Field Settings from Remote Controller
SiUS331708EA
107
Field Settings and Test Operation
Humidification when Heating Thermostat is OFF
Setting to Equipped turns ON the humidifier if suction air temperature is 20°C (68°F) or above and turns OFF the
humidifier if suction air temperature is 18°C (64.4°F) or below when the heating thermostat is OFF.
Setting of Direct Duct Connection
This is used when "fresh air intake kit equipped with fan" is connected. The indoor fan carries out residual
operation for one minute after the thermostat is stopped. (For the purpose of preventing dust on the air filter from
falling off.)
Interlocked Operation between Humidifier and Drain Pump
This is used to interlock the humidifier with the drain pump. When water is drained out of the unit, this setting is
unnecessary.
Individual Setting of Ventilation
This is set to perform individual operation of Energy recovery ventilator using the remote controller/central unit
when Energy recovery ventilator is built in.
(Switch only when Energy recovery ventilator is built in.)
Display of Contact Center (For BRC1E73 only)
You can turn OFF the display of "DAIKIN Contact Center" as "Contact for Service Display."
Display of Error Codes on the Remote Controller (For BRC1E73 only)
Error code (four digits) is displayed for limited products.
Select two-digit display if four-digit display is not preferred.
Mode No.
First Code No.
Second Code No.
Contents
15 (25)
1
01
Not equipped
02
Equipped
Mode No.
First Code No.
Second Code No.
Contents
15 (25)
2
01
Not equipped
02
Equipped
Mode No.
First Code No.
Second Code No.
Contents
15 (25)
3
01
Not interlocked
02
Interlocked
Mode No.
First Code No.
Second Code No.
Contents
15 (25)
5
01
Not individual
02
Individual
Mode No.
First Code No.
Second Code No.
Contents
1b
3
01
Displayed
02
Not displayed
Mode No.
First Code No.
Second Code No.
Contents
1b
4
01
—
02
Two-digit display
03
—
04
Four-digit display
Summary of Contents for RXSQ24TAVJU
Page 1: ...Service Manual SiUS331708EA RXSQ24 36 48 60TAVJU Heat Pump 60 Hz...
Page 290: ...Wiring Diagrams SiUS331708EA 277 Appendix RXSQ48TAVJU 3D109546A...
Page 291: ...SiUS331708EA Wiring Diagrams Appendix 278 RXSQ60TAVJU 3D109547A...
Page 295: ...SiUS331708EA Wiring Diagrams Appendix 282 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 298: ...Wiring Diagrams SiUS331708EA 285 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 300: ...Wiring Diagrams SiUS331708EA 287 Appendix FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU 3D110467B...
Page 301: ...SiUS331708EA Wiring Diagrams Appendix 288 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Page 302: ...Wiring Diagrams SiUS331708EA 289 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 303: ...SiUS331708EA Wiring Diagrams Appendix 290 FXAQ07 09 12 18 24PVJU 3D075354C...
Page 309: ...SiUS331708EA Wiring Diagrams Appendix 296 VAM1200GVJU 3D073270D...