SiUS331708EA
Field Settings from Remote Controller
Field Settings and Test Operation
104
Swing Pattern Settings
(For units with the infrared presence/floor sensor only)
Set the flap operation in swing mode.
With the factory swing, flaps facing each other are synchronized to operate, and flaps placed side by side are set
to swing in an opposite direction to agitate airflow to reduce temperature irregularity.
Conventional swing operation (all direction synchronized swing) can be set onsite.
Operation of Downward Flow Flap (for FXEQ-P models)
When only the front-flow is used, sets yes/no of the swing flap operation of down-flow.
Setting of Airflow Direction Adjustment Range
Make the following airflow direction setting according to the respective purpose.
∗
Some indoor unit models are not equipped with draft prevention (upward) function.
Setting of the Static Pressure Selection (for FXDQ models)
CFM Table Setting (for CXTQ-TA models)
Change this setting from
Standard
to
Low
when connecting CXTQ with the following rated combinations.
Once
Low
is set, the indoor airflow CFM will be equivalent to one tonnage lower for only heat pump operation.
Note:
Change this setting only for the rated combinations of indoor units above.
Mode No.
First Code No.
Second Code No.
Contents
13 (23)
2
01
All direction synchronized swing
02
—
03
Facing swing
Mode No.
First Code No.
Second Code No.
Contents
13 (23)
3
01
Equipped
02
Not equipped
Mode No.
First Code No.
Second Code No.
Contents
13 (23)
4
01
Upward (Draft prevention)
02
Standard
03
Downward (Ceiling soiling prevention)
Model No.
First Code No.
Second Code No.
Contents
13 (23)
5
01
Standard (FXDQ07-12: 10 Pa (0.04 inWG),
FXDQ18/24: 30 Pa (0.12 inWG))
02
High static pressure
(FXDQ07-12: 15 Pa (0.06 inWG),
FXDQ18/24: 45 Pa (0.18 inWG))
Combination A
Combination B
Combination C
Outdoor unit
2 ton × 1 unit
3 ton × 1 unit
4 ton × 1 unit
CXTQ
3 ton × 1 unit
4 ton × 1 unit
5 ton × 1 unit
Other indoor unit
Not applicable
Not applicable
Not applicable
Model No.
First Code No.
Second Code No.
Contents
13 (23)
5
01
Standard
02
Low
Summary of Contents for RXSQ24TAVJU
Page 1: ...Service Manual SiUS331708EA RXSQ24 36 48 60TAVJU Heat Pump 60 Hz...
Page 290: ...Wiring Diagrams SiUS331708EA 277 Appendix RXSQ48TAVJU 3D109546A...
Page 291: ...SiUS331708EA Wiring Diagrams Appendix 278 RXSQ60TAVJU 3D109547A...
Page 295: ...SiUS331708EA Wiring Diagrams Appendix 282 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 298: ...Wiring Diagrams SiUS331708EA 285 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 300: ...Wiring Diagrams SiUS331708EA 287 Appendix FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU 3D110467B...
Page 301: ...SiUS331708EA Wiring Diagrams Appendix 288 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Page 302: ...Wiring Diagrams SiUS331708EA 289 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 303: ...SiUS331708EA Wiring Diagrams Appendix 290 FXAQ07 09 12 18 24PVJU 3D075354C...
Page 309: ...SiUS331708EA Wiring Diagrams Appendix 296 VAM1200GVJU 3D073270D...