wiring or the wires push up the lid 4 Put the control box lid and wrap the wire sealing material Small 10 around the wires so as to block the wire through holes CAUTION After all the wiring connections are done fill in any gaps in the through holes with putty or insulation procured locally to prevent small animals and insects from entering the unit fr...

Page 284: ...e N m Terminal block for remote controller and transmission wires 0 80 0 96 Terminal block for power supply 1 18 1 44 Power supply wiring Earth wiring Transmission wiring Remote controller wiring Fixing use Wire fixing screw 13 accessory Wire fixing bracket 12 accessory Clamp 8 accessory Electric wire Round crimp style terminal Attach insulation sleeve Connect the wires evenly Do not connect a wir...

Page 285: ...the remote controller to select operation 10 5 CENTRALIZED CONTROL For centralized control it is necessary to designate the group No For details refer to the manual of each optional control lers for centralized control 11 FIELD SETTING NOTE Before the test operation of the outdoor unit as explained in 12 TEST OPERATION be sure to make the following field settings as explained in 11 FIELD SETTING M...

Page 286: ... OPERATION button Then the operation lamp will be lit and the air conditioner will go into fan operation for airflow automatic adjustment Do not adjust the throttles of the air outlets or inlets during automatic adjustment of the air conditioner After the air conditioner runs approximately one to eight min utes the air conditioner will finish airflow adjustment automatically the operation lamp wil...

Page 287: ...ot to operate the air conditioner until the interior finish work is com pleted for the protection of the air conditioner Otherwise substances that will be generated from interior finish work materials such as paint and adhesive agents may con taminate the air conditioner External Static Pressure MODE NO FIRST CODE NO SECOND CODE NO 30Pa 1 13 23 06 01 50Pa 02 60Pa 03 70Pa 04 80Pa 05 90Pa 06 100Pa 0...

Page 288: ...K160W KTBJ25K36F KTBJ25K56F KTBJ25K80F KTBJ25K160F KTBJ25K36T KTBJ25K56T KTBJ25K80T KTBJ25K160T Air discharge adapter KDAJ25K36A KDAJ25K56A KDAJ25K71A KDAJ25K140A 3D060443B M4 8 M5 16 20 25 32 type 6 40 type 50 63 80 type 100 125 type 10 18 26 Thin Thick Screws for duct flanges 3 Insulation for fitting As described in table below for liquid pipe 4 for gas pipe 5 Sealing pad Clamp 8 Washer fix ing ...

Page 289: ...be made to look nice with the service access panel Thin 10 mm design for the exposed part Caution Ceiling joist and ceiling joist support required Locally procured Model Item KTBJ25K36W T F KTBJ25K56W T F KTBJ25K80W T F KTBJ25K160W T F Main applicable models 20 32 Class 40 50 Class 63 80 Class 100 125 Class Color W White T Brown F Fresh white Accessories Installation manual Mass weight kg 6 0 6 5 ...

Page 290: ...ED34 862 Accessories FXMQ P 285 7 Installation C 3P225173A Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 291: ...Accessories ED34 862 286 FXMQ P 3P225173A Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 292: ...s Installation manual Mass weight kg 1 1 1 5 2 5 3 5 Component parts Air discharge adaptor Screws except KDAJ25K36A Installation manual Dimensions Unit mm KDAJ25K56A KDAJ25K71A KDAJ25K140A D3K06137 D3K06138A D3K06136 D3K06518 KDAJ25K36A A arrow view 150 245 375 φ200 332 300 Suction duct Field supply Suction grille Field supply Inlet air To air discharge unit To air discharge unit Flexible duct wit...

Page 293: ...Accessories ED34 862 288 FXMQ P Installation 3P012475C Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 294: ... 800 2 500 1 800 Filter element Non woven fabric of synthetic fiber Number of sheets included 1 1 2 2 3 3 4 4 Note 1 Dust concentration 0 15 mg m3 Dimensions Unit mm J D3K06645 Cannot be water washed for reuse The Filter Chamber for high efficiency filter KDDF37AA36 56 80 160 is required when the high efficiency filter will be installed Hook and loose fastener black Hook and loose fastener white A...

Page 295: ... KAF373AA160 Long life filter KAF371AA36 KAF371AA56 KAF371AA80 KAF371AA160 Accessories Mounting screws Installation manual Mass weight kg 4 4 4 5 5 5 7 5 Dimensions Unit mm JC D3K06642 Model Connection duct opening Connection duct side Indoor unit side burring Service cover High efficiency filter 650 KDDF37AA36 450 KDDF37AA56 80 160 Long life filter oblong hole Service space Service cover side 582...

Page 296: ...life filter will be installed Model KAF371AA36 KAF371AA56 KAF371AA80 KAF371AA160 Item Initial pressure loss Pa 3 or less 7 or less 8 or less Final pressure loss Pa 49 or less Average efficiency 50 gravity method Air flow rate 1 sheet m3 min 9 8 Life h 2 500 dust concentration 0 15 mg m3 Filter element Mildew proof resin net Polypropylene Filter frame Polystyrene Number of sheets included 1 2 3 4 В...

Page 297: ...et t 0 8 coating Adaptor for wiring KRP1C64 KRP4AA51 Accessories Mounting screws M4 8 2 Sealing material 2 Clamp 8 Installation manual Main unit mounting hole hole Adaptor mounting hole hole Hole Hole Main unit mounting claw 2 places Clamp material mounting hole 10 places Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 298: ...ED34 862 Accessories FXMQ P 293 7 2P226887 Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 299: ...Accessories ED34 862 294 FXMQ P 2P226887 Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 300: ...3 Dimensions 298 4 Piping Diagrams 299 5 Wiring Diagrams 300 6 Electric Characteristics 301 7 Capacity Tables 302 7 1 Cooling Capacity 302 8 Fan Performances 303 8 1 50Hz 303 9 Sound Levels 304 10 Installation 305 11 Accessories 309 Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 301: ...u much more flexibility in designing of the air conditioning system to satisfy the needs of individual air conditioning even in the broad area High external static pressure allows extensive duct work for flexible applications Ceiling mounted duct type FXMQ200MA FXMQ250MA 200 250 type Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 302: ...80 1 100 470 1 380 1 100 Coil Cross Fin Coil Rows Stages Fin Pitch mm 3 26 2 0 3 26 2 0 Face Area m 0 68 0 68 Fan Model D13 4G2DA1 2 D13 4G2DA1 2 Type Sirocco Fan Sirocco Fan Motor Output Number of Units W 380 2 380 2 Air Flow Rate H L m min 58 50 72 62 cfm 2 047 1 765 2 542 2 189 External Static Pressure 50Hz Pa 221 132 3 270 191 3 Drive Direct Drive Direct Drive Temperature Control Microprocesso...

Page 303: ...es 1 Location of unit s Name Plates Switch box surface 2 Mount the air filter at the suction side Select its colorimethod gravity method 50 or more 32 φ4 7 hole A 3 100 300 Description 3 100 300 Gas pipe connection 5 330 Name plate 1100 or more Inspection hole 600 or more 32 φ7 hole All around 650 or more Suction side Note 2 8 Discharge companion flange Suction flange Gas side Attached piping Atte...

Page 304: ...g Diagrams FXMQ MA 299 8 4 Piping Diagrams Refrigerant pipe connection port diameters 4D034245B mm Model Gas Liquid FXMQ200MA φ19 1 φ9 5 FXMQ250MA φ22 2 Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 305: ...F 2F 6 M1F A1 2 ORG INPUT FROM OUTSIDE X1A 12 F1 X12A NOTE 3 RED 25 3 NOTE 4 t WHT M L 3 4 FC A1 K3M TERMINAL BLOCK CONTROL 1 X4M X3M K1M 7 MAGNETIC CONTACTOR M1F 2F K2M CONTROLLER K2M A2 10 A1P F1 F2 H FL t K3R WHT WHT WHT RED RED RED WHT WHT WHT RED RED RED X8A S1L RED RED RED K2M K3M T1R X2M K1M X18A ELECTRIC PARTS BOX A1P C2R SS X3M X4M C1R X8A X1M R1T WHT WHT WHT 50Hz 220 240V POWER SUPPLY RE...

Page 306: ...ED34 862 Electric Characteristics FXMQ MA 301 8 6 Electric Characteristics C 4D040330A Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 307: ... 18 0 14 9 21 0 16 3 22 4 16 8 23 2 16 8 23 8 16 0 24 3 15 3 39 0 15 1 13 4 18 0 14 9 21 0 16 3 22 4 16 8 22 8 16 6 23 4 15 8 23 9 15 1 250 10 0 18 9 16 9 22 5 18 5 26 2 20 4 28 0 20 9 29 8 21 2 33 5 22 1 36 8 22 1 12 0 18 9 16 9 22 5 18 5 26 2 20 4 28 0 20 9 29 8 21 2 33 5 22 1 36 3 21 8 14 0 18 9 16 9 22 5 18 5 26 2 20 4 28 0 20 9 29 8 21 2 33 5 22 1 35 9 21 6 16 0 18 9 16 9 22 5 18 5 26 2 20 4 ...

