SiUS331708EA
Field Settings from Remote Controller
Field Settings and Test Operation
96
Note that the control is automatically switched to the one performed only by the suction air thermistor for indoor
unit when the Second code No. is
01
during group control.
To use the remote controller thermistor during group control, select the Second code No.
02
in First code No.
6
.
Note:
When the 10(20)-6 setting is changed to
02
, several indoor units are controlled by one remote
controller thermistor, so note that the room temperature might be uneven.
Filter Cleaning Sign
Whether or not to display "Filter Cleaning" after operation of certain duration can be selected.
∗
Filter cleaning sign is not displayed when an Auto-clean Panel is connected.
Information for intelligent Touch Manager / intelligent Touch Controller (for FXZQ-TA and FXSQ-TA models)
∗
When field setting 10 (20)-6-
02
is set at the same time as 10 (20)-2-
01,02,03,
field setting 10 (20)-2 has priority.
When field setting 10 (20)-6-
01
is set at the same time as 10 (20)-2-
01,02,03,
field setting 10 (20)-6 has priority
for group connection, and 10 (20)-2 has priority for individual connection.
Time for Absence Area Detection
(For units with the infrared presence/floor sensor only)
By selecting the energy-saving operation mode in the absence, the target temperature is shifted to the energy-
saving end by 1°C (maximum 2°C) after the state of absence continues for a certain period of time.
Absent time defined for detection can be selected as follows:
• The set temperature displayed on the remote controller remains same even if the target temperature is shifted.
• As soon as people is detected while the temperature is shifted, this control will be cancelled (reset).
Mode No.
First Code No. Second Code No.
Contents
10 (20)
6
01
Remote controller thermostat control is not permitted during group control.
02
Remote controller thermostat control is permitted during group control.
Mode No.
First Code No.
Second Code No.
Contents
10 (20)
3
01
Displayed
02
Not displayed
Mode No.
First Code No.
Second Code No.
Contents
10 (20)
5
01
Only indoor unit sensor value (or remote controller
sensor value, if installed.)
02
Sensor values according to 10 (20)-2 and 10 (20)-6.
Mode No.
First Code No.
Second Code No.
Contents
10 (20)
7
01
30 minutes
02
60 minutes
30 (60)
∗
60 (120)
∗
31
19
28
27
26
17
21
30
29
20
18
Elapsed time of absence (min.)
Set temperature (˚C)
Human detection
Cooling (at 28˚C)
Heating (at 20˚C)
State of absence
∗
The values in parentheses represent the time
when Second code No. is "02."
Summary of Contents for RXSQ24TAVJU
Page 1: ...Service Manual SiUS331708EA RXSQ24 36 48 60TAVJU Heat Pump 60 Hz...
Page 290: ...Wiring Diagrams SiUS331708EA 277 Appendix RXSQ48TAVJU 3D109546A...
Page 291: ...SiUS331708EA Wiring Diagrams Appendix 278 RXSQ60TAVJU 3D109547A...
Page 295: ...SiUS331708EA Wiring Diagrams Appendix 282 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 298: ...Wiring Diagrams SiUS331708EA 285 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 300: ...Wiring Diagrams SiUS331708EA 287 Appendix FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU 3D110467B...
Page 301: ...SiUS331708EA Wiring Diagrams Appendix 288 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Page 302: ...Wiring Diagrams SiUS331708EA 289 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 303: ...SiUS331708EA Wiring Diagrams Appendix 290 FXAQ07 09 12 18 24PVJU 3D075354C...
Page 309: ...SiUS331708EA Wiring Diagrams Appendix 296 VAM1200GVJU 3D073270D...