Troubleshooting by Error Code
SiUS331708EA
195
Service Diagnosis
Troubleshooting
Note:
∗
1. Connector
Diagnosis procedure 2
Infrared floor sensor error
(Error code
CE-02
)
Turn off the power and then reconnect.
Check infrared floor sensor output; refer to sensor
and address data No. 26.
Connect the connector correctly.
Connect the connector correctly.
NO
YES
YES
NO
YES
YES
Is the
connection of the
sensor connector
normal?
Normal.
NO
Displays
"--" by the above
verification
method.
Normal.
NO
Displays
CE-02
again or "--" for
sensor and
address data.
Replace the sensor.
Is the
connection of
the connector on
infrared floor sensor PCB
(A3P) and the connector
(
∗
1) on A2P
normal?
Model
Connector for infrared floor sensor PCB
FXFQ-T
X2A
FXUQ-P
X81A
Summary of Contents for RXSQ24TAVJU
Page 1: ...Service Manual SiUS331708EA RXSQ24 36 48 60TAVJU Heat Pump 60 Hz...
Page 290: ...Wiring Diagrams SiUS331708EA 277 Appendix RXSQ48TAVJU 3D109546A...
Page 291: ...SiUS331708EA Wiring Diagrams Appendix 278 RXSQ60TAVJU 3D109547A...
Page 295: ...SiUS331708EA Wiring Diagrams Appendix 282 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 298: ...Wiring Diagrams SiUS331708EA 285 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 300: ...Wiring Diagrams SiUS331708EA 287 Appendix FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU 3D110467B...
Page 301: ...SiUS331708EA Wiring Diagrams Appendix 288 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Page 302: ...Wiring Diagrams SiUS331708EA 289 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 303: ...SiUS331708EA Wiring Diagrams Appendix 290 FXAQ07 09 12 18 24PVJU 3D075354C...
Page 309: ...SiUS331708EA Wiring Diagrams Appendix 296 VAM1200GVJU 3D073270D...