SiUS331708EA
Outline of Control (Indoor Unit)
Functions and Control
86
6.17.3 Economizer
When indoor and outdoor air temperatures are reversed, the compressor is stopped to let in the
outdoor air to save energy.
This operation is called economizer operation, and the equipment to detect indoor and outdoor air
temperatures and open and close the damper to perform this operation is called an economizer.
The economizer detects indoor and outdoor air temperatures, informs the air conditioner that the
economizer operation is ready, and opens and closes the damper.
The indoor unit stops the outdoor unit when it receives a signal from the economizer and performs
air supply operation.
When the indoor air temperature is cooled down sufficiently by the economizer operation, and it is
no longer necessary (thermostat OFF), the indoor unit outputs a signal to the economizer to close
the damper.
Thermostat ON signal
Operation
Indoor unit ON signal
∗
1. Thermostat ON signal: A signal to turn ON the indoor unit thermostat and allow the economizer
to open the damper.
It turns ON the relay on the X2M-ECONOMIZER2 on the PCB.
∗
2. External input ON is an input signal to the X1M-ECONOMIZER1 terminal on the PCB.
∗
3. Refer to
Optional Kit Setting (UV lamp + Humi Economizer) (for FXTQ-TA and CXTQ-TA
models)
∗
4. Remote control ON signal: Contact output which shows the operating status of the indoor unit.
This signal turns on the relay X2M-CONTROL ON/OFF on the PCB.
&
Other conditions
Stop the thermostat ON signal (
∗
1)
to the economizer.
Transfer the thermostat ON signal (
∗
1) to
the economizer.
•
Cooling mode
•
When the thermostat is ON
&
•
Cooling mode
•
When the thermostat is ON
•
External output: ON (
∗
2)
OR
•
Tcon
≤
Ts’ continues for 1
minute
•
Economizer set time (
∗
3):
Free cooling only
&
•
Economizer set time (
∗
3)
≠
Free cooling only
•
Thermostat ON continues for
the economizer set time (
∗
3)
•
Air conditioner operation is
stopped.
•
The remote controller indicates
cooling operation.
•
The fan tap follows the remote
controller.
•
Air conditioner operation is
started.
•
The remote controller
indicates cooling operation.
•
The fan tap follows the
remote controller.
Normal operation
Other
conditions
Free cooling
Free cooling & Mech Cooling
Remote control ON
Remote control OFF
Stop indoor unit ON signal (
∗
4)
to the economizer.
Transfer indoor unit ON signal (
∗
4) to the
economizer.
Summary of Contents for RXSQ24TAVJU
Page 1: ...Service Manual SiUS331708EA RXSQ24 36 48 60TAVJU Heat Pump 60 Hz...
Page 290: ...Wiring Diagrams SiUS331708EA 277 Appendix RXSQ48TAVJU 3D109546A...
Page 291: ...SiUS331708EA Wiring Diagrams Appendix 278 RXSQ60TAVJU 3D109547A...
Page 295: ...SiUS331708EA Wiring Diagrams Appendix 282 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 298: ...Wiring Diagrams SiUS331708EA 285 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 300: ...Wiring Diagrams SiUS331708EA 287 Appendix FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU 3D110467B...
Page 301: ...SiUS331708EA Wiring Diagrams Appendix 288 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Page 302: ...Wiring Diagrams SiUS331708EA 289 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 303: ...SiUS331708EA Wiring Diagrams Appendix 290 FXAQ07 09 12 18 24PVJU 3D075354C...
Page 309: ...SiUS331708EA Wiring Diagrams Appendix 296 VAM1200GVJU 3D073270D...