Field Settings from Remote Controller
Field Settings and Test Operation
102
Thermostat Switching
Differential value during thermostat ON/OFF control can be changed.
Airflow Setting when Heating Thermostat is OFF
This setting is used to set airflow when heating thermostat is OFF.
∗
When thermostat OFF airflow volume up mode is used, careful consideration is required before deciding
installation location.
Setting of Operation Mode to AUTO
This setting makes it possible to change differential values for mode selection while in automatic operation mode.
The automatic operation mode setting is made by the use of the "Operation Mode Selector" button.
Auto Restart after Power Failure Reset
For the air conditioners with no setting for the function, the units will be left in the stop condition when the power
supply is reset automatically after power failure reset or the main power supply is turned ON again after once
turned OFF. However, for the air conditioners with the setting (same as factory setting), the units may start
automatically after power failure reset or the main power supply turned ON again (return to the same operation
condition as that of before power failure).
For the above reasons, when the unit is set enabling to utilize “Auto restart function after power failure reset”,
utmost care should be paid for the occurrence of the following situation.
Airflow when Cooling Thermostat is OFF
This is used to set airflow to "LL airflow" when cooling thermostat is OFF.
Mode No.
First Code No.
Second Code No.
Contents
12 (22)
2
01
1°C (1.8°F)
02
0.5°C (0.9°F)
Mode No.
First Code No.
Second Code No.
Contents
12 (22)
3
01
LL tap
02
Set fan speed
03
OFF
Mode No.
First Code No.
Second Code No.
01
02
03
04
05
06
07
08
12 (22)
4
0°C
(0°F)
1°C
(1.8°F)
2°C
(3.6°F)
3°C
(5.4°F)
4°C
(7.2°F)
5°C
(9.0°F)
6°C
(10.8°F)
7°C
(12.6°F)
Mode No.
First Code No.
Second Code No.
Contents
12 (22)
5
01
Not equipped
02
Equipped
Caution The air conditioner starts operation suddenly after power failure reset or
when the main power supply is turned on again. Consequently, the user
might be surprised and wonder why this has happened. In service work, for
example, turning off the main power switch while the unit is in operation,
and turning on the switch again after the work is completed start unit
operation (the fan rotates).
Mode No.
First Code No.
Second Code No.
Contents
12 (22)
6
01
LL tap
02
Set fan speed
03
OFF
Summary of Contents for RXSQ24TAVJU
Page 1: ...Service Manual SiUS331708EA RXSQ24 36 48 60TAVJU Heat Pump 60 Hz...
Page 290: ...Wiring Diagrams SiUS331708EA 277 Appendix RXSQ48TAVJU 3D109546A...
Page 291: ...SiUS331708EA Wiring Diagrams Appendix 278 RXSQ60TAVJU 3D109547A...
Page 295: ...SiUS331708EA Wiring Diagrams Appendix 282 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 298: ...Wiring Diagrams SiUS331708EA 285 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 300: ...Wiring Diagrams SiUS331708EA 287 Appendix FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU 3D110467B...
Page 301: ...SiUS331708EA Wiring Diagrams Appendix 288 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Page 302: ...Wiring Diagrams SiUS331708EA 289 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 303: ...SiUS331708EA Wiring Diagrams Appendix 290 FXAQ07 09 12 18 24PVJU 3D075354C...
Page 309: ...SiUS331708EA Wiring Diagrams Appendix 296 VAM1200GVJU 3D073270D...