Page 308: ...50 30 20 10 0 30 20 10 0 53 50Hz 220V Standard ESP External static pressure mmH2O mmH2O Air flow m3 min U pper lim it of ESP H igh ESP Upper limit of ESP Standard ESP Lower limit of ESP High ESP Lower limit of ESP Standard ESP 3D035172 5 Pa 0 200 100 300 10 20 0 30 10 20 0 30 80 72 60 75 62 65 50Hz 220V External static pressure mmH2O mmH2O Air flow m3 min Low High ESP High High ESP U pper lim it o...

Page 309: ...g values were obtained in a dead room conversion values Sound level will vary depending on a range of factors such as the construction acoustic absorption coefficient of the particular room in which the equipments installed dBA Model 220V 50Hz 240V 50Hz H L H L FXMQ200MA FXMQ250MA 48 45 49 46 FXMQ200MAVE FXMQ250MAVE 4D034593A C 4D035168 C 4D035169 Все каталоги и инструкции здесь http splitoff ru t...

Page 310: ...ED34 862 Installation FXMQ MA 305 8 10 Installation Installation Example Center of Gravity FXMQ200 250MA C 4D035171 Unit mm Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 311: ...cause serious injury Where the false ceiling is not noticeably on an incline Where there is no risk of flammable gas leakage Where sufficient clearance for maintenance and service can be ensured Refer to Fig 1 Where piping between indoor and outdoor units is possible within the allowable limit Refer to the installation manual of the outdoor unit CAUTION Install the indoor and outdoor units power s...

Page 312: ... Use bolts of 10 mm diameter Install the equipment where supporting structures are strong enough to bear the equipment s weight Use embedded inserts or anchor bolts with new buildings and hole in anchors with old buildings C 3P086156 6U FXMQ200 250MAVE Fig 2 Indoor unit Air outlet Inspection hatch 600 1296 Air inlet Approx 150 mm 1100 1100 or more 1148 1380 service space Suspension bolt 4 length m...

Page 313: ...g pipe PS1B and should be kept equal to or greater than that of the connecting pipe 2 After piping work is finished check drainage flows smoothly Open the water supply port add approximately 1 liter of water slowly into the drain pan and check drainage flow CAUTION Drain piping connections Do not connect the drain piping directly to sewage pipes that smell of ammonia The ammonia in the sewage migh...

Page 314: ...al for hanger 2 pcs Washers 8 pcs Clamps 2 pcs Hexagon head bolt for pipe flange M10 2 pcs Spring washer for pipe flange M10 2 pcs Quantity 1 set Shape Type FXMQ200MA FXMQ250MA Item Drain pump kit KDU30L250VE High efficiency filter 65 KAFJ372L280 90 KAFJ373L280 Filter chamber KDJ3705L280 Long life replacement filter KAFJ371L280 3D040334B Main Unit High Efficiency Filter High Efficiency Filter Filt...

Page 315: ...ic method 90 Initial Pressure Loss Pa 27 42 29 45 Final Pressure Loss Pa 98 98 Filter Non woven fabric of synthetic fiber Non woven fabric of synthetic fiber Life Time h 2500 hours dust density 0 15mg m 1800 hours dust density 0 15mg m Seats Structured 2 2 Applicable Models 200 250 Class 200 250 Class KAFJ372L280 KAFJ373L280 Dimensions of filter KAFJ372L280 KAFJ373L280 Installation Meet the airflo...

Page 316: ...r Chamber for Bottom Suction KDJ3705L280 Dimensions W D T mm 684 445 30 Average Efficiency 50 Gravity method Pressure Loss Pa Initial 9 8 1mmH2O Final 49 5mmH2O Material Mildew Proof Resin Net Number Required per Unit 2 Life Time h 2 500 h dust particle concentration at 0 15mg m Applicable Model 200 250 Class Model A B Quantity KAFJ371L280 684 445 2 KDJ3705L280 Все каталоги и инструкции здесь http...

Page 317: ...Standard drain outlet of the unit 222 250 Drain Outlet VP25 Internal diameter φ25 external diameter φ32 Safety Device Float switch Weight kg 10 Applied Models 200 250 Class KDU30L250VE Wrong Good If the drain pump kit has already been installed note the following when installing the indoor unit Do not install the indoor unit on an incline against drainage flow away from the drain outlet This can l...

Page 318: ...ter about Circumference 300 or less than 300 Circumference View View hole Circumference JC 3D011124G 8 7 6 5 4 3 2 1 Number Drain hose Water inlet Drain piping connection Drain pump kit Long life filter High efficiency filter Filter chamber Ceiling mounted duct type s body Name Attached to Drain pump kit VP25 O D φ32 I D φ25 Built in a body Description Все каталоги и инструкции здесь http splitoff...

Page 319: ...Accessories ED34 862 314 FXMQ MA Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 320: ...ecifications 317 3 Dimensions 318 4 Piping Diagrams 321 5 Wiring Diagrams 322 6 Electric Characteristics 323 7 Capacity Tables 324 7 1 Cooling Capacity 324 8 Sound Levels 325 9 Installation 326 10 Accessories 329 Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 321: ... 39 34 100 45 37 dB A Low operating sound Uses the new quiet stream fan and many more quiet technologies Sound absorption member Turbulent flow is produced Straightening vane New quiet stream fan Installation is easy Maintenance is easy Drain up kit built inside main unit 600mm Bristle free Frap minimizes contamination and makes cleaning simpler Non dew Frap 100 New model Wide air discharge openin...

Page 322: ... and Heating Microprocessor Thermostat for Cooling and Heating Microprocessor Thermostat for Cooling and Heating Sound Absorbing Thermal Insulation Material Glass Wool Glass Wool Glass Wool Air Filter Resin Net with Mold Resistant Resin Net with Mold Resistant Resin Net with Mold Resistant Piping Connections Liquid Pipes mm φ6 4 Flare Connection φ9 5 Flare Connection φ9 5 Flare Connection Gas Pipe...

Page 323: ...arth terminal Inside the electric components box Suspension bracket Backward piping and wiring connection opening lid Upward piping and wiring connection opening lid Right side pipe connection Left back drain pipe connection Left side drain pipe connection Right side drain pipe connection Hole of wall for taking out in piping back Upward drain pipe connection Upward gas pipe connection Upward liqu...

Page 324: ...e the machine attached 0 5mm 2 2wicks O D φ5 4 It is not attached to VRV 17 40 155 80 60 300 or more 65 6 260 2 6 170 4 18 680 195 210 115 60 50 The front 7 4 5 55 1160 φ45 30 or more 145 4 M8 M10 Hanging bolt For height installation 135 View from the front Air discharge grille Air suction grille Air filter Gas pipe connection Liquid pipe connection Drain pipe connection Earth terminal Inside the ...

Page 325: ...3 Position slit hole for taking out in piping back Obstacle For height installation From the floor side 2500 or more Required space 300 or more Required space 4 M8 M10 Hanging bolt Hanging position Air discharge grille Air suction grille Air filter Gas pipe connection Liquid pipe connection Drain pipe connection Earth terminal Inside the control box Suspension bracket Backward piping and wiring co...

Page 326: ...onnection port diameters Electronic expansion valve Filter M Heat exchanger Filter Fan Liquid pipe connection port Gas pipe connection port 4D034245C mm Model Gas Liquid FXHQ32MA φ12 7 φ6 4 FXHQ63 100MA φ15 9 φ9 5 Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 327: ... X25A X4A TO WIRELESS REMOTE CONTROLLER MAGNETIC RELAY M1S H4P T1R SELECTOR SWITCH MAIN SUB X18A T1R H2P R1T WIRELESS REMOTE CONTROLLER RECEIVER DISPLAY UNIT WIRED REMOTE CONTROLLER THERMISTOR AIR KPR HAP S1Q RECEIVER DISPLAY UNIT ATTACHED L PUSH BUTTON ON OFF TRANSFORMER 220 240V 22V REMOTE CONTROLLER SELECTOR SWITCH H1P BLK RED YLW MOTOR SWING FLAP PRINTED CIRCUIT BOARD SERVICE MONITOR GREEN WHT...

