Field Settings from Remote Controller
SiUS331708EA
101
Field Settings and Test Operation
Compensating the Floor Temperature
(For units with the infrared presence/floor sensor only)
Offset the detected value of the infrared floor sensor with a certain temperature. This setting should be used to
have the actual floor temperature detected when, for example, the unit is installed close to a wall.
Actual procedure to use the setting
Although the standard setting is normally used with no problem, the setting should be changed in the following
cases:
Optional Output Switching
Using this setting, "operation output signal" and "abnormal output signal" can be provided. Output signal is output
between terminals X1 and X2 of "adaptor for wiring", an optional accessory.
External ON/OFF Input
This input is used for "ON/OFF operation" and "Protection device input" from the outside. The input is performed
from the T1-T2 terminal of the operation terminal block in the electrical component box.
Mode No.
First Code No.
Second Code No.
Contents
11 (21)
9
01
–4°C (–7.2°F)
02
–2°C (–3.6°F)
03
0°C (0°F)
04
+2°C (+3.6°F)
Environment
Operation Mode
Problem
Setting Value
· The unit is installed close to a wall or a window.
· High thermal capacity of the floor (such as
concrete, etc).
· There are many heat sources including PC.
· There is a non-negligible heat source such as
floor heating.
Heating
Excessive heating
+2°C (+3.6°F)
Insufficient heating
–2°C or –4°C
(–3.6°F or –7.2°F)
Mode No.
First Code No.
Second Code No.
Contents
12 (22)
0
01
Indoor unit thermostat ON/OFF signal is provided.
02
—
03
Output linked with "Start/Stop" of remote controller is
provided.
04
In case of "Error Display" appears on the remote
controller, output is provided.
05
—
06
—
07
Only for FXMQ-PB
Economizer (field supply) ON/OFF signal is provided.
Mode No.
First Code No.
Second Code No.
Contents
12 (22)
1
01
ON: Forced stop (prohibition of using the remote
controller)
OFF: Permission of using the remote controller
02
OFF
→
ON: Permission of operation
ON
→
OFF: Stop
03
ON: Operation
OFF: The system stops, then the applicable unit
indicates
A0
. The other indoor units indicate
U9
.
04
—
05
Only for FXMQ-PB
ON: Economizer (field supply) is connected.
OFF: Not connected
F2 T1 T2
Forced stop
Input A
Summary of Contents for RXSQ24TAVJU
Page 1: ...Service Manual SiUS331708EA RXSQ24 36 48 60TAVJU Heat Pump 60 Hz...
Page 290: ...Wiring Diagrams SiUS331708EA 277 Appendix RXSQ48TAVJU 3D109546A...
Page 291: ...SiUS331708EA Wiring Diagrams Appendix 278 RXSQ60TAVJU 3D109547A...
Page 295: ...SiUS331708EA Wiring Diagrams Appendix 282 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 298: ...Wiring Diagrams SiUS331708EA 285 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 300: ...Wiring Diagrams SiUS331708EA 287 Appendix FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU 3D110467B...
Page 301: ...SiUS331708EA Wiring Diagrams Appendix 288 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Page 302: ...Wiring Diagrams SiUS331708EA 289 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 303: ...SiUS331708EA Wiring Diagrams Appendix 290 FXAQ07 09 12 18 24PVJU 3D075354C...
Page 309: ...SiUS331708EA Wiring Diagrams Appendix 296 VAM1200GVJU 3D073270D...