Troubleshooting by Error Code
SiUS331708EA
227
Service Diagnosis
Troubleshooting
YES
NO
Is
indoor-outdoor
unit transmission wiring
normal?
Fix the indoor-outdoor
unit transmission wiring.
Press and hold the
RESET
(BS5)
button on the outdoor
unit PCB for 5 seconds.
Replace the outdoor main
PCB (A1P).
YES
NO
NO
Replace the outdoor main
PCB (A1P).
YES
Operation ready
lamp (H2P) is
blinking.
Lamp does not go off
for 12 minutes or
more.
A
NO
YES
Outdoor unit PCB
microcomputer monitor
(HAP) blinks.