Page 328: ...ED34 862 Electric Characteristics FXHQ MA 323 9 6 Electric Characteristics C 4D035304B Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 329: ...5 1 7 1 5 2 7 6 5 3 8 5 5 5 8 7 5 2 23 0 4 8 4 1 5 7 4 6 6 6 5 1 7 1 5 2 7 6 5 3 8 4 5 4 8 5 5 1 25 0 4 8 4 1 5 7 4 6 6 6 5 1 7 1 5 2 7 6 5 3 8 3 5 4 8 4 5 1 27 0 4 8 4 1 5 7 4 6 6 6 5 1 7 1 5 2 7 6 5 3 8 1 5 3 8 3 5 0 29 0 4 8 4 1 5 7 4 6 6 6 5 1 7 1 5 2 7 6 5 3 8 0 5 2 8 2 5 0 31 0 4 8 4 1 5 7 4 6 6 6 5 1 7 1 5 2 7 6 5 3 7 9 5 1 8 1 4 9 33 0 4 8 4 1 5 7 4 6 6 6 5 1 7 1 5 2 7 6 5 3 7 8 5 1 7 9 4 ...

Page 330: ...d in a dead room conversion values Sound level will vary depending on a range of factors such as the construction acoustic absorption coefficient of the particular room in which the equipments installed dBA Model 220 240V 50Hz H L FXHQ32MA 36 31 FXHQ63MA 39 34 FXHQ100MA 45 37 FXHQ32MAVE FXHQ63MAVE FXHQ100MAVE 4D035301 Microphone C 4D035301 C 4D035302 C 4D035303A Все каталоги и инструкции здесь htt...

Page 331: ... CAUTION Install the indoor and outdoor units power supply wiring and connecting wires at least 1 meter away from tele visions or radios in order to prevent image interference or noise Depending on the radio waves a distance of 1 meter may not be sufficient enough to eliminate the noise 2 This indoor unit may be installed on ceilings up to 3 5 m in height However if the ceiling is higher than 2 7m...

Page 332: ... the diameter of the connecting pipe Vinyl tube pipe size 20 mm outer dimension 26 mm Keep the drain pipe short and sloping downwards at a gradient of at least 1 100 to prevent air pockets from form ing Refer to Fig 21 Use the drain hose 1 and the metal clamp 2 Insert the drain hose into the drain socket up to the gray tape Refer to Fig 22 Tighten the metal clamp until the screw head is less than ...

Page 333: ...mell of ammonia The ammonia in the sewage might enter the indoor unit through the drain pipes and corrode the heat exchanger Keep in mind that it will become the cause of getting drain pipe blocked if water collects on drain pipe C 3PN01417 7P Tilt down Do not lift When drain hose is connected Make sure there is no slack Make sure it is not in the water Good Wrong Fig 21 Taping area Drain hose 1 a...

Page 334: ...ntity 1 pc 1 pc 8 pcs 6 pcs 1 pc 1 each Shape 6 For gas pipe 7 For liquid pipe Name Sealing pad Other Operation manual Installation manual Quantity 1 each Shape 8 Large 9 Small No Model FXHQ32MAVE FXHQ63MAVE FXHQ100MAVE Item 1 Drain pump kit KDU50M60VE KDU50M125VE 2 Replacement long life filter Resin net KAFJ501D56 KAFJ501D80 KAFJ501D112 3 L type piping kit for upward direction KHFP5M35 KHFP5M63 F...

Page 335: ... bellow hose for VP20 All units of drain up height was unified to 600mm From the bottom of the ceiling Wiring diagram L Shape Connection Pipe Kit Application purpose This kit must be bent inside the unit as shown below when the refrigerant piping is carried out in a ceiling space This L shape kit is an optional accessory which has been developed for improving the work of the processing on site Ins...

Page 336: ...ifications 333 3 Dimensions 335 4 Piping Diagrams 338 5 Wiring Diagrams 339 6 Electric Characteristics 340 7 Capacity Tables 341 7 1 Cooling Capacity 341 8 Sound Levels 342 9 Installation 343 10 Accessories 351 Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 337: ... be set by remote controller Washable grille the front grille can be easily removed for washing Discharge angle is automatically set at the same angle as the previous operation when restarts Initial setting 10 for cooling and 70 for heating 1 050 mm For 50 63 Class 70 mm 200 mm 290 mm More compact than compared with previous model 50 63 class Drastic 10 kg weight reduction from 24 kg to 14 kg Volu...

Page 338: ...Microprocessor Thermostat for Cooling and Heating Microprocessor Thermostat for Cooling and Heating Microprocessor Thermostat for Cooling and Heating Sound Absorbing Thermal Insulation Material Foamed Polystyrene Foamed Polyethylene Foamed Polystyrene Foamed Polyethylene Foamed Polystyrene Foamed Polyethylene Air Filter Resin Net Washable Resin Net Washable Resin Net Washable Piping Connections Li...

Page 339: ...rocessor Thermostat for Cooling and Heating Microprocessor Thermostat for Cooling and Heating Microprocessor Thermostat for Cooling and Heating Sound Absorbing Thermal Insulation Material Foamed Polystyrene Foamed Polyethylene Foamed Polystyrene Foamed Polyethylene Foamed Polystyrene Foamed Polyethylene Air Filter Resin Net Washable Resin Net Washable Resin Net Washable Piping Connections Liquid P...

Page 340: ...er Refer to the drawing of wireless remote contorller in detail 50 or more 6 Outside line 4 Approx 460 230 107 Approx 290 795 90 or more 98 2 7 626 290 155 Approx 400 1 232 62 9 Approx 475 120 or less 50 or more 8 φ80 hole 125 Approx 415 14 5 5 44 44 3 Dimensions for full open front panel 60 Name plate Note 2 φ80 hole 105 30 or more 9 8 7 6 5 4 3 2 1 No Left side pipe connection hole Right side pi...

Page 341: ... Flexible tube part Piping direction Filter part Outside line 50 or more 1050 290 Approx 415 Approx 290 8 Approx 400 44 98 125 1 155 14 5 50 or more 894 4 Approx 460 30 or more 105 60 2 φ80 hole 6 Dimensions for full open front panel 7 5 230 3 52 90 or more 232 120 or less Approx 475 104 φ80 hole Name plate Note 2 44 9 9 8 7 6 5 4 3 2 1 No Left side pipe connection hole Right side pipe connection ...

Page 342: ...ace of casing Filter part Piping direction 4 Approx 400 60 5 30 or more Approx 475 Name plate Note 2 98 7 50 or more 9 Dimensions for full open front panel 3 6 8 155 Approx 460 90 or more 232 2 894 1050 230 44 125 104 52 50 or more 1 120 or less 105 Approx 415 φ80 hole Outside line 290 φ80 hole 14 5 44 9 8 7 6 5 4 3 2 1 No Left side pipe connection hole Right side pipe connection hole Grounding te...

Page 343: ... ED34 862 338 FXAQ MA 4 Piping Diagrams Refrigerant pipe connection port diameters mm Model Gas Liquid FXAQ20 25 32 40 50MA φ12 7 φ6 4 FXAQ63MA φ15 9 φ9 5 Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 344: ...WIRELESS REMOTE CONTROLLER R3T R1T SS1 WHT N NOTE 8 X15A X35A X18A PNK R2T POWER SUPPLY TRANSMISSION WIRING CENTRAL REMOTE CONTROLLER RED M1S R1T CONNECTOR FOR OPTIONAL PARTS RECEIVER DISPLAY UNIT ATTACHED TO WIRELESS REMOTE CONTROLLER P1 BS1 NOTE 2 SS1 INPUT FROM OUTSIDE RED L YLW NE 5 WHEN CONNECTING THE INPUT WIRES FROM OUTSIDE FORCED OFF OR ON OFF CONTROL OPERATION CAN BE SELECTED BY REMOTE CO...

Page 345: ...Electric Characteristics ED34 862 340 FXAQ MA 6 Electric Characteristics C 4D034907E Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 346: ... 6 9 4 2 21 0 1 9 1 8 2 3 2 0 2 6 2 2 2 8 2 2 3 0 2 2 3 4 2 3 3 4 2 2 21 0 3 8 3 2 4 5 3 7 5 2 4 1 5 6 4 2 6 0 4 3 6 7 4 4 6 8 4 2 23 0 1 9 1 8 2 3 2 0 2 6 2 2 2 8 2 2 3 0 2 2 3 3 2 3 3 4 2 2 23 0 3 8 3 2 4 5 3 7 5 2 4 1 5 6 4 2 6 0 4 3 6 6 4 4 6 7 4 1 25 0 1 9 1 8 2 3 2 0 2 6 2 2 2 8 2 2 3 0 2 2 3 3 2 2 3 3 2 2 25 0 3 8 3 2 4 5 3 7 5 2 4 1 5 6 4 2 6 0 4 3 6 5 4 3 6 6 4 1 27 0 1 9 1 8 2 3 2 0 2 6 ...

