Troubleshooting by Error Code
SiUS331708EA
169
Service Diagnosis
4.8.2 Indoor Fan Motor Abnormality (FXSQ54TA, FXMQ15-54PB Models)
Error Code
A6
Applicable
Models
FXSQ54TA, FXMQ15-54PB
Method of Error
Detection
Error from the current flow on the fan PCB
Error from the rotation speed of the fan motor in operation
Error from the position signal of the fan motor
Error from the current flow on the fan PCB when the fan motor starting operation
Error Decision
Conditions
An overcurrent flows.
The rotation speed is less than a certain level for 6 seconds.
A position error in the fan rotor continues for 5 seconds or more.
Supposed
Causes
Clogging of a foreign matter
Disconnection of the fan motor connectors (X1A and X2A)
Disconnection of the connectors between the indoor unit main PCB (A1P) and fan PCB (A2P)
Defective fan PCB (A2P)
Defective fan motor
Summary of Contents for RXSQ24TAVJU
Page 1: ...Service Manual SiUS331708EA RXSQ24 36 48 60TAVJU Heat Pump 60 Hz...
Page 290: ...Wiring Diagrams SiUS331708EA 277 Appendix RXSQ48TAVJU 3D109546A...
Page 291: ...SiUS331708EA Wiring Diagrams Appendix 278 RXSQ60TAVJU 3D109547A...
Page 295: ...SiUS331708EA Wiring Diagrams Appendix 282 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 298: ...Wiring Diagrams SiUS331708EA 285 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 300: ...Wiring Diagrams SiUS331708EA 287 Appendix FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU 3D110467B...
Page 301: ...SiUS331708EA Wiring Diagrams Appendix 288 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Page 302: ...Wiring Diagrams SiUS331708EA 289 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 303: ...SiUS331708EA Wiring Diagrams Appendix 290 FXAQ07 09 12 18 24PVJU 3D075354C...
Page 309: ...SiUS331708EA Wiring Diagrams Appendix 296 VAM1200GVJU 3D073270D...