![background image](http://html1.mh-extra.com/html/daikin/rxsq24tavju/rxsq24tavju_service-manual_2459946108.webp)
Field Settings from Remote Controller
SiUS331708EA
95
Field Settings and Test Operation
FXTQ-TA, CXTQ-TA
When the Second Code No. is set to
02
, room temperature is controlled by the remote sensor thermistor.
When the Second Code No. is set to
03
, room temperature is controlled by the remote controller thermistor.
When the unit is equipped with an infrared presence/floor sensor:
∗
Refer to
Compensating the temperature around people
on page 100.
Mode No.
First Code No.
Second Code No.
Contents
10 (20)
2
01
—
02
Remote sensor thermistor
03
Remote controller thermistor
20
22
24
26
28
30
32
34
36
21
19
17
23
25
27
29
31
33
35
37
(˚C)
(˚C)
14
16
18
20
22
24
26
28
30
32
(˚C)
(˚C)
68
71.6
75.2
78.8
82.4
86
89.6
93.2
96.8
57.2
60.8
64.4
68
71.6
75.2
78.8
82.4
86
89.6
(˚F)
(˚F)
14
16
18
20
22
24
26
28
30
32
34
66.2
62.6
69.8 73.4
77
80.6 84.2 87.8 91.4
95
98.6
(˚F)
(˚F)
57.2 60.8
64.4
68
71.6 75.2
78.8 82.4
86
89.6 93.2
In cooling
In heating
Suction air temperature
Suction air temperature
Suction air
thermistor
Suction air
thermistor
Suction air
thermistor
Suction air
thermistor
Suction air
thermistor
Suction air
thermistor
Suction air
thermistor
Suction air
thermistor
Remote controller
thermistor
Remote controller
thermistor
Remote controller
thermistor
Remote controller
thermistor
Set temper
ature
Set temper
ature
Mode No.
Second Code No.
10 (20)
2
01
02
02
02
02
03
11 (21)
8
01
01
02
03
04
01
The thermistor to be used
Remote controller thermistor
9
—
—
—
—
9
Suction air thermistor
9
9
9
9
9
—
Infrared presence/floor sensor
—
—
9
9
9
—
First Code No.
The infrared
presence/floor
sensor is not used
Priority given to
the suction air
temperature (
∗
)
Only the remote
controller thermistor
is used
Priority given to the
floor temperature (
∗
)
Only the suction air
thermistor is used
Standard setting
(Factory setting)
Summary of Contents for RXSQ24TAVJU
Page 1: ...Service Manual SiUS331708EA RXSQ24 36 48 60TAVJU Heat Pump 60 Hz...
Page 290: ...Wiring Diagrams SiUS331708EA 277 Appendix RXSQ48TAVJU 3D109546A...
Page 291: ...SiUS331708EA Wiring Diagrams Appendix 278 RXSQ60TAVJU 3D109547A...
Page 295: ...SiUS331708EA Wiring Diagrams Appendix 282 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 298: ...Wiring Diagrams SiUS331708EA 285 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 300: ...Wiring Diagrams SiUS331708EA 287 Appendix FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU 3D110467B...
Page 301: ...SiUS331708EA Wiring Diagrams Appendix 288 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Page 302: ...Wiring Diagrams SiUS331708EA 289 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 303: ...SiUS331708EA Wiring Diagrams Appendix 290 FXAQ07 09 12 18 24PVJU 3D075354C...
Page 309: ...SiUS331708EA Wiring Diagrams Appendix 296 VAM1200GVJU 3D073270D...