Page 347: ...y depending on a range of factors such as the construction acoustic absorption coefficient of the particular room in which the equipments installed dBA Model 220 240V 50Hz H L FXAQ20MA 35 29 FXAQ25MA 36 29 FXAQ32MA 37 29 FXAQ40MA 39 34 FXAQ50MA 42 36 FXAQ63MA 46 39 FXAQ20MAVE FXAQ25MAVE FXAQ32MAVE FXAQ40MAVE FXAQ50MAVE FXAQ63MAVE Microphone 4D037087D 4D037087D 4D037088D 4D037089D 4D038513A 4D03851...

Page 348: ... 25 2 12 20 long hole 25 21 5 171 268 290 20 40 20 20 20 6 6 3 3 3 20 20 44 5 98 30 30 177 50 50 54 23 50 37 5 44 5 26 54 153 20 75 φ65 φ65 60 44 5 89 44 5 245 5 109 44 5 13 8 5 Hole for concrete wall Bolt projection length from wall surface should be less than 20mm Bolt size M10 Temporary hole for fixing outline of unit outline of mounting plate Drain hose position Liquid pipe Gas pipe Shanghai A...

Page 349: ...n φ80 φ80 Recommended mounting plate retention spots 9 spots in all Bolt size M10 Bolt size M10 Place a leveler on raised tab b Use tape measure as shown Position the end of tape measure at Gas pipe end Liquid pipe end The removed pipe port cover can be kept in the mounting plate pocket Removed pipe port cover A Mounting plate C 2P095003 1C Все каталоги и инструкции здесь http splitoff ru tehn doc...

Page 350: ...ED34 862 Installation FXAQ MA 345 10 Service Space Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 351: ...Installation ED34 862 346 FXAQ MA Installation Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 352: ...ED34 862 Installation FXAQ MA 347 10 Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 353: ...Installation ED34 862 348 FXAQ MA Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 354: ...ED34 862 Installation FXAQ MA 349 10 Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 355: ...Installation ED34 862 350 FXAQ MA Drain Piping Work Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 356: ...stallation panel 3 Paper pattern for installation 4 Insulating tape 5 Clamp Quantity 1 set 8 pcs FXA Q 20 25 32 type 9 pcs FXA Q 40 50 63 type 1 pc 1 pc 1 large 3 small Shape M4 25L Name 6 Securing screws Other Operation manual Installation manual Quantity 2 pcs Shape M4 12L No Type FXAQ20MA FXAQ25MA FXAQ32MA FXAQ40MA FXAQ50MA FXAQ63MA Item 1 Drain pump kit K KDU572EVE Все каталоги и инструкции зд...

Page 357: ...t such as kitchens is shrouded and the place where an organic solvent drifts Dimensions Unit mm Inlet drain connection 40 165 270 260 40 43 190 Outlet drain connection 48 VP20 VP20 DRAIN UP KIT Specification K KDU572EVE Drain pump head mm Note 1 1 000 Power supply Single phase 220 240V 220V 50 60Hz Power consumption 14 1 12 9 W Operating current 0 18 0 16 A Insulation Class E Drain inlet connectio...

Page 358: ...ccessories FXAQ MA 353 10 External drawing of drain pump kit and Service space Small capacity machine 795 Large capacity machine 1050 Component Parts Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 359: ...ter level Normal water level Operation water level Stop water level ON OFF ON OFF Recovery Air conditioner stop signal output Abnormal water level fixed Note 2 5 min 5 min 5sec Note1 Note3 ON OFF Drain pan Float switch For operation Float switch For abnormal Drain up mechanism Note 1 When the float switch for abnormal water level is reset within five minutes the air conditioner operates again with...

Page 360: ...ED34 862 Accessories FXAQ MA 355 10 3K019617 Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 361: ...Accessories ED34 862 356 FXAQ MA 3K019617 3K019618 Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 362: ...ED34 862 Accessories FXAQ MA 357 10 3K019618 Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 363: ...Accessories ED34 862 358 FXAQ MA 3K019618 Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 364: ...ns 361 2 1 FXLQ MA 361 2 2 FXNQ MA 363 3 Dimensions 365 3 1 FXLQ MA 365 3 2 FXNQ MA 368 4 Piping Diagrams 371 5 Wiring Diagrams 372 6 Electric Characteristics 373 7 Capacity Tables 374 7 1 Cooling Capacity 374 8 Sound Levels 375 9 Installation 377 10 Accessories 380 Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 365: ...2 Improvement on the installation The piping connection work is facilitated drastically 3 Easy maintenance When the unit is hung on the wall it is easy to clean the floor Exposed type The maintenance of the discharge grille is improved The interval of filter cleaning is prolonged Efficient for perimeter zone airconditioning FXLQ MA Can be built into pericounter FXNQ MA Все каталоги и инструкции зд...

Page 366: ...ssor Thermostat for Cooling and Heating Microprocessor Thermostat for Cooling and Heating Microprocessor Thermostat for Cooling and Heating Sound Absorbing Thermal Insulation Material Glass Fiber Urethane Foam Glass Fiber Urethane Foam Glass Fiber Urethane Foam Air Filter Resin Net with Mold Resistant Resin Net with Mold Resistant Resin Net with Mold Resistant Piping Connections Liquid Pipes mm φ6...

Page 367: ...stat for Cooling and Heating Microprocessor Thermostat for Cooling and Heating Microprocessor Thermostat for Cooling and Heating Sound Absorbing Thermal Insulation Material Glass Fiber Urethane Foam Glass Fiber Urethane Foam Glass Fiber Urethane Foam Air Filter Resin Net with Mold Resistant Resin Net with Mold Resistant Resin Net with Mold Resistant Piping Connections Liquid Pipes mm φ6 4 Flare Co...

Page 368: ...sor Thermostat for Cooling and Heating Microprocessor Thermostat for Cooling and Heating Microprocessor Thermostat for Cooling and Heating Sound Absorbing Thermal Insulation Material Glass Fiber Urethane Foam Glass Fiber Urethane Foam Glass Fiber Urethane Foam Air Filter Resin Net with Mold Resistant Resin Net with Mold Resistant Resin Net with Mold Resistant Piping Connections Liquid Pipes mm φ6 ...

Page 369: ...sor Thermostat for Cooling and Heating Microprocessor Thermostat for Cooling and Heating Microprocessor Thermostat for Cooling and Heating Sound Absorbing Thermal Insulation Material Glass Fiber Urethane Foam Glass Fiber Urethane Foam Glass Fiber Urethane Foam Air Filter Resin Net with Mold Resistant Resin Net with Mold Resistant Resin Net with Mold Resistant Piping Connections Liquid Pipes mm φ6 ...

Page 370: ... 70 575 219 172 10 590 149 192 4 181 102 194 600 596 222 3 4 12 30 SLOT HOLE 301 233 184 1 PERFORATED HOLE FOR PIPNG 13 10 88 143 15 2 12 18 SLOT HOLE 5 165 15 5 391 PERFORATED HOLE FOR PIPING 2 WIRING HOLE 1000 NOTE NUMBER 1 2 3 4 5 1 LOCATION OF UNIT S NAME PLATE OUTSIDE SURFACE OF RIGHT SIDE PLATE NAME LIQUID PIPE CONNECTION PORT GAS PIPE CONNECTION PORT DRAIN PIPE CONNECTION PORT SWITCH BOX AI...

Page 371: ...6 165 730 219 42 575 194 PERFORATED HOLE FOR PIPNG 172 4 12 30 SLOT HOLE 102 WIRING HOLE 219 233 149 10 222 181 5 301 143 70 2 391 209 88 13 156 10 65 600 1140 5 4 10 2 PERFORATED HOLE FOR PIPING 3 NOTE NUMBER 1 2 3 4 5 1 LOCATION OF UNIT S NAME PLATE OUTSIDE SURFACE OF RIGHT SIDE PLATE NAME LIQUID PIPE CONNECTION PORT GAS PIPE CONNECTION PORT DRAIN PIPE CONNECTION PORT SWITCH BOX AIR FILTER DESCR...

Page 372: ...6 15 192 42 4 2 12 18 SLOT HOLE 65 219 233 575 3 156 143 10 209 1420 301 1016 2 219 149 10 222 PERFORATED HOLE FOR PIPING 600 WIRING HOLE 88 13 1010 5 PERFORATED HOLE FOR PIPNG Indoor unit FXLQ50M A VE FXLQ50MHV1 FXLQ63M A VE Gas side Liquid side NOTE 1 LOCATION OF UNIT S NAME PLATE OUTSIDE SURFACE OF RIGHT SIDE PLATE NUMBER 1 2 3 4 5 NAME LIQUID PIPE CONNECTION GAS PIPE CONNECTION DRAIN PIPE CONN...

