Refrigerant Circuit
Refrigerant Circuit
10
1.1.2 RXSQ48TAVJU
No. in
piping
diagram
Symbol
Name
Function
(1)
M1C
Inverter compressor
Inverter compressor is operated on frequencies between 15 rps and 109 rps by using the
inverter.
(2)
M1F
Inverter fan
Because the system is of an air heat exchange type, the fan is operated at 8-step rotation
speed by using the inverter.
(3)
Y1E
Electronic expansion valve
(Main)
While in heating operation, PI control is applied to keep the outlet superheated degree of
air heat exchanger constant.
(4)
Y1S
Four way valve
Used to switch the operation mode between cooling and heating.
(5)
Y3S
Solenoid valve (Injection)
Used to protect discharge temperature of compressor.
(6)
S1NPH High pressure sensor
Used to detect high pressure.
(7)
S1NPL
Low pressure sensor
Used to detect low pressure.
(8)
S1PH
High pressure switch
In order to prevent the increase of high pressure when an error occurs, this switch is
activated at high pressure of 4.0 MPa (580 psi) or more to stop the compressor operation.
(9)
—
Fusible plug
In order to prevent the increase of pressure when abnormal heating is caused by fire or
others, the fusible part of the plug is molten at a temperature of 70 ~ 75°C (158 ~ 167°F) to
release the pressure into the atmosphere.
(10)
—
Pressure regulating valve 1
(Receiver to discharge pipe)
This valve opens at a pressure of 4.0 MPa (580 psi) or more for prevention of pressure
increase, thus resulting in no damage of functional parts due to the increase of pressure in
transportation or storage.
(11)
R1T
Thermistor (Outdoor air)
Used to detect outdoor air temperature, correct discharge pipe temperature, and for other
purposes.
(12)
R2T
Thermistor (Discharge pipe)
Used to detect discharge pipe temperature, make the temperature protection control of
compressor, and for other purposes.
(13)
R3T
Thermistor (Suction pipe 1)
Used to detect suction pipe temperature, keep the suction superheated degree constant in
heating operation, and for other purposes.
(14)
R4T
Thermistor (Heat exchanger
deicer)
Used to detect liquid pipe temperature of air heat exchanger, determine defrost operation,
and for other purposes.
(15)
R5T
Thermistor (Suction pipe 2)
Used to the calculation of an internal temperature of compressor, etc.
(16)
R7T
Thermistor (Liquid pipe)
Used to detect refrigerant overcharge in check operation, and for other purposes.
(17)
FINTH
Thermistor (Radiation fin)
• Used for outdoor fan speed control.
• Used for inverter radiation fin temperature control.
Summary of Contents for RXSQ24TAVJU
Page 1: ...Service Manual SiUS331708EA RXSQ24 36 48 60TAVJU Heat Pump 60 Hz...
Page 290: ...Wiring Diagrams SiUS331708EA 277 Appendix RXSQ48TAVJU 3D109546A...
Page 291: ...SiUS331708EA Wiring Diagrams Appendix 278 RXSQ60TAVJU 3D109547A...
Page 295: ...SiUS331708EA Wiring Diagrams Appendix 282 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 298: ...Wiring Diagrams SiUS331708EA 285 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 300: ...Wiring Diagrams SiUS331708EA 287 Appendix FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU 3D110467B...
Page 301: ...SiUS331708EA Wiring Diagrams Appendix 288 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Page 302: ...Wiring Diagrams SiUS331708EA 289 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 303: ...SiUS331708EA Wiring Diagrams Appendix 290 FXAQ07 09 12 18 24PVJU 3D075354C...
Page 309: ...SiUS331708EA Wiring Diagrams Appendix 296 VAM1200GVJU 3D073270D...