SiUS331708EA
Field Settings from Outdoor Unit
Field Settings and Test Operation
114
2.3
Setting Mode 1
This mode is used to set and check the following items.
1. Set items ............ In order to make COOL/HEAT selection in a batch of outdoor unit group, change the setting.
• COOL/HEAT selection (IND) ................Used to select COOL or HEAT by individual
outdoor unit (factory setting).
• COOL/HEAT selection (MASTER) .......Used to select COOL or HEAT by outdoor unit
group with the master unit.
• COOL/HEAT selection (SLAVE)...........Used to select COOL or HEAT by outdoor unit
group with the slave unit.
2. Check items ....... The following items can be checked.
(1) Current operating conditions (Normal / Abnormal / In check operation)
(2) Setting conditions of COOL/HEAT selection (Individual / Batch master / Batch slave)
(3) Low noise operating conditions (In normal operation / In low noise operation)
(4) Demand operating conditions (In normal operation / In demand operation)
Procedure for changing COOL/HEAT selection setting
Press the
SET (BS2)
button to set
the blinking LED according to the
pattern shown on the right.
Press the
RETURN (BS3)
button to
determine the setting.
Check the system for each condition
through LED displays. (Refer to
information in table on the right.)
Press the
RETURN (BS3)
button and
return to the initial status of setting
mode 1.
h
h
h
h
h
h
l
h
h
h
l
h
h
h
l
h
h
h
h
h
h
k
ON
h
OFF
l
Blink
Procedure for checking
Setting mode 1 is the initial status
(normal). In case of other status,
press the
MODE (BS1)
button one
time and return to the setting mode 1.
MODE
H1P
TEST
H2P
COOL/HEAT select
IND
H3P
MASTER
H4P
SLAVE
H5P
Low
noise
H6P
Demand
H7P
h
h
k
h
h
h
h
Setting (displaying) item
MODE
H1P
TEST
H2P
COOL/HEAT select
IND
H3P
MASTER
H4P
SLAVE
H5P
LOW
NOISE
H6P
DEMAND
H7P
For selection by individual outdoor
unit (factory setting)
For selection in a batch of outdoor
unit group with master unit
For selection in a batch of outdoor
unit group with slave unit
The system returns to the initial status of setting mode 1.
Current operating conditions
h
Normal
k
Abnormal
l
In preparation or in
check operation
Setting of COOL/HEAT selection
k h h
By individual outdoor
unit
h k h
In a batch of outdoor unit
group with master unit
h h k
In a batch of outdoor unit
group with slave unit
Low noise operating conditions
h
In normal operation
k
In low noise operation
Demand operating conditions
h
In normal operation
k
In demand operation
Setting mode 1 is the initial status
(normal). In case of other status,
press the
MODE (BS1)
button one
time and return to the setting mode 1.
Summary of Contents for RXSQ24TAVJU
Page 1: ...Service Manual SiUS331708EA RXSQ24 36 48 60TAVJU Heat Pump 60 Hz...
Page 290: ...Wiring Diagrams SiUS331708EA 277 Appendix RXSQ48TAVJU 3D109546A...
Page 291: ...SiUS331708EA Wiring Diagrams Appendix 278 RXSQ60TAVJU 3D109547A...
Page 295: ...SiUS331708EA Wiring Diagrams Appendix 282 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 298: ...Wiring Diagrams SiUS331708EA 285 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 300: ...Wiring Diagrams SiUS331708EA 287 Appendix FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU 3D110467B...
Page 301: ...SiUS331708EA Wiring Diagrams Appendix 288 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Page 302: ...Wiring Diagrams SiUS331708EA 289 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 303: ...SiUS331708EA Wiring Diagrams Appendix 290 FXAQ07 09 12 18 24PVJU 3D075354C...
Page 309: ...SiUS331708EA Wiring Diagrams Appendix 296 VAM1200GVJU 3D073270D...