Page 373: ... M6 REQUIRED INSTALLATION SPACE FRONT FACE LEVEL ADJUSTING SCREW AS STANDARD ACCESSORY HOLE FOR FIXING TO THE FLOOR NOTE 2 12 18 SLOT HOLE TOTAL ON RIGHT LEFT 20 OR MORE 4 12 30 SLOT HOLE TOTAL ON FRONT REAR 1 LOCATION OF UNIT S NAME PLATE THE RIGHT LOWER CORNER OF FRONT PLATE NUMBER 1 2 3 4 5 NAME LIQUID PIPE CONNECTION PORT GAS PIPE CONNECTION PORT DRAIN PIPE CONNECTION PORT SWITCH BOX AIR FILTE...

Page 374: ...ISCHARGE FLANGE TOTAL ON FRONT REAR 730 389 609 199 130 35 42 65 11 218 7 2 φ4 7 HOLE 74 181 6 100 600 192 103 702 65 2 25 3 163 206 152 TOP PLATE 4 391 42 129 5 301 1 760 7 φ4 7 HOLE 233 736 139 84 NOTE 1 LOCATION OF UNIT S NAME PLATE THE RIGHT LOWER CORNER OF FRONT PLATE NUMBER 1 2 3 4 5 NAME LIQUID PIPE CONNECTION PORT GAS PIPE CONNECTION PORT DRAIN PIPE CONNECTION PORT SWITCH BOX AIR FILTER DE...

Page 375: ...06 139 74 9 100 900 1016 1 163 130 35 10 φ4 7 HOLE 129 65 3 233 1010 301 192 982 181 25 152 2 103 65 84 389 391 42 2 φ4 7 HOLE 7 TOP PLATE 42 11 218 199 1040 609 Indoor unit FXNQ50M A VE FXNP56MMVC FJNP56MMVC FXNQ63M A VE FXNP71MMVC FJNP71MMVC Gas side Liquid side NUMBER 1 2 3 4 5 NAME LIQUID PIPE CONNECTION PORT GAS PIPE CONNECTION DRAIN PIPE CONNECTION SWITCH BOX AIR FILTER DESCRIPTION FLARE CON...

Page 376: ... diameters Electronic expansion valve Filter M Heat exchanger Filter Fan Liquid pipe connection port Gas pipe connection port 4D034245C mm Model Gas Liquid FXLQ20 25 32 40 50MA FXNQ20 25 32 40 50MA φ12 7 φ6 4 FXLQ63MA FXNQ63MA φ15 9 φ9 5 Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 377: ... B 5A 250V LIGHT EMITTING DIODE SERVICE MONITOR GREEN MAGNETIC RELAY M1F MOTOR INDOOR FAN THERMO SWITCH M1F EMBEDDED THERMISTOR AIR THERMISTOR COIL TRANSFORMER 220 240V 22V TERMINAL BLOCK POWER X2M Y1E R1T SS1 X18A TERMINAL BLOCK CONTROL ELECTRONIC EXPANSION VALVE THERMISTOR AIR SELECTOR SWITCH MAIN SUB CONNECTOR WIRING ADAPTOR FOR ELECTORICAL APPENDICES NOTES 1 TERMINAL BLOCK CONNECTOR TERMINAL 2...

Page 378: ...ED34 862 Electric Characteristics FXLQ MA FXNQ MA 373 11 6 Electric Characteristics C 4D034579C Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 379: ...6 7 4 1 6 9 3 9 21 0 1 9 1 6 2 3 1 8 2 6 2 0 2 8 2 1 3 0 2 1 3 4 2 1 3 4 2 0 21 0 3 8 3 0 4 5 3 4 5 2 3 8 5 6 3 9 6 0 4 0 6 7 4 1 6 8 3 8 23 0 1 9 1 6 2 3 1 8 2 6 2 0 2 8 2 1 3 0 2 1 3 3 2 1 3 4 2 0 23 0 3 8 3 0 4 5 3 4 5 2 3 8 5 6 3 9 6 0 4 0 6 6 4 0 6 7 3 8 25 0 1 9 1 6 2 3 1 8 2 6 2 0 2 8 2 1 3 0 2 1 3 3 2 1 3 3 2 0 25 0 3 8 3 0 4 5 3 4 5 2 3 8 5 6 3 9 6 0 4 0 6 5 4 0 6 6 3 7 27 0 1 9 1 6 2 3 1...

Page 380: ...c absorption coefficient of the particular room in which the equipments installed Floor Standing Type Concealed Floor Standing Type dBA dBA Model 220V 50Hz 240V 50Hz Model 220V 50Hz 240V 50Hz H L H L H L H L FXLQ20MA FXLQ25MA FXLQ32MA 35 32 37 34 FXNQ20MA FXNQ25MA FXNQ32MA 35 32 37 34 FXLQ40MA 38 33 40 35 FXNQ40MA 38 33 40 35 FXLQ50MA 39 34 41 36 FXNQ50MA 39 34 41 36 FXLQ63MA 40 35 42 37 FXNQ63MA ...

Page 381: ...V 50Hz FXLQ20 25MAVE FXLQ32MAVE FXLQ40MAVE FXLQ50MAVE FXLQ63MAVE FXNQ20 25MAVE FXNQ32MAVE FXNQ40MAVE FXNQ50MAVE FXNQ63MAVE 4D034528A 4D034564A 4D034566A 4D034567A 4D034534B 4D034535A 4D034536B 4D034537B 4D034538B Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 382: ...le limit Refer to the installation manual of the outdoor unit CAUTION Install the indoor and outdoor units power supply wiring and connecting wires at least 1 meter away from televisions or radios in order to prevent image interference or noise Depending on the radio waves a distance of 1 meter may not be sufficient enough to eliminate the noise C 3P086154 2N Base FXLQ Window 100 or more FXLQ 150 ...

Page 383: ...ear 4 Lift the front of the top plate 5 Lower the front panel towards the front of the unit To close perform the procedure in opposite order Pull towards the front unit the knob snaps in place C 3P086154 2N FXLQ FXNQ C 4D034527C 500 570 710 Unit mm FXLQ32 40MAVE FXLQ50 63MAVE FXLQ20 25MAVE C 4D034533C 395 465 505 Unit mm FXNQ20 25MAVE FXNQ32 40MAVE FXNQ50 63MAVE A 192 233 FXNQ20 25MAVE FXNQ32 40MA...

Page 384: ...heck drainage flows smoothly Add approximately 1 liter of water slowly from the air outlet and check drainage flow 3 Be sure to insulate all indoor pipes CAUTION Drain piping connections Do not connect the drain piping directly to sewage pipes that smell of ammonia The ammonia in the sewage might enter the indoor unit through the drain pipes and corrode the heat exchanger Keep in mind that it will...

Page 385: ...ing pad Clamp Leveling Other Operation manual Installation manual Quantity 1 set 1 each 1 pc 8 pcs 4 pcs Shape Hose 1 Metal clamp 1 3 For gas pipe 4 For liquid pipe No Type FXLQ20MA FXNQ20MA FXLQ25MA FXNQ25MA FXLQ32MA FXNQ32MA FXLQ40MA FXNQ40MA FXLQ50MA FXNQ50MA FXLQ63MA FXNQ63MA Item 1 Long life replacement filter KAFJ361K28 KAFJ361K45 KAFJ361K71 1 2 5 6 7 Long Life Replacement Filter Все каталог...

Page 386: ...ng Diagrams 388 5 Wiring Diagrams 389 6 Electric Characteristics 391 7 Capacity Tables 392 7 1 Cooling Capacity 392 8 Air Velocity and Temperature Distributions Reference Data 393 9 Sound Levels 395 10 Installation 396 10 1 Indoor Units 396 10 2 Connecting Units 401 11 Accessories 411 Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 387: ...ype Ceiling Suspended Type Ceiling Suspended Type Suitable for where there is no ceiling space Realized comfort and design flexibility at the same time for exposed installation Better air distribution and easy installation Take the both advantage in this product Daikin unique cassette Low Silhouette design 71 Type 165mm thickness Current Multi Flow Cassette 338mm Flexible Design Easy Installation ...

Page 388: ...irect Drive Direct Drive Direct Drive Temperature Control Microprocessor Thermostat for Cooling and Heating Microprocessor Thermostat for Cooling and Heating Microprocessor Thermostat for Cooling and Heating Sound Absorbing Thermal Insulation Material Heat Resistant Foamed Polyethylene Regular Foamed Polyethylene Heat Resistant Foamed Polyethylene Regular Foamed Polyethylene Heat Resistant Foamed ...

