SiUS331708EA
Troubleshooting by Error Code
Service Diagnosis
240
4.61 System Abnormality, Refrigerant System Address
Undefined
Error Code
UH
Applicable
Models
All indoor units
All outdoor units
Method of Error
Detection
An indoor unit without automatically set address is detected.
Error Decision
Conditions
The error decision is made as soon as the abnormality aforementioned is detected.
Supposed
Causes
Improper connection of transmission wiring between indoor-outdoor units
Defective indoor unit PCB
Defective outdoor main PCB (A1P)