SiUS331708EA
Field Settings from Outdoor Unit
Field Settings and Test Operation
118
The numbers in the No. column represent the number of times to press the
SET (BS2)
button.
No.
Setting item display
Setting condition display
Setting item
MODE
H1P
TEST
H2P
C/H selection
Low
noise
H6P
Demand
H7P
IND
H3P
Master
H4P
Slave
H5P
∗
Factory setting
14
Switch over ambient
setting
k
h
h
k
k
k
h
–20.5°C (–5°F)
k h h h h h h
k h h h h h k
k h h h h k h
–17.7°C (0°F)
k h h h h k k
–15.0°C (5°F)
k h h h k h h
–12.2°C (10°F)
k h h h k h k
–9.4°C (15°F)
k h h h k k h
∗
–6.6°C (20°F)
k h h h k k k
–3.8°C (25°F)
k h h k h h h
–1.1°C (30°F)
k h h k h h k
1.6°C (35°F)
k h h k h k h
4.4°C (40°F)
k h h k h k k
7.2°C (45°F)
k h h k k h h
10°C (50°F)
k h h k k h k
Gas furnace operation only
k h h k k k h
Heat pump operation only
k h h k k k k
15
Switch over ambient
setting
(Release differential)
k
h
h
k
k
k
k
2.8°C (5°F)
k h h h h h h
5.6°C (10°F)
k h h h h h k
∗
8.3°C (15°F)
k h h h h k h
16
Setting of heat pump
lockout 1
k
h
k
h
h
h
h
OFF
k h h h h h k
∗
ON
k h h h h k h
19
Emergency automatic
heat pump lockout
k
h
k
h
h
k
k
OFF
k h h h h h k
ON
k h h h h h h
∗
20
Additional refrigerant
charge operation setting
k
h
k
h
k
h
h
Refrigerant charging: OFF
k h h h h h k
∗
Refrigerant charging: ON
k h h h h k h
21
Refrigerant recovery /
vacuuming mode setting
k
h
k
h
k
h
k
Refrigerant recovery /
vacuuming: OFF
k h h h h h k
∗
Refrigerant recovery /
vacuuming: ON
k h h h h k h
22
Night-time low noise
setting
k
h
k
h
k
k
h
OFF
k h h h h h h
∗
Level 1 (outdoor fan with 6 step or lower)
k h h h h h k
Level 2 (outdoor fan with 5 step or lower)
k h h h h k h
Level 3 (outdoor fan with 4 step or lower)
k h h h h k k
25 Setting of low noise level
k
h
k
k
h
h
k
Level 1 (outdoor fan with 6 step or lower)
k h h h h h k
Level 2 (outdoor fan with 5 step or lower)
k h h h h k h
∗
Level 3 (outdoor fan with 4 step or lower)
k h h h k h h
26
Night-time low noise
operation start setting
k
h
k
k
h
k
h
About 08:00 PM
k h h h h h k
About 10:00 PM (factory setting)
k h h h h k h
∗
About 12:00 AM
k h h h k h h
27
Night-time low noise
operation end setting
k
h
k
k
h
k
k
About 06:00 AM
k h h h h h k
About 07:00 AM
k h h h h k h
About 08:00 AM (factory setting)
k h h h k h h
∗
28
Power transistor check
mode
k
h
k
k
k
h
h
OFF
k h h h h h k
∗
ON
k h h h h k h
29
Capacity precedence
setting
k
h
k
k
k
h
k
OFF
k h h h h h k
∗
ON
k h h h h k h
Summary of Contents for RXSQ24TAVJU
Page 1: ...Service Manual SiUS331708EA RXSQ24 36 48 60TAVJU Heat Pump 60 Hz...
Page 290: ...Wiring Diagrams SiUS331708EA 277 Appendix RXSQ48TAVJU 3D109546A...
Page 291: ...SiUS331708EA Wiring Diagrams Appendix 278 RXSQ60TAVJU 3D109547A...
Page 295: ...SiUS331708EA Wiring Diagrams Appendix 282 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 298: ...Wiring Diagrams SiUS331708EA 285 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 300: ...Wiring Diagrams SiUS331708EA 287 Appendix FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU 3D110467B...
Page 301: ...SiUS331708EA Wiring Diagrams Appendix 288 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Page 302: ...Wiring Diagrams SiUS331708EA 289 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 303: ...SiUS331708EA Wiring Diagrams Appendix 290 FXAQ07 09 12 18 24PVJU 3D075354C...
Page 309: ...SiUS331708EA Wiring Diagrams Appendix 296 VAM1200GVJU 3D073270D...