Page 389: ...4D045388A BRC1C62 Power Power supply supply line line Transmission Transmission line line Control Wiring Control Wiring 1 Wiring Work The connecting line between SkyAir Indoor Unit BEV Unit 3 cores like a Transmission Line BEV Unit s power supply line Single phase 2 line like a VRV Indoor unit BEV Unit other VRV indoor unit or outdoor unit 2 cores DIII network wiring super wiring 2 Piping work Sky...

Page 390: ...s received Refer to the drawing of wireless remote controller in detail 3 When closing the discharge grill 2 or 3 way discharge direction of pipe connection will be limited please refer to Installation manual Liquid pipe connection Gas pipe connection Drain pipe connection Air outlet Air suction grille Corner decoration cover Right pipe wiring connection Rear pipe wiring connection Pipe through co...

Page 391: ...hrough cover Accessory drain elbow Description Name Number 1 2 3 4 5 6 7 8 9 10 φ9 5 flare φ15 9 flare VP20 Drain connection location for upper piping Drain connection location for rear piping Note 1 Location for manufacture s label on bell mouth 2 This is where the signal of wireless remote controller is received Refer to the drawing of wireless remote controller in detail 3 When closing the disc...

Page 392: ...e the space which can be the thinghtening work of the flare nut Unit mm C 3D045389 3 255 Inspection hatch 4 97 66 200 or more 165 5 200 or more 225 182 350 Note 2 49 9 100 250 305 219 5 30 100 265 100 or more Note 3 50 Suspension bolt pitch Servicing space Suspension bolt pitch Servicing space Servicing space Servicing space When hanging the unit from the ceiling 7 6 1 4 2 2 4 1 450 INSTALLATION F...

Page 393: ...Piping Diagrams ED34 862 388 FXUQ MA 4 Piping Diagrams Indoor unit Connection Unit C 4D037995H 4D034127B Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 394: ...FOR SKY AIR SERIES CONNECTOR WIRELESS REMOTE CONTROLLER V1TR C1 X 1 M SS1 A1P X 2 M CONTROL BOX A2P RyA SIGNAL TRANSMISSION CIRCUIT SIGNAL RECEIVER FLOAT SWITCH TERMINAL STRIP SELECTOR SWITCH EMERGENCY PHASE CONTROL CIRCUIT LIMIT SWITCH SWING FLAP TERMINAL STRIP MOTOR DRAIN PUMP MAGNETIC RELAY M1P PRINTED CIRCUIT BOARD TRANSFORMER 220 240V 16V THERMISTOR COIL THERMISTOR AIR LIGHT EMITTING DIODE SE...

Page 395: ...INGS FOR THE INDOOR OUTDOOR AND BS UNITS 4 SEE THE INDOOR UNIT S WIRING DIAGRAM WHEN INSTALLING OPTIONAL PARTS FOR THE INDOOR UNIT 5 ONLY ONE INDOOR UNIT MAY BE CONNECTED TO THE BEV UNIT SEE THE INDOOR UNIT S WIRING DIAGRAM FOR WHEN CONNECTING THE REMOTE CONTROL 6 ALWAYS USE THE SKY AIR CONNECTION ADAPTER FOR THE INDOOR UNIT WHEN USING A CENTRAL CONTROL UNIT REFER TO THE MANUAL ATTACHED THE UNIT W...

Page 396: ...ED34 862 Electric Characteristics FXUQ MA 391 12 6 Electric Characteristics C 4D034128B Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 397: ... 23 0 7 6 6 6 9 0 7 1 10 5 8 0 11 2 8 2 11 9 8 3 13 2 8 2 13 5 7 8 25 0 7 6 6 6 9 0 7 1 10 5 8 0 11 2 8 2 11 9 8 3 13 0 8 1 13 3 7 7 27 0 7 6 6 6 9 0 7 1 10 5 8 0 11 2 8 2 11 9 8 3 12 8 8 0 13 1 7 7 29 0 7 6 6 6 9 0 7 1 10 5 8 0 11 2 8 2 11 9 8 3 12 6 7 9 12 9 7 6 31 0 7 6 6 6 9 0 7 1 10 5 8 0 11 2 8 2 11 9 8 3 12 4 7 9 12 7 7 6 33 0 7 6 6 6 9 0 7 1 10 5 8 0 11 2 8 2 11 9 8 3 12 2 7 8 12 5 7 6 35 ...

Page 398: ...r Velocity and Temperature Distributions Reference Data FXUQ MA 393 12 8 Air Velocity and Temperature Distributions Reference Data FXUQ71MA FXUQ100MA Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 399: ...Air Velocity and Temperature Distributions Reference Data ED34 862 394 FXUQ MA FXUQ125MA Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 400: ... obtained in a dead room conversion values Sound level will vary depending on a range of factors such as the construction acoustic absorption coefficient of the particular room in which the equipments installed dBA Model 230V 50Hz H L FXUQ71MAV1 40 35 FXUQ100MAV1 43 38 FXUQ125MAV1 44 39 FXUQ71MAV1 FXUQ100MAV1 FXUQ125MAV1 4D014037D 4D014037D 4D014038D 4D014039D Все каталоги и инструкции здесь http ...

Page 401: ...ion can be ensured Where nothing blocks air passage Where condensate can be properly drained Where the ceiling is strong enough to bear the indoor unit weight Where the false ceiling is not noticeably on an incline Where sufficient clearance for maintenance and service can be ensured Where there is no risk of flammable gas leakage Where piping between indoor and outdoor units is possible within th...

Page 402: ... False ceiling Suspension bolt Fig 3 Long nut or turnbuckle 2 FOR 2 WAY OR 3 WAY AIR DISCHARGE 2 way and 3 way air discharge must be set from the remote controller For details see FIELD SETTING 1 Relation of holes for indoor unit suspension bolt position piping and wiring Refer to Fig 8 NOTE Illustrations seen from ceiling Dimension in for 100 and 125 models Suspension bolt pitch 2 Make holes for ...

Page 403: ... 1 for rightward running drain hose or elbow 10 for upward run ning drain hose and clamp 2 Fit the drain hose 1 or elbow 10 over the drain pipe up to the neck and fasten tight with the clamp 2 Insulate the clamp 2 and drain hose or elbow 10 with the included sealing pad 8 Refer to Fig 28 Make sure that heat insulation work is executed on the following 2 spots to prevent any possible water leakage ...

Page 404: ...air discharge outlet Adding water from inspection opening PRECAUTIONS FOR UPWARD DRAIN RAISING PIPING Install the drain raising pipes at a height of less than 500 mm Install the drain raising pipes at a right angle to the indoor unit Refer to Fig 30 CAUTION If the upward running drain hose leans at a slant the float switch will malfunction and water will leak WRONG Fig 30 Caution Drain piping conn...

Page 405: ...y switch back to NORM Inter unit wiring terminal block Indoor PC board assembly Single phase power supply Fig 32 Clamp C Tab Inter unit wiring terminal block 1 2 3 Clamp C NORM EMERG Emergency switch Checking the drain NORM EMERG After the checking Remove the control box lid and change the emergency switch above the PC board assembly of the indoor unit from NORM to EMERG Connect the single phase p...

Page 406: ...he type of R 410A refrigerant to be used before installing the unit Using an incorrect refrigerant will prevent normal operation of the unit BEV unit is an electronic expansion valve unit for allowing the indoor unit to be connected to the system for the VRV system BEV unit may only be connected to the models shown in the table below Do not attempt connection with other models Indoor unit Ceiling ...

Page 407: ...tighten the flare nuts Make sure the wiring outtake is facing down and no other direction Service space When installing the unit on a wall Fig 2 length mm Upright and diagonal position Take the gas piping thermistor out from above Direction of the gas piping connection piping Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 408: ...t or turnbuckle Suspension bolt BEV unit proper Note All the above parts are field supplied Example of installation Anchor Fig 4 37 182 287 Fig 5 When installing the unit on a wall 1 Check the relative locations of ceiling hole unit and hanging bolts length mm Nut field supplied Washer field supplied 10 15mm Hanging fitting BEV main unit Hanging bolt field supplied Fig 6 When hanging the unit from...

Page 409: ...roughly right away The outdoor unit is charged with refrigerant For the refrigerant piping and branching follow the piping connection procedure Be sure to use both a spanner and torque wrench together as shown in the drawing when connecting or disconnecting piping to from the unit Refer to the Table 1 for the dimensions of flare nut spaces When connecting the flare nut apply ether oil or ester oil...

Page 410: ... the refrig erant oil Before brazing local refrigerant piping nitrogen gas shall be blown through the piping to expel air from the piping If your brazing is done without nitrogen gas blowing a large amount of oxide film develops inside the piping and could cause system malfunction When brazing the refrigerant piping only begin brazing after having carried out nitrogen substitution or while inserti...

