SiUS331708EA
Field Settings from Remote Controller
Field Settings and Test Operation
92
Notes :
1. Settings are made simultaneously for the entire group, however, if you select the mode No. inside
parentheses, you can also set by each individual unit. Setting changes however cannot be checked except in
the individual mode for those in parentheses.
∗
2. The mode numbers inside parentheses cannot be used by wireless remote controllers, so they cannot be set
individually. Setting changes also cannot be checked.
3. Do not make settings other than those described above. Nothing is displayed for functions the indoor unit is
not equipped with.
4.
88
or
Checking the connection. Please stand by.
may be displayed to indicate the remote controller is
resetting when returning to the normal mode.
∗
5. If the setting mode to “Equipped”, energy recovery ventilator fan conducts the fan residual operation by
linking to indoor unit.
∗
6. Only for FXTQ-TA models
∗
7. Only for FXDQ-M, FXTQ-TA, CXTQ-TA models
∗
8. If the airflow setting when thermostat is OFF is set to OFF (12(22)-3-03, 12(22)-6-03), the air in the indoor
unit will be stagnant and suction air thermistor may not detect room temperature correctly, resulting in
problems that thermostat will not be ON easily.
Use optional remote sensor in such conditions, or set the field setting 10(20)-2 to
03
(only remote controller
thermistor).
∗
9. Only for FXFQ-T and FXUQ-P sensing models
∗
10.Only for CXTQ-TA models
∗
11.Only for FXTQ-TA and CXTQ-TA models
∗
12.Only for FXDQ-M models
∗
13.Only for FXEQ-P models
∗
14.Only for FXZQ-TA and FXSQ-TA models
Mode
No.
(
∗
2)
First
Code
No.
Setting Contents
Second Code No.
01
02
03
04
13(23)
0
Setting of airflow rate
Refer to page 103 for details.
1
Airflow direction setting
(Set when a blocking pad kit has been installed.)
F (4 directions)
T (3 directions)
W
(2 directions)
—
2 (
∗
9) Swing pattern settings
All direction
synchronized swing
—
Facing swing
—
3 (
∗
13) Operation of downward flow flap
Equipped
Not equipped
—
—
4
Setting of airflow direction adjustment range
Draft prevention
Standard
Ceiling soiling
prevention
—
5 (
∗
10) CFM table setting
Standard
Low
—
—
5 (
∗
12) Setting of static pressure selection
Standard
High static pressure
—
—
6
External static pressure settings
Refer to page 105 for details.
14
(24)
4 (
∗
11)
Optional kit setting (UV lamp + humi
economizer)
Refer to page 106 for details.
5 (
∗
11) Residential dry
Set temperature:
room temperature
Set temperature:
same as cooling set
temperature
—
—
9 (
∗
13) Mold proof operation setting
Standard
For high humidity
areas
—
—
11 (
∗
10) Gas furnace test mode
OFF
Low heat
High heat
—
15(25)
0
Drain pump operation settings
—
ON
OFF
—
1
Humidification when heating thermostat is OFF
Not equipped
Equipped
—
—
2
Setting of direct duct connection
(when the indoor unit and energy recovery
ventilator unit are connected by duct directly.)
(
∗
5)
Not equipped
Equipped
—
—
3
Interlocked operation between humidifier and
drain pump
Not interlocked
Interlocked
—
—
5
Individual setting of ventilation
Not individual
Individual
—
—
1b
3
Display of contact center
Displayed
Not displayed
—
—
4
Display of error codes on the remote controller
—
Two-digit display
—
Four-digit
display
12
Key-lock pattern settings
No operation
allowed (Cancel
procedure is
displayed.)
No operation
allowed (Cancel
procedure is not
displayed.)
No menu
operation is
allowed
(Cancel
procedure is
displayed.)
No menu
operation is
allowed any
time.
14
Setting "restricted / permitted" of airflow block
Refer to page 108 for details.
1c
0
Room temperature display
Room temperature
is not displayed
Room temperature
is displayed
—
—
Summary of Contents for RXSQ24TAVJU
Page 1: ...Service Manual SiUS331708EA RXSQ24 36 48 60TAVJU Heat Pump 60 Hz...
Page 290: ...Wiring Diagrams SiUS331708EA 277 Appendix RXSQ48TAVJU 3D109546A...
Page 291: ...SiUS331708EA Wiring Diagrams Appendix 278 RXSQ60TAVJU 3D109547A...
Page 295: ...SiUS331708EA Wiring Diagrams Appendix 282 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 298: ...Wiring Diagrams SiUS331708EA 285 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 300: ...Wiring Diagrams SiUS331708EA 287 Appendix FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU 3D110467B...
Page 301: ...SiUS331708EA Wiring Diagrams Appendix 288 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Page 302: ...Wiring Diagrams SiUS331708EA 289 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 303: ...SiUS331708EA Wiring Diagrams Appendix 290 FXAQ07 09 12 18 24PVJU 3D075354C...
Page 309: ...SiUS331708EA Wiring Diagrams Appendix 296 VAM1200GVJU 3D073270D...