Service Mode
SiUS331708EA
37
Remote Controller
Indoor Unit Status
FLOAT
Float switch OPEN/CLOSE
T1/T2
T1/T2 input from outside OPEN/CLOSE
Th1
Suction air thermistor
Th2
Heat exchanger liquid pipe thermistor
Th3
Heat exchanger gas pipe thermistor
Th4
Discharge air thermistor
Th5
—
Th6
—
Outdoor Unit Status
Unit No.
Select the unit number you want to check.
FAN step
Fan tap
COMP
Compressor power supply frequency (Hz)
EV1
Degree that electronic expansion valve is open (pulse)
SV1
Solenoid valve ON/OFF
Th1
—
Th2
—
Th3
—
Th4
—
Th5
—
Th6
—
Forced Defrost
Forced defrost ON
Enables the forced defrost operation.
Forced defrost OFF
Disables the forced defrost operation.
Error Display
Display Error ON
Displays the error on the screen.
Display Error OFF
Displays neither errors nor warnings.
Display Warning ON
Displays a warning on the screen if an error occurs.
Display Warning OFF
No warning is displayed.
Swap Unit No.
Current Unit No.
A unit number can be transferred to another.
Transfer Unit No.
Addressed Sensor
Value
Unit No.: 0 - 15
Select the unit number you want to check.
Code
00
:
01
:
02
:
03
:
04
:
05
:
06
:
07
:
08
:
09
:
30: (
∗
4)(
∗
7)
31: (
∗
4)(
∗
5)
32: (
∗
4)(
∗
5)
33: (
∗
4)
34: (
∗
4)(
∗
5)
35: (
∗
4)(
∗
6)
Remote controller thermistor (°F)
Suction air thermistor (°F)
Heat exchanger liquid pipe thermistor (°F)
Heat exchanger gas pipe thermistor (°F)
Indoor unit address No.
Outdoor unit address No.
Branch selector unit address No.
Zone control address No.
Cooling/Heating batch address No.
Demand/low-noise address No.
Displays thermostat step 1 ON/OFF.
Thermostat step 1 OFF: 00
Thermostat step 1 ON: 01
Displays the heat demand that CXTQ-TA is currently sending to
the gas furnace (%).
Displays the fan demand that CXTQ-TA is currently sending to
the gas furnace (%).
Current status of heat pump ON/OFF for CXTQ-TA
HP OFF: 00
HP ON: 01
Current status of gas combustion heating
Displays current heat actual status (%).
Current airflow of the fan
Displays current airflow (CFM).
Data
The corresponding data will be displayed, based on the unit
number and code selected.
Maintenance Menu
Item 2
Remarks
Summary of Contents for RXSQ24TAVJU
Page 1: ...Service Manual SiUS331708EA RXSQ24 36 48 60TAVJU Heat Pump 60 Hz...
Page 290: ...Wiring Diagrams SiUS331708EA 277 Appendix RXSQ48TAVJU 3D109546A...
Page 291: ...SiUS331708EA Wiring Diagrams Appendix 278 RXSQ60TAVJU 3D109547A...
Page 295: ...SiUS331708EA Wiring Diagrams Appendix 282 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 298: ...Wiring Diagrams SiUS331708EA 285 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 300: ...Wiring Diagrams SiUS331708EA 287 Appendix FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU 3D110467B...
Page 301: ...SiUS331708EA Wiring Diagrams Appendix 288 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Page 302: ...Wiring Diagrams SiUS331708EA 289 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 303: ...SiUS331708EA Wiring Diagrams Appendix 290 FXAQ07 09 12 18 24PVJU 3D075354C...
Page 309: ...SiUS331708EA Wiring Diagrams Appendix 296 VAM1200GVJU 3D073270D...