![background image](http://html1.mh-extra.com/html/daikin/rxsq24tavju/rxsq24tavju_service-manual_2459946219.webp)
SiUS331708EA
Troubleshooting by Error Code
Service Diagnosis
206
4.34 Outdoor Fan Motor Abnormality
Error Code
E7
Applicable
Models
All outdoor units
Method of Error
Detection
The fan motor circuit error is detected based on the rotation frequency detected by Hall IC during
the fan motor operation.
Error Decision
Conditions
In the condition of fan motor rotation, the number of rotation is below the fixed number for more
than 6 seconds. (System down is caused by 4 times of detection.)
Supposed
Causes
Defective fan motor
Defect or connection error of the connectors/ harness between the fan motor and PCB
The fan can not rotate due to obstruction of foreign matter.
Clear condition: Continue normal operation for 5 minutes
Missing phase L1 and missing phase N
Summary of Contents for RXSQ24TAVJU
Page 1: ...Service Manual SiUS331708EA RXSQ24 36 48 60TAVJU Heat Pump 60 Hz...
Page 290: ...Wiring Diagrams SiUS331708EA 277 Appendix RXSQ48TAVJU 3D109546A...
Page 291: ...SiUS331708EA Wiring Diagrams Appendix 278 RXSQ60TAVJU 3D109547A...
Page 295: ...SiUS331708EA Wiring Diagrams Appendix 282 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 298: ...Wiring Diagrams SiUS331708EA 285 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 300: ...Wiring Diagrams SiUS331708EA 287 Appendix FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU 3D110467B...
Page 301: ...SiUS331708EA Wiring Diagrams Appendix 288 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Page 302: ...Wiring Diagrams SiUS331708EA 289 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 303: ...SiUS331708EA Wiring Diagrams Appendix 290 FXAQ07 09 12 18 24PVJU 3D075354C...
Page 309: ...SiUS331708EA Wiring Diagrams Appendix 296 VAM1200GVJU 3D073270D...