Page 411: ...rst branch piping to the indoor unit 4 Additional refrigerant amount When measuring the amount of additional to refrigerant to fill include the length of the liquid piping between the BEV unit and the indoor unit Additional filling amount a b c d e f g h i j k l m n p q Refer also to the installation manual included with the outdoor unit Outdoor unit BEV unit Gas piping Liquid piping L 5m or less ...

Page 412: ... lead wire and the transmission wiring using the included clamp 1 CAUTIONS Do not under any circumstances connect the power supply wiring to the transmission terminal block F1 F2 as this may cause damage to the entire system CAUTION When clamping wiring use the included clamping material to prevent outside presure being exerted on the wiring connections and clamp firmly When doing the wiring make ...

Page 413: ...ower supply wiring inter unit wiring ground wire and other power wiring The equipment may malfunction if subjected to electrical external noise 5 For remote controller wiring refer to the INSTALLATION MANUAL OF REMOTE CONTROLLER attached to the remote controller 6 Never connect power supply wiring to the terminal block for remote controller wiring A mistake of the sort could damage the entire syst...

Page 414: ...n calculating the limit of connected indoor units count all the lower BEV units as one unit If the remote controller does not have a cooling heating selection right operation switch is being managed will be displayed Fig 18 1 2 3 1 2 3 Power supply 220 240V 50Hz or 220V 60Hz Power supply 220 240V 50Hz or 220V 60Hz Power supply 220 240V 50Hz or 220V 60Hz Power supply 220 240V 50Hz or 220V 60Hz 2 Fo...

Page 415: ...T D BS IN D 1 2 3 Power supply 220 240V 50Hz or 220V 60Hz Power supply 220 240V 50Hz or 220V 60Hz 4 DEFAULT SETTINGS 1 Once piping work is completed conduct the following settings as needed 1 When connecting the BEV unit to the BS unit in the heating cooling free system turn the SS1 on the A1P to M Main for only one of the BEV units connected to the remote controller on which heating cooling switc...

Page 416: ... hose 2 Metal Clamp 3 Washer for look ing hanger 4 Clamp Quantity 1 pc 1 pc 8 pcs 6 pcs Shape Name 5 Wahers fixing plate Insulation for fitting Sealing pad 10 Elbow Quantity 4 pcs 1 each 2 pcs 1 pc Shape 6 For gas pipe 8 Large 9 Small 7 For liquid pipe Name 11 Paper pattern for installation 12 Blocking pad 13 Retainer for blocking pad 14 Retainer for blocking pad Quantity 1 pc 2 pcs 2 pcs 2 pcs Sh...

Page 417: ...F80 140 Dimension Model KDBHJ49F80 KDBHJ49F140 Material Galvanized Steel Plate with Flocking Model KDBHJ49F80 KDBHJ49F140 Dimension Model KDBTJ49F80 KDBTJ49F140 Model KDBTJ49F80 KDBTJ49F140 Material Galvanized Steel Plate with Flocking Dimension Model KDGJ49F80 KDGJ49F140 Packing Quantity 4 each 2 2 Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 418: ...erage Efficiency Life Time h Filter Pass Air Flow Rate Materials Number Required Per Model Weight kg KAFJ495F140 Less Than 7 Less Than 49 50 Gravity Method 2 500 Dust Particle Concentration at 0 15mg m3 18 5m 3 min Mildew Proof Resin Net 1 0 4 Dimension Model KHFP49M140 Liquid Side Gas Side 88 15 9 Dimension KRP1B97 KRP4A53 Model No Item Adaptor for Wiring Cover Box Все каталоги и инструкции здесь...

Page 419: ...Accessories ED34 862 414 FXUQ MA Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 420: ...ED34 862 Outdoor Air Processing Unit 415 Part 3 Outdoor Air Processing Unit FXMQ MF Outdoor Air Processing Unit 417 Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 421: ...ED34 862 416 Outdoor Air Processing Unit Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 422: ...3 1 Indoor Units 421 3 2 Dimensions with Option 423 4 Piping Diagrams 425 5 Wiring Diagrams 426 6 Capacity Tables 427 7 Operation Limit 430 8 Electric Characteristics 432 9 Sound Levels 433 10 Fan Performances 434 11 Installation 436 12 Accessories 449 Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 423: ... Indoor Unit Indoor Unit VRV Series Outdoor Units Air Conditioning Outdoor Air Supply The following restrictions must be observed in order to maintain the indoor units connected to the same system Connection Conditions When outdoor air processing units are connected the total connection capacity must be within 50 to 100 of that of the outdoor units When outdoor air processing units and standard in...

Page 424: ...e deployed including remote control from distances of up to 500 m Group control is not possible between this unit and standard type indoor units Connect remote controllers to each unit Wired remote controller option A central control system compatible with the VRV system can be installed It is not possible to change the discharge air temperature settings from the central control system Do not asso...

Page 425: ... 0 28 0 65 0 65 Fan Model D13 4G2DA1 D13 4G2DA1 D13 4G2DA1 Type Sirocco Fan Sirocco Fan Sirocco Fan Motor Output Number of Units W 380 1 380 1 380 1 Air Flow Rate H L m min 18 28 35 cfm 635 988 1 236 External Static Pressure 4 Pa 185 225 205 Drive Direct Drive Direct Drive Direct Drive Temperature Control Microprocessor Thermostat for Cooling and Heating Microprocessor Thermostat for Cooling and H...

Page 426: ...ame Ground terminal M5 Inside Control box Note 1 PS1B Internal thread Major dia φ33 349 Minor dia φ30 391 Drain piping connection Hanger bracket Description Liquid pipe connection Gas pipe connection 200 2 9 580 1100 5 30 10 390 6 25 346 685 744 630 760 470 3 11 50 296 360 30 7 1 8 613 4 Power supply wiring connection Name plate Transmission wiring connection Control box Water supply port Discharg...

Page 427: ...ction Service space Hanger bracket Service space 250 All around Description Attendant piping connection 3 12 1 2 9 5 6 8 7 11 4 10 All around 360 Discharge companion flange FXMQ250MFV1 FXMQ200MFV1 φ22 2 attached piping φ9 5 φ19 1 attached piping φ9 5 Gas side Piping size Field supply Indoor unit Liquid side Approx 150 Ground terminal Number 650 or more 360 7 11 5 6 3 330 1230 11 100 1100 10 25 A 1...

Page 428: ...ace 630 600 330 Attached to Drain pump kit 0 250 330 8 3 100 300 5 100 500 223 200 79 594 529 222 456 744 360 222 685 8 564 285 222 472 16 φ8 HOLE All around 5 100 500 1100 20 φ4 7 HOLE All around 300 or less 744 Water supply port Long life replacement filter Number Builted in Drain pump kit Drain pipe connection drain pump kit VRV D P Unit C duct type Name High eficiency filter Filter chamber Des...

Page 429: ... Water supply port 200 3 100 300 529 1100 5 8 300 or less 0 250 1380 79 1230 330 4 223 7 1200 1 8 2 6 456 1380 1296 5 200 1000 360 3 222 VRV D P Unit C duct type Filter chamber Number Builted in High eficiency filter Drain pipe connection drain pump kit Long life replacement filter Drain pump kit Description Name 32 φ4 7 HOLE All around 222 472 222 32 φ7 hole 11 100 1100 1200 1230 16 φ8 HOLE All a...

Page 430: ...ED34 862 Piping Diagrams FXMQ MF 425 13 4 Piping Diagrams 4D018650B Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 431: ...A S X6A RED WHT NOTE 2 TRANSMISSION WIRING CENTRAL REMOTE CONTROLLER WHT BLU X3M WIRED REMOTE CONTROLLER OPTIONAL ACCESSORY BLU F1U BLU T1R M1F A1 P2 X30A M A1P K1R WHT NOTE 4 INPUT FROM OUTSIDE X9A IN CASE OF FXMQ 200 250MFV1 CONTROL BOX ELECTRIC PARTS BOX C2 RED P1 X18A K1M X2M M X1M X8A BLU KSR A2 BLK X3M NOTE 3 DRAIN PUMP KIT OPTIONAL ACCESSORY C1 X3A YLW BRN X3M Y1 WHT 12 13 YLW M1F WHT C1 YL...

Page 432: ...capacities values are general average values which can be generated by each compressor operation level 3 A value enclosed in means rated capacity 4D046308 Outdoor temperature C WB C DB 15 0 17 0 20 0 23 0 26 0 28 0 30 0 32 0 Capacity kW kW kW kW kW kW kW kW 20 0 3 6 3 8 22 0 3 6 3 8 5 1 25 0 3 6 3 8 5 1 6 8 27 0 3 8 5 1 6 7 29 0 5 1 6 7 11 0 31 0 5 0 6 6 10 9 14 1 33 0 5 0 6 5 10 8 14 0 16 4 35 0 ...

