![background image](http://html1.mh-extra.com/html/daikin/rxsq24tavju/rxsq24tavju_service-manual_2459946203.webp)
SiUS331708EA
Troubleshooting by Error Code
Service Diagnosis
190
4.25 Indoor Blower Does Not Have Required Parameters to
Function
Error Code
C6-02
Applicable
Models
FXTQ-TA
Outline
Indoor units perform required settings for control on the fan motor, but if the minimum required
settings are not made then information indicating as such will be included among the periodic
control status information.
Error is issued when the information shows abnormality.
Error Decision
Conditions
If the parameter information shows abnormality, it will be deemed abnormal operation.
At that point, parameter settings when initializing the fan motor will be implemented from the
beginning.
Error Reset
Conditions
If the parameter information is normal, the error will be cleared.
Supposed
Causes
Locked motor rotor condition
Corrective
Actions
Check for locked rotor condition.
Replace the indoor unit PCB or motor.
Summary of Contents for RXSQ24TAVJU
Page 1: ...Service Manual SiUS331708EA RXSQ24 36 48 60TAVJU Heat Pump 60 Hz...
Page 290: ...Wiring Diagrams SiUS331708EA 277 Appendix RXSQ48TAVJU 3D109546A...
Page 291: ...SiUS331708EA Wiring Diagrams Appendix 278 RXSQ60TAVJU 3D109547A...
Page 295: ...SiUS331708EA Wiring Diagrams Appendix 282 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 298: ...Wiring Diagrams SiUS331708EA 285 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 300: ...Wiring Diagrams SiUS331708EA 287 Appendix FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU 3D110467B...
Page 301: ...SiUS331708EA Wiring Diagrams Appendix 288 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Page 302: ...Wiring Diagrams SiUS331708EA 289 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 303: ...SiUS331708EA Wiring Diagrams Appendix 290 FXAQ07 09 12 18 24PVJU 3D075354C...
Page 309: ...SiUS331708EA Wiring Diagrams Appendix 296 VAM1200GVJU 3D073270D...