Page 433: ...ues are general average values which can be generated by each compressor operation level 3 A value enclosed in means rated capacity 4D046309 Outdoor temperature C WB C DB 15 0 17 0 20 0 23 0 26 0 28 0 30 0 32 0 Capacity kW kW kW kW kW kW kW kW 20 0 5 7 6 1 22 0 5 7 6 1 8 2 25 0 5 7 6 1 8 2 10 8 27 0 6 1 8 1 10 7 29 0 8 1 10 6 17 6 31 0 8 0 10 5 17 4 22 6 33 0 8 0 10 3 17 3 22 4 26 2 35 0 10 2 17 1...

Page 434: ...es are general average values which can be generated by each compressor operation level 3 A value enclosed in means rated capacity 4D046310 Outdoor temperature C WB C DB 15 0 17 0 20 0 23 0 26 0 28 0 30 0 32 0 Capacity kW kW kW kW kW kW kW kW 20 0 7 1 7 6 22 0 7 1 7 6 10 2 25 0 7 1 7 6 10 2 13 5 27 0 7 6 10 1 13 4 29 0 10 1 13 3 22 0 31 0 10 0 13 1 21 8 28 2 33 0 10 0 12 9 21 6 28 0 32 8 35 0 12 8...

Page 435: ...ocessing capacity 4 The system will not operate in fan mode when the outdoor air temperature is 5 C or below 3D047750 Operation limit cooling Operation limit heating 2 The discharge air temperature may not match the temperature setting for too large outdoor air processing capacity Thermostat OFF may be carried out Fan only operation O u t d o o r a i r t e m p C W B Outdoor air temp C DB NOTE 1 Th...

Page 436: ...operation O u t d o o r a i r t e m p C W B Outdoor air temp C DB NOTE 1 These figures assume the following operating conditions Indoor and outdoor units Equivalent pipe length 7 5m Level difference 0m 3 THe discharge air temperature may not match the temperature setting for too small outdoor air processing capacity 4 The system will not operate in fan mode when the outdoor air temperature is 5 C ...

Page 437: ...Electric Characteristics ED34 862 432 FXMQ MF 8 Electric Characteristics 4D046146A Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 438: ...ead room conversion values Sound level will vary depending on a range of factors such as the construction acoustic absorption coefficient of the particular room in which the equipments installed dBA Model 50Hz 220V 240V FXMQ125MFV1 42 43 FXMQ200MFV1 47 48 FXMQ250MFV1 47 48 220V 240V FXMQ125MFV1 FXMQ200MFV1 FXMQ250MFV1 4D046271 4D046271 4D046272 4D046273 Все каталоги и инструкции здесь http splitof...

Page 439: ...tandard ESP External static pressure L o w e r l i m i t o f E S P s t a n d a r d E S P Air flow m3 min Air flow m3 min 3D046266 Air flow m3 min Air flow m3 min External static pressure Lower limit of ESP standard ESP External static pressure Lower lim it of ESP standard ESP Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 440: ...35 13 FXMQ250MFV1 3D046265 External static pressure Lower limit of ESP standard ESP External static pressure Lower lim it of ESP standard ESP Air flow m3 min Air flow m3 min Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 441: ... to take the unit s weight the unit could fall out of place and cause serious injury Where the false ceiling is not noticeably on an incline Where there is no risk of combustible gas leakage Where sufficient clearance for maintenance and service can be ensured Refer to Fig 1 Where the total piping length involving indoor unit and outdoor unit is below the allowable piping length See the installati...

Page 442: ... strong enough to support the weight of the unit or not If there is a risk reinforce the ceiling before installing the unit Outdoor air processing unit Upper face 650 or more 530 or more Service space 1100 or more Service space length mm Fig 1 Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Page 443: ...n hole is opened in the ceiling where the unit is to be installed pass refrigerant and drain pipe and the power supply transmission and remote control ler wire to the unit s pipe and wire connection ports After opening the ceiling hole it might be necessary to reinforce the ceiling frame to prevent shaking or to main tain the levelness of the ceiling Consult an architect or carpenter for details 4...

Page 444: ...r to make sure that the unit is level and that the tilt downward slope to the drain socket and air inlet side is within 1 Refer to Fig 5 4 Tighten both upper and lower nuts 1 3 Refer to Fig 4 5 Insulate the four hanger brackets with the sealing pad accessory 5 Insulate the hanger brackets so that the surface and edges of the hanger brackets cannot be seen Refer to Fig 6 CAUTION Setting the unit at...

Page 445: ...r than the designated refrigerant to get mixed into the refrigerant circuit such as air etc If any refrigerant gas leaks while working on the unit ventilate the room thoroughly right away The outdoor unit is charged with refrigerant Be sure to use both a spanner and torque wrench together as shown in the drawing when connecting or disconnecting pipes to from the unit Refer to Fig 8 Refer to Table ...

Page 446: ...n both edges with clamping material 2 Use the attached pipe Accessory 1 for connecting the gas pipes and make sure to insulate the gas pipes using field supplied insulation all the way to the base where they connect to the unit 3 The turning torque of the hexagon head bolts Accessory 7 to connect the attached pipe Accessory 1 to the unit is 21 5 28 9 N m Table 3 Pipe size Further tightening angle ...

Page 447: ...ll damage the refrigerant oil Before brazing local refrigerant piping nitrogen gas shall be blown through the piping to expel air from the piping If your brazing is done without nitrogen gas blowing a large amount of oxide film develops inside the piping and could cause system malfunction When brazing the refrigerant piping only begin brazing after having carried out nitrogen substitution or while...

Page 448: ... and materials and electric works must conform to local codes Use copper wire only For electric wiring work refer to also WIRING DIAGRAM label attached to the electric parts box lid For remote controller wiring details refer to the installation manual attached to the remote controller All wiring must be performed by an authorized electrician This system consists of multiple indoor units Mark each ...

Page 449: ... And How To Set The Remote Controller HOW TO CONNECT WIRINGS Remove the electric parts box lid and wire as shown in the figure below Units Power supply Fan motor Model Hz Volts Voltage range MCA MFA KW FLA FXMQ125MFV1 50 220 240 Max 264 Min 198 1 9 15 0 380 1 5 FXMQ200MFV1 3 3 15 0 380 2 6 FXMQ250MFV1 3 8 15 0 380 3 0 MCA Min Circuit Amps A MFA Max Fuse Amps A KW Fan Motor Rated Output kW FLA Full...

Page 450: ...y by arranging the wires neatly and attaching the electric parts box lid firmly When attaching the electric parts box lid make sure no wires get caught in the edges Pass wire through the wiring through holes to prevent damage to them Make sure the remote controller wire the transmission wire and power supply wire ground wire do not pass through the same locations outside of the unit separating the...

Page 451: ... PRECAUTIONS 1 A single switch can be used to supply power to units on the same system However branch switches and branch circuit breakers must be selected carefully 1 When using 1 remote controller for 1 indoor unit Normal operation 2 For group control or control by 2 remote controllers Terminal Size Tightening torque Transmission terminal block X2M M3 5 0 79 0 97 N m Power supply terminal block ...

Page 452: ...ning to protect itself against cold damage In such case set the AUTOMATIC OPERATION or HEATING OPERATION mode COOLING C OUTDOOR TEMPERATURE TEMPERATURE HUMIDITY DB 19 to 43 Notes 30 to 90 Long time operation in a humidity over 90 may cause condensation on the unit and dripping WB 32 or below Air Outlet Electric Parts Box Outdoor Air Inlet Power Wire Drain Pipe Ground Wire Heat Exchanger Drain Pump...

Page 453: ... The capacity of outdoor air processing units should be less than 30 of the outdoor unit capacity 2 Restrictions of the control system 1 In case of wiring is mixed with standard indoor units group control by remote controller is not available because the setting temperature are different 3 Don t set the R C of Outdoor air processing unit as the master remote controller 2 When using the central rem...

Page 454: ... FXMQ200 250MFV1 8 Screws for flange connection M5 16 pieces for FXMQ125MFV1 28 pieces for FXMQ200 250MFV1 9 Washers 8 pieces 10 Clamps 6 pieces 11 Installation manual 12 Operation manual No Type FXMQ125MFV1 FXMQ200MFV1 FXMQ250MFV1 Item 1 Drain pump kit KDU30L250VE 2 High efficiency filter 65 KAFJ372L140 KAFJ372L280 90 KAFJ373L140 KAFJ373L280 3 Filter chamber 1 KDJ3705L140 KDJ3705L280 4 Long life ...

Page 455: ...Accessories ED34 862 450 FXMQ MF Большая библиотека технической документации http splitoff ru tehn doc html каталоги инструкции сервисные мануалы схемы ...